White Rodgers 1F90W-71 Скачать руководство пользователя страница 3

3

REPLACEMENT INSTALLATION

REMOVE OLD THERMOSTAT

1.

Shut off electricity at the main fuse box until installa-
tion is complete.  Verify power is off with a voltmeter.

2.

Remove the front cover of the old thermostat.  With
wires still attached, 
remove wall plate from the wall.

3.

If the old thermostat has a wall mounting plate,
remove the thermostat and the wall mounting plate as
an assembly.

4.

FOR HEATING ONLY SYSTEMS — Disconnect the
two wires from the old thermostat.  Skip steps 5
through 7 below and proceed to ATTACH SUBBASE
TO WALL
.

5.

FOR HEATING/COOLING SYSTEMS — Before re-
moving wires from old thermostat, identify the termi-
nals that have wires attached on the old thermostat.
Then use Table 1 to identify the type of thermostat you
are replacing.  For example, if the old thermostat has
wires attached to terminals R, W, Y, and G, the old
thermostat is a type 5 (note that the old thermostat
may not have wires attached to all the terminals
identified in Table 1).

6.

Use the self-adhesive labels enclosed with your
new thermostat to identify the wires attached to
the old thermostat.
  The labels correspond to the
thermostat type number you identified in step 5 above
(see Table 2).  For example, if you determined that the
old thermostat is a type 5, use the labels for the type
5 thermostat (you may not use all the labels for the
type number you've identified if the old thermostat did
not have wires attached to all the terminals).

7.

Label each wire as you disconnect it.  The labels have
both the old terminal markings and the new terminal
identification.  Discard any unused labels.  PULL AT
LEAST SIX INCHES OF WIRE OUT OF THE WALL
WHEN YOU DISCONNECT IT - DO NOT ALLOW
THE WIRES TO FALL BACK INTO THE WALL.

ATTACH SUBBASE TO WALL

1.

Remove the packing material from the thermostat.
Place the fingers of one hand on the center top and
bottom portion of the thermostat.  Grasp the subbase
in the other hand on the top and bottom center, and
gently pull straight out (see Fig. 2).  The thermostat
has pin and socket connectors.  Forcing or prying on
the thermostat will cause damage to the unit.

2.

Pull wires through opening in the center of the sub-
base.  DO NOT LET WIRES FALL BACK INTO
WALL.

3.

Connect wires beneath terminal screws on subbase
using appropriate wiring schematic (see Figs. 3
through 11).

4.

Place subbase over hole in wall and mark mounting
hole locations on wall using subbase as a template.

(Installation instructions continue on page 5.)

G

RC

Mounting

Hole

Pull wires through

this opening

Connect wires under

terminal screws

Mounting

Hole

6-pin Connector

3-pin Connector

6

MV

Y

W

Expansion

Plugs

Figure 3.  Subbase

Activity

Light

RH

TABLE 1.  OLD THERMOSTAT IDENTIFICATION

Type

1

Type

2

Type

3

Type

4

Type

5

4

RH

M

R5

R

W

W

H

4

W

RC

RC

V

Y

Y

C

Y6

Y

G

G

F

G

G

OLD 

THERMOSTAT

TYPE

OLD THERMOSTAT

TERMINAL IDENTIFICATION

TABLE 2.  WIRE IDENTIFICATION LABELS

Type

1

Type

2

Type

3

Type

4

Type

5

New  Old

RH     4

New  Old

 RH   RH

New  Old

RH    M

New  Old

RH    R5

New  Old

RH    R

New  Old

W     W

New  Old

 W     W

New  Old

W     H

New  Old

W     4

New  Old

W     W

New  Old

 RC   RC

New  Old

 RC   RC

New  Old

RC    V

New  Old

Y     Y

New  Old

 Y     Y

New  Old

Y     C

New  Old

 Y    Y6

New  Old

Y     Y

New  Old

G     G

New  Old

 G     G

New  Old

G     F

New  Old

 G     G

New  Old

G     G

PULL STRAIGHT OUT

Figure 2.  Removing thermostat from subbase

Содержание 1F90W-71

Страница 1: ...illivolt line orlow voltage have it inspected by a qualified heating and air conditioning contractor electrician or someone familiar with basic electricity and wiring R WHITE RODGERS Do not exceed the...

Страница 2: ...un fireplaces or any temperature radiating equip ment 4 Avoid locations close to windows adjoining outside walls or doors that lead outside 5 Avoid locations close to air registers or in the direct pa...

Страница 3: ...erminal identification Discard any unused labels PULL AT LEAST SIX INCHES OF WIRE OUT OF THE WALL WHEN YOU DISCONNECT IT DO NOT ALLOW THE WIRES TO FALL BACK INTO THE WALL ATTACH SUBBASE TO WALL 1 Remo...

Страница 4: ...vAC 120vAC Hot Neutral THERMOSTAT SYSTEM G W Figure 6 Typical Wiring Diagram for Cool Only 3 Wire Single Transformer Systems 6 Fan Relay Cooling System RH TRANSFORMER G RC 6 MV Y W RH Thermostat Termi...

Страница 5: ...MV 24vAC 120vAC Hot Neutral THERMOSTAT SYSTEM G W HEATING TRANSFORMER 6 24vAC 120vAC Hot Neutral COOLING TRANSFORMER Cooling System Fan Relay Heating System RC G RC 6 MV Y W RH Thermostat Terminal Con...

Страница 6: ...stat may occur if force is used CAUTION ENGAGE TWO LOWER GUIDES PIVOT UP Figure 13 Attaching thermostat to subbase SYSTEM CONFIGURATION A SET GROUP A OPTION SWITCHES ANY TIME GROUP B OPTION SWITCHES A...

Страница 7: ...h 2 OFF Switch 3 see step B5 ON 1 2 3 Switch 1 OFF Switch 2 ON Switch 3 see step B5 ON 1 2 3 Switch 1 ON Switch 2 ON Switch 3 see step B5 2 Press FAN ON AUTO until FAN ON is displayed The blower shoul...

Страница 8: ...e Product F O B Seller sfactory orSeller sissuanceofacreditintheamount of the purchase price of such Product for resale as described below Seller shall have the option of requiring the return of any d...

Отзывы: