CAUTION

!

CHECK THERMOSTAT OPERATION

www.white-rodgers.com

NOTE

To prevent static discharge problems, touch side of ther-
mostat to release static build-up before touching any keys.

If at any time during testing your system does not operate
properly, contact a qualified serviceperson.

Fan Operation

If your system does not have a G terminal connection, skip to
Heating System.

1. Turn on power to the system.

2. Move fan switch to ON position. The blower should begin to

operate.

3. Move fan switch to AUTO position. The blower should stop

immediately.

Do not allow the compressor to run unless the compres-
sor oil heaters have been operational for 6 hours and the
system has not been operational for at least 5 minutes.

Heating System

1. Press SYSTEM key to select the Flame icon ( ). If the auxiliary

heating system has a standing pilot, be sure to light it.

2. Press 

 to adjust thermostat setting to 1

°

 above room

temperature. The heat pump system should begin to operate.
However, if the Flame icon ( ) and Snowflake icon ( ) are
flashing, the compressor lockout feature is operating (see
Configuration menu, item 3.)

3. Adjust temperature setting to 4

°

 above room temperature. The

auxiliary heat system should begin to operate and the Flame
icon
 ( ) will be flashing.

4. Press  

  to adjust thermostat setting below room tempera-

ture. The heating system should stop operating.

Emergency System

EMER bypasses the Heat Pump to use the heat source wired
to terminal E on the thermostat. EMER is typically used when
compressor operation is not desired, or you prefer back-up
heat only.
1. Press SYSTEM key to select EMER. EMER will flash on the

display.

2. Press  

  to adjust thermostat setting above room tempera-

ture. The Aux heating system will begin to operate. The
Flame icon ( ) will display flashing to indicate that the Aux
system is operating.

3. Press 

 to adjust the thermostat below room temperature.

The Aux heating system should stop operating.

To prevent compressor and/or property damage, if the
outdoor temperature is below 50

°

F, DO NOT operate the

cooling system

Cooling System

1. Press SYSTEM key to select the Snowflake icon ( ).

2. Press 

 to adjust thermostat setting below room tempera-

ture. The blower should come on immediately on high speed,
followed by cold air circulation.

3. Press 

 to adjust temperature setting above room tem-

perature. The cooling system should stop operating.

Before you begin configuring your thermostat, you should be
familiar with its features and with the display and the location and
operation of the thermostat buttons. Your thermostat consists of
two parts: the thermostat cover and the base. To remove the
cover, gently pull it straight out from the base. To replace the
cover, line up the cover with the base and press gently until the
cover snaps onto the base.

The Thermostat Buttons and Switches

1 (Up arrow) Raises temperature setting.

2 (Down arrow) Lowers temperature setting.

3

FAN switch (ONAUTO).

4 SYSTEM key (HEAT ( ), EMER*, OFF, COOL ( ),

AUTO (   ).

* EMER is available when H.P. is selected in the configuration
menu.

The Display

5 Indicates a malfunction with the system.

Flame icon ( ) is displayed when the SYSTEM mode is in

HEAT. Flame icon ( ) is displayed flashing when 2nd-stage
heat (Aux or Emergency) is energized. Snowflake icon ( )
is displayed (non-flashing) when the SYSTEM mode is in
COOL. Snowflake and Flame  icons are displayed when the
SYSTEM mode is in AUTO.  Snowflake and  Flame icons
are displayed (flashing) if the thermostat is in lockout mode
to prevent the compressor from cycling too quickly.

EMER is displayed flashing when the system switch is in

EMER position.

8 Displays current temperature.

5

CAUTION

!

6

FAN

ON

MODE

SYSTEM

AUTO

STG1+2

EMER

Содержание IF73

Страница 1: ...at a time DO NOT LET WIRES FALL BACK INTO THE WALL 6 Install new thermostat using the following procedures To prevent electrical shock and or equipment damage disconnect electrical power to the system...

Страница 2: ...ch require the changeover relay to be energized in COOL If the thermostat you are replacing or the heat pump being installed with this thermostat requires a B terminal to energize the changeover relay...

Страница 3: ...y Switches 24 VAC Limit or Safety Switches COMMON COMMON Auxiliary Heating Transformer Class II Current Limited Heat Pump Transformer Class II Current Limited 24 VAC ACCESSORY RELAY N O CONTACT Polari...

Страница 4: ...s for specific sys tem wiring informtion You can configure the thermostat for use with the following heat pump system types HEAT PUMP TYPE 1 Single stage compressor system gas or electric backup This...

Страница 5: ...ate The Flame icon will display flashing to indicate that the Aux system is operating 3 Press to adjust the thermostat below room temperature The Aux heating system should stop operating To prevent co...

Страница 6: ...tes 6 Select Compressor Lockout CL OFF or ON Selecting CL ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power It will also wai...

Страница 7: ...ction to thermostat or system Verify thermostat and system wires are securely attached 3 Cooling system requires service or Same procedure as diagnostic for No Heat thermostat requires replacement con...

Страница 8: ...and the size The cycle rate for cooling is fixed and can not be narrow or wide temperature swing of the Cooling System can influence the adjusted Contact a local service person for cycle rate suggest...

Отзывы: