6 Set up with the display and adjustment module
WIKA Operating Instructions - Process pressure transmitter CPT-2x
after the other and provided with the correct parameters. If possible,
go through the items in the given sequence.
The procedure is described below.
The following submenu points are available:
The submenu points are described below.
6.5.1 Setup
In this menu item you activate/deactivate the slave sensor for elec-
tronic differential pressure and select the application.
CPT-2x can be used for process pressure and level measurement.
Default setting is process pressure measurement. The mode can be
changed in this adjustment menu.
If you have connected
no slave sensor, you confirm this with "
Deac-
tivate
".
Depending on the selected application, different subchapters in the
following adjustment steps are important. There you can find the
individual adjustment steps.
Enter the requested parameters via the appropriate keys, save your
settings with
[OK]
and jump to the next menu item with the
[ESC]
and
the
[->]
key.
In this menu item, the adjustment units of the instrument are deter-
mined. The selection determines the unit displayed in the menu items
"
Min. adjustment (Zero)
" and "
Max. adjustment (Span)
".
Unit of measurement:
If the level should be adjusted in a height unit, the density of the me-
dium must also be entered later during the adjustment.
In addition, the temperature unit of the instrument is specified. The
selection determines the unit displayed in menu items "
Peak value,
temperature
" and "in the variables of the digital output signal".
Temperature unit:
Application
Units