TROUBLESHOOTING 

 

TROUBLESHOOTING

Green 

LED Flash

Amber 

LED Flash

Red 

LED Flash

Error / Condition

Up to 5 Flash Codes Stored in Memory (Auto-Erased After 14 Days)

11

No Stored Codes

12

Reversed 120 VAC Polarity / Grounding

14

Ignition Lockout (Due to Excessive Retries)

15

Ignitor Failure

16

Gas Valve De-Energized When It Should Be Energized

21

Gas Heating Lockout (Gas Valve Energized When It Should Be De-Energized)

22

Abnormal Flame Proving Signal 

(Flame Sensed When Flame Should Not Be Present)

23

Low Heat Pressure Switch Did Not Open

(Shorted Pressure Switch, 1st stage)

24

Fuse is Open

25

High Heat Pressure Switch Did Not Open (Shorted Pressure Switch, 2nd stage)

31

High-Heat Pressure Switch or Inducer Relay Did Not Close or Re-opened  

(Open Pressure Switch, 2nd stage)

32

Low-Heat Pressure Switch or Inducer Relay Did Not Close or Re-opened (Open 

Pressure Switch, 1st stage)

33

Limit Circuit Fault (Open Limit or Roll Out)

34

Ignition Proving Failure (Due to Ignition Recycles)

Flash codes NOT stored in memory

OFF

OFF

OFF

No 120 VAC and 24 VAC Power

Control Circuitry Lockout

Alternate

Alternate

Alternate

Self-Test Mode Active

Solid ON

Standby

Rapid Flash

Fan Only Call

1

Call For Low Cool

2

Call For High Cool

3

Blower On After Power Up

Rapid flash

Weak Flame Error

1

Call For Low Heat

2

Call For High Heat

3

Defrost Mode

Rapid flash

Twinning Error

NOTE:

 Rapid Flash LED flash code uses 250ms ON time and 250ms OFF time. 

Two-digit Red LED flash codes use 1s ON time, 250ms OFF time.  There is a 1s OFF time between 1

st

 and 2

nd

 digit of the 

error code. There is a 2s OFF time between each error code. 

FAULT AND STATUS CODES

The LED will indicate fault or status codes as shown in the table below:

FAULT RECALL 

When the control is in standby mode (no call for heat or cool), 
press the "SELECT" button for approximately 2 to 5 seconds or 
until the diagnostic LED turns off. Up to 5 fault codes are stored.

NOTE:

 While displaying the stored fault codes, the control will 

ignore any new call for heat, cool or fan.

FAULT CODE RESET

When the control is in standby mode (no call for heat or cool), 
press the "SELECT" button for 5 to 10 seconds or until the 
diagnostic LED begins to rapid flash. 

NOTE

:  If the switch is held pressed for over 10 seconds the 

rapid flash will stop and the LED will be on to indicate 
return to normal status.

TECHNICAL SUPPORT:  1-888-725-9797

Содержание 21V51D-751

Страница 1: ...mblies Control Label 8 Wire Nuts Installation Instructions white rodgers com emerson com PART NO 37 7625001 1711 TWINNING 21V51D 751 CANNOT be twinned with any Carrier ICP or ICM brand controls Both c...

Страница 2: ...rd Set blower type dipswitch to PSC VS The green DEHUM wire from the VS motor connects to G terminal green wire of A harness if previously connected to G on old style control board Cut the existing sp...

Страница 3: ...umper is present NOTE For adaptive cooling operation connect thermostat cool input to Y1 terminal yellow wire of A harness LHT Low Heat Only Adaptive Heating The control can operate a two speed furnac...

Страница 4: ...eat stages two stage thermostat LHT Disable 90s 150s 120s 180s Ht Off Dly Ht Off Dly Ht Off Dly Ht Off Dly Low Heat High Heat Cool Cont Fan Speed Cont Fan Speed Cont Fan Speed ECMx SW3 SW2 4 3 2 1 4 3...

Страница 5: ...wer Off Delay System Off Thermostat W2 Thermostat W1 15 s 17 19 s 5 s 45 s 15 s 90 120 150 180 High Speed Inducer IND HI Low Speed Inducer IND LO Pressure Switch HPS Pressure Switch LPS Ignitor HSI Se...

Страница 6: ...ermostat is Satisfied Blower Off Delay System Off Thermostat DEHUM Thermostat Y2 Thermostat Y1 3 sec 10 min 10 min 10 min 5 sec Outdoor Compressor Outdoor Fan Blower Cool Speed Blower High Heat Speed...

Страница 7: ...seconds the ignitor will turn ON for 15 seconds then OFF Blower motor operates on LOW HEAT speed for 10 seconds Blower motor operates on HIGH HEAT speed for 10 seconds Blower motor operates on COOL s...

Страница 8: ...y OFF OFF OFF No 120 VAC and 24 VAC Power Control Circuitry Lockout Alternate Alternate Alternate Self Test Mode Active Solid ON Standby Rapid Flash Fan Only Call 1 Call For Low Cool 2 Call For High C...

Страница 9: ...rnaise 50V51 751 avec support de montage 3 faisceaux de fils tiquette de la commande 8 connecteurs Directives d installation white rodgers com emerson com No DE PI CE 37 7625001 1711 JUMELAGE La comma...

Страница 10: ...eau panneau de commande R gler le commutateur DIP du type de souffleur sur PSC VS Le fil vert DEHUM du moteur VS se branche dans la borne G fil vert du faisceau A s il tait pr alablement branch sur la...

Страница 11: ...est r gl sur ON marche REMARQUE Pour le chauffage adaptatif brancher l entr e de de chauffage du thermostat dans la borne W W1 fil blanc du faisceau A R GLAGE DE CAVALIER ACRDJ ON OFF ON Active le co...

Страница 12: ...uffage thermostat bi tage LHT Neutraliser 90 s 150 s 120 s 180 s D lai arr t chauff D lai arr t chauff D lai arr t chauff D lai arr t chauff Chauff faible Chauff lev Climatisation Vit vent cont Vit ve...

Страница 13: ...uffleur Arr t du syst me Thermostat W2 Thermostat W1 15 s 17 19 s 5 s 45 s 15 s 90 120 150 180 Inducteur grande vitesse IND HI Inducteur basse vitesse IND LO Pressostat HPS Pressostat LPS Allumeur HSI...

Страница 14: ...du souffleur Arr t du syst me Programmation du thermostat Thermostat Y2 Thermostat Y1 3 s 10 min 10 min 10 min 5 s Compresseur ext rieur Ventilateur ext rieur Souffleur vitesse de climatisation Souff...

Страница 15: ...es puis il s ARR TE Le moteur du souffleur fonctionne vitesse CHAUFFAGE LENT pendant 10 secondes Le moteur du souffleur fonctionne vitesse CHAUFFAGE HAUTE pendant 10 secondes Lemoteurdusouffleurfoncti...

Страница 16: ...n alternance En alternance Mode auto test actif Reste ALLUM E En attente Clignotement rapide Commande de ventilateur seulement 1 Commande de climatisation lente 2 Commande de climatisation rapide 3 So...

Отзывы: