![Wieland samos PRO COMPACT Скачать руководство пользователя страница 114](http://html1.mh-extra.com/html/wieland/samos-pro-compact/samos-pro-compact_manual_979665114.webp)
Appendix
Wieland Electric GmbH | BA000966 | 08/2017 [8151]
114
Error No.
Error type Logbook message
System behavior
Remedy
240Bxxxx
Info
Output error rectified
System continues to
run
-
240Dxxxx
Error
Error in system configuration
System stop; voltage
OFF-ON required
Reload system confi-
guration and restart
240Exxxx
Warning
Problem with forcing
System continues to
run
Restart forcing
240Fxxxx
Warning
Problem with forcing
System continues to
run
Restart forcing
2410xxxx
Warning
Problem with forcing
System continues to
run
Restart forcing
2411xxxx
Warning
Problem with forcing
System continues to
run
Restart forcing
2412xxxx
Warning
Problem with forcing
System continues to
run
Restart forcing
2413xxxx
Warning
Problem with forcing
System continues to
run
Restart forcing
2414xxxx
Warning
Problem with forcing
System continues to
run
Restart forcing
2415xxxx
Warning
Problem with forcing
System continues to
run
Restart forcing
2416xxxx
Warning
Connection problem
System stop
Restart
2417xxxx
Warning
Forcing time expired
System continues to
run
-
2418xxxx
Error
Internal error
System stop; voltage
OFF-ON required
Restart or make
complaint
2419xxxx
Warning
Error in system configuration.
System continues to
run
Reload system confi-
guration
241Axxxx
Warning
Output error
System continues to
run
Check outputs
241B0001
Warning
Stuck-at-high at Q1
System continues to
run
Check outputs
241B0002
Warning
Stuck-at-high at Q2
System continues to
run
Check outputs
241B0003
Warning
Stuck-at-high at Q3
System continues to
run
Check outputs
241B0004
Warning
Stuck-at-high at Q4
System continues to
run
Check outputs
241B0005
Warning
Stuck-at-high at IQ1
System continues to
run
Check outputs
241B0006
Warning
Stuck-at-high at IQ2
System continues to
run
Check outputs
241B0007
Warning
Stuck-at-high at IQ3
System continues to
run
Check outputs
241B0008
Warning
Stuck-at-high at IQ4
System continues to
run
Check outputs
241Bxxxx
Warning
Output error
System continues to
run
Check outputs
241D0001
Warning
Test pulse error at I1
System continues to
run
Check cabling
241D0002
Warning
Test pulse error at I2
System continues to
run
Check cabling
Содержание samos PRO COMPACT
Страница 1: ...samos PRO samos PRO COMPACT Hardware Manual Doc no BA000966 Last Update 08 2017 8151...