WHITECROFT LIGHTING Concert SL Скачать руководство пользователя страница 2

Product Specification 

IMPORTANT:

 The luminaire must not be covered by any debris or insulating material. Ensure there is a minimum of 50mm air-

space around the luminaire and control gear. Electrical termination must be carried out by a qualified electrician in accordance 
with the latest edition of the IEE wiring regulations BS7671. 

PLEASE RETAIN THIS GUIDE FOR FUTURE REFERANCE AND RECYCLE PACKAGING. 

 

 

 

 

Dimensions 

Round Wallwasher 

Square Wallwasher 

Square Downlight 

Round Downlight 

85 mm bezel 

Ø 79 mm cut-out 

85 mm bezel 

Ø 79 mm cut-out 

85x85 mm bezel 

79x79 mm cut-out 

85x85 mm bezel 

79 x79 mm cut-out 

Specification 

Lamp Type:- LED 

Supply:-220-240V, 50-60Hz 

Power Output:- 8W & 14W 

Nominal Lumen Output:- 500 lm  to 1000 lm 

Colour Temperature:- 3000K & 4000K 

Ingress Protection:- IP44 

Trim Colour:- RAL9003 Signal White

 

 

 

 

50mm 

50mm 

Airspace around luminaire and driver 

50mm 

GENERAL INFORMATION  

1)A qualified electrician, in accordance with IEE wiring regulations should carry out connection to mains wiring.  

2) Ensure that the rated voltage and frequency requirements are compatible with the available mains supply.  

3) Cleaning of reflectors and lenses should be carried out using clean, soft and lint free cloths and anti-static cleaning fluid.  

4) Do not carry out high voltage insulation test, i.e. 500/1000v this may damage internal components.  

50mm 

ISOLATE MAINS SUPPLY BEFORE COMMENCING INSTALLATION 

 Ceiling thickness:- MINIMUM 3mm*, MAXIMUM 30mm  

 *A PATTRESS IS RECOMMENDED FOR CEILING THICKNESS LESS THAN 3mm . 

 

 

 

Feed the driver and control gear into ceiling void, 

     

ensuring it is not covered by debris or insulating        
material and is correctly positioned.

 

 

 

E1 

Reinstate mains 

 

 

 

 

 

 

Apply a bead of quick drying grip adhesive to the rear  
face of the plaster in frame. 

 

Locate into hole. 

 

Secure frame into hole using plaster in screws (by others) 

 

Once adhesive has cured apply PVA bonding coat and 
plaster up edge to frame. 

 

Apply finish to ceiling and allow to dry.

 Plaster and paint 

must be dried completely before installing luminaire  
into plaster in frame. Otherwise this may invalidate      
warranty.

 

B2 

E2 

*IMPORTANT :- To avoid damage to soft ceiling types care 
must be taken when releasing the spring into the aperture. 

 

Squeeze ceiling springs and push the fitting into the 
ceiling void. 

It is important that the springs are held 

from behind and only released once the luminaire is 
in place. 

If there is a risk of the heatsink being covered 

insert a yellow cap into the top of the luminaire. 

 

Once in place make sure the luminaire is secure in the 
ceiling. 

 

 

Yellow Cap 

Yellow Cap 

Remove reflector and 
pull down on      
Luminaire 

IMORTANT– Align dot on luminaire to dot on frame before 
attempting to lock fitting into place. 

 

Check the frame is clear of paint and plaster. 

 

Push the fitting into the frame. If there is a risk of the 
heatsink being covered insert the yellow cap into the 
top of the luminaire. 

To remove luminaire for maintenance:-  

Twist out reflector then pull down on luminaire 

Specification 

Lamp Type:- LED 

Supply:-220-240V, 50-60Hz 

Power Output:- 8W & 14W 

Nominal Lumen Output:- 500 lm  to 1000 lm 

Colour Temperature:- 3000K & 4000K 

Ingress Protection:- IP44 

Trim Colour:- RAL9003 Signal White

 

 

 

 

 

Wire mains flex into driver according to the applicable 
wiring diagram on the back of this leaflet.

 

 

Connect flex to mains supply. 

Round—Cut a 79mm circular hole using a hole saw. 

Square– Cut a 79mm square hole . 

To avoid damage to the ceiling tiles  it is not recommended to remove the luminaire once installed into soft ceiling types .  The luminaire 
and driver can be maintained from the adjacent ceiling tile or by removing the whole tile with luminaire attached. 

Push 

IMPORTANT: When installing wall wash type             
luminaires the  plaster in frame must be installed with 
the dot facing the wall to be illuminated. 

 

Remove Packaging 

 

Push down on Luminaire to remove from the 
plaster in frame. 

B1  

 

PLASTER IN ONLY 

PLASTER IN ONLY 

METAL PAN / SOFT CEILING 
TYPES* / PLASTER BOARD 

Отзывы: