EN / W-TG 3000 / June 2012
13
Engine load during longer operation:
Please ensure that the generating set is not overloaded.
Overloading occurs when the electrical load (demand) is
so high that the generator cannot be turned around
properly by the diesel engine. Overloading causes the
engine to run rough, while using oil and excessive fuel and
producing soot by the exhaust. The engine can even stop.
The generator should therefore only be loaded at the
maximum rated power for short periods (2-3 hours) only!
The high peak current is meant for the ability to start
electrical devices that need a high current for starting
especially electric motors and compressors (from a still
stand state).
Do not run the generator for very long periods at no load
or at very low load. When this is necessary do load the
generator at least one hour in 10 hours for minimum 70%.
Long term running at too low load will cause the exhaust to
be choked by carbon.
Never remove the battery while the engine is
running or any electrical cable while the
battery is connected in the circuit. Only
disconnect the battery with the engine
stopped and all switches in "OFF" position.