White Rodgers 1F95-71 Скачать руководство пользователя страница 7

7

CAUTION

!

Cooling System Operation

To prevent compressor and/or property damage,
if power to the compressor has been off or
interrupted for more than 1 hour and the outdoor
temperature is below 50

°

F, DO NOT operate the

system for at least the amount of time the compres-
sor was off! This will allow the compressor heaters to
warm the compressor oils to avoid damage due to
slugging.

1.

Press 

SYSTEM

SWITCH

 until COOL is displayed.

2.

Press 

 to adjust the thermostat to 40

°

F. All

stages of the cooling system should come on within
five minutes (if the compressor is not operating, it may
be locked out. See LOCKOUT BYPASS OPTION).

Refer to the OPERATION GUIDE if you need additional
information on thermostat operation.

TROUBLESHOOTING

Refer to the Question & Answer section of the OPERA-
TION GUIDE
 for information on troubleshooting the
thermostat.

5.

To enable partial keypad lockout (only the tem-
perature
 buttons will function; all other buttons will be
disabled and will not operate until configuration is
changed):

Switch #4 in ON position disables all buttons except 
and  

 (see OPERATION GUIDE).

The battery maintains the stored program in the event of
a power failure. When attached to the wall with 24 VAC
power applied, the thermostat will function normally with-
out the battery. However, the program will be lost in the
event of power interruption or failure if the battery is not
installed. When power is restored, the thermostat will
automatically maintain a temperature of 64

°

F or a cooling

temperature of 82

°

F (factory preprogrammed) as needed.

CHECK THERMOSTAT OPERATION

Fan Operation

1.

Turn on power to the system. If the heat source has
a standing pilot, be sure to light it.

2.

Press 

FAN

SWITCH

 until FAN ON is displayed. The blower

should begin to operate.

3.

Press 

FAN

SWITCH

 until FAN AUTO is displayed. The

blower should stop operating within approximately
one minute.

Heating System Operation

1.

Press 

SYSTEM

SWITCH

 until HEAT is displayed (it may already

be displayed).

2.

Press 

 to adjust thermostat to 99

°

F. All stages of

the heating system should begin to operate within five
minutes.

ON

1

2

3

4

Switch #1 (see steps 1-2)
Switch #2 (see step 3)
Switch #3 (see step 4)
Switch #4 ON

NOTE

CAUTION

!

LOCKOUT BYPASS OPTION

FOR QUALIFIED SERVICE TECHNI-
CIANS’ USE ONLY. OPERATORS
SHOULD NOT USE THIS FEATURE DUE
TO POSSIBILITY OF EQUIPMENT OR
PROPERTY DAMAGE, OR PERSONAL
INJURY.

DO NOT USE THE LOCKOUT BYPASS
OPTION UNLESS THE COMPRESSOR OIL
HEATERS HAVE BEEN OPERATIONAL
FOR 6 HOURS AND THE SYSTEM HAS
NOT BEEN OPERATIONAL FOR AT
LEAST 5 MINUTES.

COMPRESSOR SHORT TERM

CYCLE PROTECTION

This thermostat has a built-in short term (5-minute)
time delay. During this 5-minute period, the thermo-
stat will lock out the compressor to allow head pres-
sure to stabilize. If you want to override this feature

while testing thermostat operation, simply press 

VIEW

TEMP

and 

VIEW

PRGM

 buttons at the same time at initial start-up.

Содержание 1F95-71

Страница 1: ...ermostat to Subbase Operation 6 System Configuration Set Option Switches Check Thermostat Operation Fan Operation Heating System Operation Cooling System Operation Troubleshooting PRECAUTIONS Ifindoub...

Страница 2: ...building temperature Observe the following general rules when selecting a location 1 Locate thermostat about 5 ft above the floor 2 Install thermostat on a partitioning wall not on an outside wall 3 N...

Страница 3: ...THE WALL 7 Install new thermostat using the following proce dures Attach Subbase To Wall 1 Remove the packing material from the thermostat Place the fingers of one hand on the center top and bottom po...

Страница 4: ...RSONALINJURY AND OR EQUIPMENT DAMAGE COULD RESULT NOTE TABLE 2 WIRE IDENTIFICATION LABELS 1 G G 1 9 Y1 Y1 9 2 C C 2 3 L L 3 4 R R 4 5 O O 5 6 B B 6 7 E1 E1 7 8 E2 E2 8 10 Y2 Y2 10 11 W1 W1 11 12 W2 W2...

Страница 5: ...HOT side of the second transformer is jumpered to the COMMON side of the first transformer a short will be made Damage to equipment will occur when power is restored IF SAFETY CIRCUITS ARE IN ONLY ONE...

Страница 6: ...the top of the thermostat and the 4 connector pins on the thermostat with the connectors near the top right section of the subbase when viewed from the front Gently pivot the thermostat down until th...

Страница 7: ...lure if the battery is not installed When power is restored the thermostat will automatically maintain a temperature of 64 F or a cooling temperatureof82 F factorypreprogrammed asneeded CHECK THERMOST...

Страница 8: ...If you need further information about this product please write to White Rodgers Division Emerson Electric Co 9797 Reavis Road St Louis MO 63123 5398 Attention Technical Service Department...

Отзывы: