Mounting, wiring and demounting
Wieland Electric GmbH | BA001269 | 09/2021 (Rev. A)
28
5.3.3
Wiring power modules
Terminal module terminals
Power modules are either integrated to the head module or may be installed between the extension
modules. With power modules, terminals with spring clamp technology are used for wiring. The
spring clamp technology allows quick and easy connection of your signal and supply lines. In con-
trast to screw terminal connections this type of connection is vibration proof.
Data
U
max
DC 30 V
I
max
10 A
Cross-section
0.08 … 1.5 mm² (AWG 28 … 16)
wire strip length 1000 mm
Wiring procedure
1
Pin number at the connector
2
Opening for screwdriver
3
Connection hole for wire
Insert a suited screwdriver at an angel into the square opening as shown.
Press and hold the screwdriver in the opposite direction to open the contact spring.
Insert the stripped end of wire into the round opening. You can use wires with a cross section of
0.08 mm² up to 1.5 mm².
By removing the screwdriver, the wire is securely fixed via the spring contact to the terminal.
Standard wiring
1
DC 24 V for power section supply I/O area
(max. 10 A)
2
DC 24 V for electronic power supply bus
coupler and I/O area
DC24V
0V
DC24V
0V
1
2
DC 24V max. 10A
S ys DC 5V max. 3A