RECOMMENDED ROUTINE TEST PROCEDURE 
 
The following test is designed to ensure the continued 
protection of your premises and occupants. Because of 
the possibility of a failure of the normal lighting supply 
occurring shortly after a period of testing, all tests should 
whenever possible, be undertaken at times of least risk, 
e.g. during daylight hours. 
 
 
 
ONCE A DAY 
 
Visual inspection of battery charge LED. 
 
 
ONCE A MONTH 
 
Each unit should be energised from its battery for about 
15 minutes by simulation of a failure of the normal 
lighting supply to ensure the LED’s operate in the 
emergency condition. 
 
 
ONCE A YEAR 
 
Each unit should be energised from its battery for the full 
rated duration.  Inspect the LED’s and if any of them have 
failed the whole unit will need to be replaced.  The LED’s 
will probably continue to operate for approximately 
10years but batteries will require replacement every five 
years. 

 

1.

 

Undo the single screw at the bottom of 
the body and hinge the body up and 
away from the back plate. NB: The body 
houses the LED/reflector assembly and 
this is electrically connected to the back 
plate. Therefore, to completely remove 
the main body disconnect the earth lead 
from the spade terminal on the base, 
and the LED lead from the PCB/module 
also located on the base. 

2.

 

Fit the back plate to the wall using the 
keyhole slots or the BESA mounting. 

3.

 

Bring the supply cable through the most 
convenient entry. Emergency Lighting 
circuits must be connected to an un-
switched 230v 50Hz live supply. Connect 
the mains supply cable into the terminal 
block on the base as follows:- N- Neutral; 
E- Earth; L1- un-switched Live; L2- 
switched Live (if required). 

4.

 

Re-connect the earth lead to the spade 
terminal on the base and the LED lead 
to the PCB/module. Replace the body by 
hooking over the top of the back plate 
and hinging down. Refit the single screw 
at the bottom. 

Concert EX2S LED wall mounted Exit Signs 

Concert EX2S LED Exit signs must be ordered with the appropriate down, left 
or right direction legend (changing the Legends on-site is not recommended). 
The back-plate should be fitted to the mounting surface using fixings 
appropriate to the application. Supply cables should be installed according to 
National Wiring Regulations and should suit the type of mounting 
arrangement chosen. 
The body of the Concert EX2S LED exit sign simply hooks on to the top of the 
back plate then hinges down and is retained with a single screw at the bottom. 

 

NB: These units are available with a Self-Test feature. If fitted, this circuit will carry out function checks once per month and indicate any problems with the 
battery or circuit. 
 
Concert EX2S LED luminaires use long life LED’s to illuminate the sign legend. Only the battery pack is a customer serviceable part. The batteries are 
designed to last for 5years after which time they should be returned to the supplier for recycling and replaced with a new pack. 
 
The sign legends are part of an LED & reflector assembly. Therefore, it is not recommended to change sign legends on site. 

 