Installation and user manual 

UNICOM 300 N531

 

 

DDN5006GHEN/04-2021/rev.B1      

 

17

 

 

6  Activation of the modem, TCP and NTP services 

6.1  Activation of the modem 

The modem can be turned on by pressing switch SW1 for at least 4 seconds until the NETWORK status 
LED starts flashing, SW1 can then be released.  
 
If switch SW1 is operated again, the modem will log in again, turning the modem off and on again. This 
is apparent as the NETWORK status LED (see Chapter 5) is off for a short time.  
 

6.2  Activation of TCP services 

If the TCP server function is activated in UNICOM 300, the device will log on to GPRS/LTE cat. 1 when 
the modem is switched on.  
Before the TCP server is activated an IP-address will be assigned to UNICOM 300. If logging on to 
GPRS/LTE cat. 1, or activating the TCP server fails, this will be repeated up to four times. If after four 
attempts the registration is not successful, UNICOM 300 will be registered on the GSM network, 
(NETWORK status LED will flash) but not on the GPRS/LTE cat. 1 network. The user may optionally 
initiate a re-login by means of switch SW1. 
 

6.3  Activation of NTP  

UNICOM 300 is equipped with a function to read out the NTP-time server.  When connected to this time 
server, the date and time are read out.  If NTP is activated and UNICOM 300 has been synchronized with 
the  NTP  server  in  the  last  24  hours,  then  UNICOM  MODEM's  clock  is  no  longer  synchronized  by 
monitoring data traffic.  

To activate NTP functionality, the NTP time server must be set via C92.65 and C.92.66.  In addition, the 
APN data must also be set.  

The  requested  NTP  time  is  the  GMT  time.    Through  time  zone  setting  (C.92.64)  and  with  DST 
(summer/winter time) the time is adjusted in UNICOM 300.         

When the NTP function is activated, the clock is requested once a day at approximately 00:35. 

If reading out the NTP time server does not succeed, another attempt will be made after 12 hours. 

 

6.4  Activation of FTP 

To  use  the  FTP  functionality,  the  FTP  server  data  must  be  set  (FTP  server,  FTP  user  name,  FTP 
password, FTP port). Also the APN data and the FTP interval have to be set. 

If the FTP functionality of the UNICOM 300 is activated, the UNICOM 300 will send the load profile after 
activating the datalogger. See chapter 8 for activation of the data log functions. If UNICOM 300 is placed 
as modem at UNIGAS 300 and CI module, UNICOM 300 will forward the FTP message from UNIGAS 
300. 

UNICOM  300  checks  if  the  FTP  message  arrived  correctly  on  the  server.  At  first  installation  or  at  not 
correctly sending  the FTP  message,  UNICOM  300 or UNIGAS  300  will, when  sending  the (next)  FTP 
message, send the data of the failed message. The data is depending on the set load profile (0.8.5) limited 
as follows: 

Setting 0.8.5: 
  5 minutes = 10 days 
10 minutes = 10 days 
15 minutes = 31 days 
30 minutes = 31 days 
60 minutes = 61 days 
         1 day = 61 days  

 

Содержание UNICOM 300

Страница 1: ...Installation and user manual type N531 Mains operated UNICOM 300...

Страница 2: ...ck of this manual or simply enquire Wigersma Sikkema B V Passing this manual to third parties and its duplication in full or in part are only allowed with written permission from Wigersma Sikkema B V...

Страница 3: ...services 17 6 3 Activation of NTP 17 6 4 Activation of FTP 17 7 Function Check 18 7 1 Checking the system status by means of the status LEDs 18 7 2 Checking the system status data logger 18 8 Configu...

Страница 4: ...tmosphere Two microprocessors provide several functions including pulse registration readout of an encoder counter processing and storage of data data logging communication of this data via 2G 4G time...

Страница 5: ...ctly whether there are any loose wires and whether the cable gland has been properly tightened Also check to see whether the Ex protective cover 2 see figure 1 has been put in place 4 The mains or ext...

Страница 6: ...tenna during installation If the cable is damaged the antenna should be replaced as a whole with a non damaged unit 1 Mounting position for optional back up battery 2 Ex protective cover for the conne...

Страница 7: ...ers read an encoder counter in a third counter and log it in an interval logger Mains operated UNICOM 300 can transmit the incoming pulses or encoder counter reading to two pulse outputs Mains operate...

Страница 8: ...uts are already configured from factory and it is possible that the corresponding cable s is are mounted The back up battery is not connected This has not been done for reasons of battery life Connect...

Страница 9: ...open Closing the housing must be done with caution The hinge of the lid has some tolerance so that the seal in the lid when closed can connect to the underside of the housing Make sure that when clos...

Страница 10: ...5006GHEN 04 2021 rev B1 10 4 6 Components Figure 4 1 Status LED logger 2 Programming switch SW5 3 LED power supply 4 Backup battery optional 5 UNICOM 300 power connector 6 Status LED encoder 7 Switch...

Страница 11: ...r manual UNICOM 300 N531 DDN5006GHEN 04 2021 rev B1 11 4 7 Components inside cover Figure 5 1 Mini SIM card holder 2 Label for terminal connections and or SIM card 3 Connectors for battery packs 4 SW3...

Страница 12: ...ds which are not used must be closed with the enclosed sealing caps 1 Cable gland for mains voltage 2 Sealing cap for cable gland 3 Cable gland for back up battery 4 24 VDC connection 15 VDC 32 VDC 5...

Страница 13: ...and tight and fit the Ex protection cap fig 6 7 5 Connect the power supply for UNIGAS 300 Fig 6 6 optional 6 Connect UNICOM 300 to the 230 VAC or 24 VDC mains supply UNICOM 300 switches on when the po...

Страница 14: ...that the threaded end is properly connected A different color coding for the serial wire connection may apply for UNIGAS see Appendix 5 4 11 Function switches mains operated UNICOM 300 Switch Switch...

Страница 15: ...5 Press lightly on the metal colored closure of the mini SIM holder and turn anticlockwise the mini SIM holder unlocks and falls open The mini SIM must be inserted with the gold contacts facing backwa...

Страница 16: ...ly be activated if NTP FTP and the APN are programmed If they are not programmed the function cannot be activated and the status LED INIT will flash 1x per second when pressing switch SW1 The initiali...

Страница 17: ...TP server in the last 24 hours then UNICOM MODEM s clock is no longer synchronized by monitoring data traffic To activate NTP functionality the NTP time server must be set via C92 65 and C 92 66 In ad...

Страница 18: ...Blinking 1 x per 4 seconds Registered on 4G Blinking 1 x per 2 seconds Registered on 4G TCP services Off registered on 2G CSD SIG1 GSM signal status Continuously on Main cell 92 dBm Blinking 1 x per 4...

Страница 19: ...ware UNITOOL 3 Manual initialization by SW4 see chapter 8 1 2 4 Device init as described in chapter 5 2 8 1 2 Manual encoder initialization It is possible for a user to manually start an encoder initi...

Страница 20: ...g the data logger If necessary the data logger functions of UNICOM 300 can be deactivated Deactivation can be performed using UNITOOL and setting parameter C 93 30 or by activating stock lock with SW1...

Страница 21: ...ccess the mode in which counters and registers can be read and written Security level 2a with register 2a writing of registers is possible Password 2a corresponds to the VDEW password If passwords are...

Страница 22: ...e Unit OBIS Security level Description Battery voltage MODEM mV C 90 6 Supply voltage Battery hour counter MODEM h C 6 0 Number of hours in operation Operation h C 90 13 Number of hours in operation n...

Страница 23: ...server 1 IP of DSN C 92 46 Password 2a FTP server IP address or DNS naam FTP server port number C 92 47 Password 2a FTP server port number Do not program port 0 This will result in modem errors FTP wo...

Страница 24: ...he value is on after the object has been programmed the modem will remain on regardless of which function the modem wants to turn on or off If the value is set to off the UNICOM MODEM will start the s...

Страница 25: ...OM 300 Serial number C 1 0 Serial number of the UNICOM 300 Firmware version MODEM PCB 7 0 0 2 0 Firmware version UNICOM MODEM PCB Firmware version LOGGER PCB 7 0 0 2 1 Firmware version UNICOM LOGGER P...

Страница 26: ...In this case the setting cannot be changed by the user Gas meter year of construction C 91 11 Password 2a Construction year of the gas meter When an encoder telework is used the year of construction...

Страница 27: ...ume difference function is disabled sswInpDiff C 93 39 Password 2a Channels for determining volume difference Settings for outputs Name Unit OBIS Security level Description OUT1_div pulse m3 C 94 1 SW...

Страница 28: ...Security level Description FTP filename C 91 8 Password 2a Text for display in the file name If this object is set to 00000000 the serial number of UNICOM 300 is issued in the file name This object is...

Страница 29: ...B V2 8 9 A B C D E F 10 A 4 5 6 7 C D E F 9 2 3 6 7 A B E F 8 1 3 5 7 9 B D F SW5 has been operated during writing of OBIS parameter Event 7 V3 8 9 A B C D E F 6 4 5 6 7 C D E F UNICOM 300 had no powe...

Страница 30: ...r are unusable BCC error or a encoder reading is lower than counter reading Vm3 Vm3 will not be modified Counters set 13 4 5 6 7 C D E F E 6 A counter reading has been set Alarm switch program 2 3 6 7...

Страница 31: ...witched on but not read out Stock lock 2 3 6 7 A B E F C D If stock lock is active this status bit is set Alarm NTP 1 3 5 7 9 B D F C C Set if deviation RTC clock and NTP clock is greater than C 92 95...

Страница 32: ...2 23 0 0 Vm3 3 23 0 0 Ingang 1 Encoder Puls Alarm contact Uit Alarm contact Encoder Decoder Gasmeter 7 1 0 2 14 C 91 10 C 91 11 Sw4 Sw6 Micro INP1 INP3 INP2 Encoder init Sw4 Stock lock deactivated St...

Страница 33: ...Installation and user manual UNICOM 300 N531 DDN5006GHEN 04 2021 rev B1 33 Appendix 2 Schematic display of the data structure Schematic display of the data structure UNICOM 300 datalogger...

Страница 34: ...endix 3 Wiring diagrams UNICOM 300 UNIGAS 300 A Serial connection between UNILOG 300 and UNIGAS 300 For the serial connection to UNIGAS 300 the optical connector cable is used Available lengths 0 3m N...

Страница 35: ...Installation and user manual UNICOM 300 N531 DDN5006GHEN 04 2021 rev B1 35 B Pulse connection between UNILOG 300 and UNIGAS 300 Available lengths 5m NN2647 10m NN2648...

Страница 36: ...UNILOG with a UNICOM power supply it is possible to use the cable used with the UNILOG Strip for the correct cable lengths of the 5 cores information below Green Brown White 50 mm Grey Yellow 105 mm D...

Страница 37: ...power microprocessor MSP 430 series 2 Mb EEprom memory Remote software update Yes Power supply input Two terminals for external power input 9 0 VDC 15 32 32 VDC Pnom 0 5 W Pmax 5 W 115 or 230 VAC 47...

Страница 38: ...n NTP Daylight saving time support yes Back up function logger only back up for few minutes clock running at power down or battery exchange Communication protocol IEC 1107 mode C VDEW 2 0 protocol for...

Страница 39: ...10 1 10 2 10 3 9 X X X 8 X X X X 7 X X X X 6 X X X X Reading of Encoder counter Every 5 minutes and at serial communication data read out mode and reading counter values Reading of Encoder b telegram...

Страница 40: ...DIN 43863 5 fixed Data matrix Wigersma en Sikkema Specification mounting bracket for mounting UNICOM 300 General dimensions approx 180 x 50 mm material Stainless steel Weight 0 2 kg Specification uni...

Страница 41: ...tor type Description Cable color black with M12 Male connector Cable color blue with M12 Male connector Cable color blue with optical connector UNIGAS EVC type UNIGAS 61D or UNIGAS 61E UNIGAS 61D or U...

Страница 42: ...DDN5006GHEN 04 2021 rev B1 Wigersma Sikkema B V Leigraafseweg 4 NL 6983 BP Doesburg The Netherlands TEL 31 0 313 47 19 98 info wigersma sikkema com www wigersma sikkema com...

Отзывы: