P
u
bl
is
he
d 1
6
.2.
04
C
Universal Pressure Transmitter UniTrans
Operation of Transmitters with Display
Subject to change due to technical modifications.
© Copyright WIKA Alexander Wiegand GmbH & Co. KG / BRD
WIKA Alexander Wiegand GmbH & Co. KG · Alexander-Wiegand-Str. · 63911 Klingenberg ·
(09372) 132 - 710 · Fax - 706 · E-mail: [email protected] · www.wika.de
72
Example:
Level 100 %:
4000 mm
Density:
1 g/cm
3
Density correction:
0.9 g/cm
3
Span end point:
The span (end-point) must be re-calibrated (with or without pressure) to 4000 mm in
order to prevent a 4000 mm level tank from being overfilled.
6.5.5
Main Menu: Language
Please check the following if "Wrong Entry" appears in the Evaluation
menu:
• whether or not more than 32 value pairs are entered in the table for tank
linearization (please note: P 0 and P 31 are fixed at 0% and 100% re-
spectively)
• whether or not an existing height value was tried to be stored again
Please enter correct values.
A change or correction in the density causes a change in the span end-
point’s unit of measure (mm, m, inch, feet). The span end-point must be
re-calibrated when changing the medium to be measured (due to a
change in density).
4000 mm 1 g/cm
3
⋅
0.9 g/cm
3
--------------------------------------------------
4444
mm
=
Important
MAIN MENU
LANGUAGE
LANGUAGE
OPTIONS
LANGUAGE
GERMAN
LANGUE
FRANCAIS
LANGUAGE
ENGLISH
All displays will
be in German
All displays will
be in English
All displays will
be in French
IDIOMA
ESPANOL
All displays will
be in Spanish
LINGUA
ITALIANO
All displays will
be in Italian