WIKA operating instructions models OLS-C01 ... OLS-C05, OLS-F1, OLS-5200
13
EN
8.1 Dismounting
Only disconnect the measuring instrument once the system has been depressurised and
the power disconnected! If necessary, the measuring line must have strain relief.
8.2 Return
Wash or clean the dismounted switch before returning it, in order to protect personnel and
the environment from exposure to residual media.
Information on returns can be found under the heading “Service” on our local
website.
8.3 Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an environmentally
compatible way and in accordance with the country-specific waste disposal regulations.
9. Specifications
General data
Measurement accuracy
±2 mm
Mounting position
as required
Visual indication of the switching
status
1 LED
Model OLS-C05: With trimmer option, internal LED to
ease adjustment
Not with models OLS-C02, OLS-5200, OLS-F1
Design data
Responsiveness
Preset for the detection of aqueous media and oils
Model OLS-C04: Also for the detection of refrigerants
Medium temperature
■
Models OLS-C01, OLS-C02
■
Models OLS-C04, OLS-F1
■
Model OLS-C05
■
Model OLS-5200
-30 ... +100 °C
-40 ... +100 °C
-40 ... +170 °C
-40 ... +130 °C
Ambient temperature
■
Models OLS-C01, OLS-C02, OLS-F1
■
Model OLS-C04
■
Models OLS-C05, OLS-5200
-25 ... +70 °C
-30 ... +70 °C
-30 ... +80 °C
Operating pressure
0 … 2.5 MPa (0 … 25 bar)
Model OLS-C04: 0 … 4 MPa (0 … 40 bar)