background image

Document 

BA00029

3

 A

 (Installation instructions

 

gesis

 RM

-16/0 (RC)

—Art.-No. 83.020.0408.0) 

Page 

1

83.020.0408.0

gesis

 RM-16/0 (RC)

ENG

 Installation instructions

 

Modular device series for 

gesis

 RAN

Wieland Electric GmbH

Brennerstraße 10-14

96052 Bamberg, Germany

Phone: 

+49 (951) 9324-0

Fax:   

+49 (951) 9324-198

Internet: www.wieland-electric.com

Email: [email protected]

Status October 2005

© 2005 Wieland Electric GmbH

A.  Important instructions – please read carefully

This supplementary sheet describes the installation of the extension module 16-times 

wireless input module of the 

gesis

 RM

 device series.

B. Function description

The wireless input module contains 2 x 8 inputs whereby each 8 inputs occupy a 

connection position in the base module. The inputs receive EOBcean telegrams and 

convert them into static signals (on/off/ closed/open). The connection of an external 

aerial is required for wireless reception.

To operate the wireless input module a base module of the 

gesis

 RM

 device series is 

required. Communication with the bus takes place through the base module. Here the 

received switch commands are accepted and forwarded to the input status.

The connection to the base module is made through one or two ribbon cables.

The power required for wireless input is received by the module over the ribbon cable 

from the base module.

This device, mountable on a top hat rail, is designed for installation in a 

gesis

 RAN

or similar housing

C. Unit drawing 

(Dimensions in mm)

gesis

 RM

-16/0 (RC)

D.  Connections, operating and observation elements

1 =  JTAG programming port (only for servicing purposes)

2 =  Connections to the base module (X1 + X2)

3 =  „Test” button

4 =  „Learn” button

5 =  „Clear” button

6 =  LED red „Clear”

7 =  LED green „Learn”

8 =  Selection switch for input channels

9 =  SMA aerial socket

10 = Locking slide

E. Installation

Installation of the module:
1.  Push the module on to the top hat rail.

2.  Push the extension module with the accompanying ribbon cable to the base module.

3.  Connect the aerial to the aerial socket.

F. Dismantling

1.  Remove the aerial from the aerial socket.

2.  Remove the ribbon cable at the device front.

3.  Insert a screwdriver into the locking slide and remove the module

from the top hat rail.

G. Accessories

Basic module   

 

from the 

gesis

 RM

 series

Aerial    83.020.0503.0

H. Device settings

Undertake parameterizing and network adaptation in the base module.

Learning:

  Set desired entry A … H (Xl/X2) with the selection switch.

  Press „Learn” button for more than a second, the green light blinks.

  Allow transmitter the to be taught to transmit three times within two seconds

(e.g. pres the button three times).

  After learning, the green LED extinguishes and the actuator exits the programming 

mode automatically.

  Test the desired function for correctness.

Deletion:

1. Delete wireless transmitter (ID) from all instructions:

  Press „Clear” button for more than a second, the red light blinks.

  This is deleted from both modules X1/X2 by transmitting an ID (e.g. button)

three times.

  The red light extinguishes and the deletion mode is exited.

2. Delete all wireless transmitters (ID) of an input A … H X1/X2:

  Set the input to be deleted with the selection switch.

  Press „Clear” button for more than a second, the red light blinks.

  Keep on pressing “Clear” button (>3s) till red LED blinks quicker Release button

  The red LED extinguishes and the deletion mode is exited.

3. Delete all wireless transmitters (ID) (supply condition):

  Press „Clear” button for more than a second, the red LED blinks.

  Keep on pressing “Clear” button (>10s) till red LED extinguished. Release button.

  Deletion mode is exited.

Test function:

The “Test” button permits the testing of the parameterized network allocations of the 

base module.

  Set the input to be tested with the selection switch.

  Press „Test” button and release. The parameterized function is triggered.

I. Faulty units

The devices must not be opened and must be returned in the malfunctioning state to:
Wieland Electric GmbH

Abteilung TQM 3

Brennerstraße 10-14

D-96052 Bamberg

Germany

CAUTION

•  Because of the protection class and protection type, this device must be built 

into a 

gesis

 terminal block (

gesis

 RAN

) or a similar housing!

•  All electrical installations and connections may only be carried out by trained 

technicians!

•  The required regulations (e.g. EN 50090-2-2) are fulfilled when the devices are 

professionally further processed to an end product. The information provided 

here, the applicable standards and safety determinations, as well as the ESD 

guidelines are to be taken into account during further processing!

•  The applicable safety and accident prevention instructions must be adhered to!

NOTES

•  The extension module can only be operated in connection with a base module 

of the 

gesis

 RM

 device series.

•  The functionality of the extension module is decisively determined by the 

software settings in the base module.

Technical data

Interface to base module   

 

two pluggable ribbon cables

Inputs 

 

 

 

 

 

2 x 8 ENOcean wireless inputs via aerial

Software   

 

 

 

 

is carried out by the base module

Protection class / protection type 

no / IP 00

Degree of contamination   

 

2

Overvoltage category 

 

 

III

Area of application   

 

 

for fixed installation inside and dry rooms

Range inside buildings 

 

 

Typically 30 m, depending on type, thickness

 

 

 

 

 

 

 

and number, of obstructions between transmitter  

 

 

 

 

 

 

 

and receiver. For exact range planning see

 

 

 

 

 

 

 

gesis

 catalogue or manual

Wireless 

protocol 

   EnOcean

Frequency 

     868.3MHz

Temperature ranges

– 

Working 

ambient 

   

5°C…

+

45°C

– 

Storage 

     

25°C…

+

70°C

Rel. air humidity/ thawing   

 

5%...93% / not permissible

Housing material/-colour   

 

halogen-free plastic / black

Fire resistance (housing)   

 

V2 to UL 

Weight 

     approx. 

98 

g

Dimensions 

 

 

 

 

Width x Length x Height see device drawing

       Height 

52mm 

including 

TH35-7.5 

carrier 

rail

Approbation 

    EIB 

/KNX 

certified

CE symbol 

 

 

 

 

according to EMV guideline (residence

 

 

 

 

 

 

 

and utility building) low voltage guideline

Installation     on 

TH35 

carrier 

rail

CAUTION

•  The ribbon cables may only be connected or pulled in a voltage-free condition.

•  When connecting and pulling the ribbon cables, it must be ensured that the 

base module is voltage-free!

•  The maximum length of the ribbon cable of 120 mm must not be exceeded.

CAUTION

The ribbon cables may only be connected or pulled in a voltage-free condition.

gesis

Hotline:

Phone: 

+49 (951) 9324-996

Fax:   

+49 (951) 9326-996

Email: [email protected]

Internet: www.gesis.com

©2005 Wieland Eletric GmbH. All rights reserved. The Wieland Electric GmbH 

reserves the right to make modifications and changes in the interest of technical 

progress. In the case of bought-in products these will always be mentioned listed 

without reference to patent rights. As a consequence, the existence of such rights 

cannot be excluded. As a consequence, modifications and changes of any kind 

to Wieland Electric products in respect of both hard and software excludes any 

liability on the part of Wieland Electric GmbH.

10

8

4

7

6

5

2

3

1

9

Input (x)

W

wieland

gesis

RM-16/0 (RC)

83.020.0408.0

2 x 8 Input RC
EnOcean

Clear Learn

>1s

>1s

ID
Inp.
All

ID

x

CLR >10s

+ CLR >3s

x

+ ID

ID

X1

X2

X1

X2

Test

x

48.4

96.2

99.7

50.1

42.3

Отзывы: