White Rodgers IF78 Скачать руководство пользователя страница 5

Symptom

Possible Cause

Corrective Action

No Heat/No Cool/No Fan

1. Blown fuse or tripped circuit breaker.

Replace fuse or reset breaker.

(common problems)

2. Furnace power switch to OFF.

Turn switch to ON.

3. Furnace blower compartment door or

Replace door panel in proper position to engage

panel loose or not properly installed.

safety interlock or door switch.

No Heat

1. Pilot light not lit.

Re-light pilot.

2. System Switch not set to Heat.

Set System Switch to Heat and raise temp above
room temp.

3. Loose connection to thermostat or system.

Verify thermostat and system wires are securely
attached.

4. Furnace Lock-Out Condition. Heat may also

Many furnaces have safety devices that shut

be intermittent.

down when a lock-out condition occurs. If the
heat works intermittently contact the furnace
manufacturer or local service person for
assistance.

5. Heating system requires service or

Diagonistic: Set System Switch to Heat and raise

thermostat requires replacement.

the setpoint above room temperature. Within a few
seconds the thermostat should make a soft click
sound. This sound usually indicates the thermo-
stat is operating properly. If the thermostat does
not click, try the reset operation listed below. If the
thermostat does not click after being reset contact
your heating and cooling service person or place
of purchase for a replacement. If the thermostat
clicks, contact the furnace manufacturer or a
service person to verify the heating is operating
correctly.

No Cool

1. System Switch not set to Cool.

Set System Switch to Cool and lower temp below
room temp.

2. Loose connection to thermostat or system.

Verify thermostat and system wires are securely
attached.

3. Cooling system requires service or

Same procedure as diagnostic for No Heat

thermostat requires replacement.

condition except set the thermostat to Cool and
lower the setpoint below the room temperature.
There may be up to a five minute delay before the
thermostat clicks in Cooling.

www.white-rodgers.com

6

ELECTRICAL DATA
Electrical Rating:

0 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.2 Amps (Load per terminal)
1.5 Amps Maximum Total Load (All terminals combined)

SPECIFICATIONS

7

THERMAL DATA
Setpoint Temperature Range:

45

°

F to 90

°

F (7

°

C to 32

°

C)

Operating Ambient Temperature Range:

32

°

F to 105

°

F

Operating Humidity Range:

0 to 90% RH (non-condensing)

Shipping Temperature Range:

-40

°

F to 150

°

F

TROUBLESHOOTING

Reset Operation
If a voltage spike or static discharge blanks out the display or
causes erratic thermostat operation you can reset the thermostat
by pressing 

 and 

 and TIME at the same time while

moving the SYSTEM switch from OFF to HEAT. This also resets
the factory defaults. If the thermostat has power, has been reset

and still does not function correctly contact your heating/cooling
service person or place of purchase.

Batteries
For optimum performance, we recommend replacing batteries
once a year with fresh “AAA” Energizer

®

 alkaline batteries.

Отзывы: