Cooling control: 

 

 

 

 

 

 

 

 

 

 

 

Adaptive Defrost Control 

The defrost cycle shall be started after the Defrost timer has expired. According to the following defrost procedure: 

Defrost must be executed every time one of the following event occurs: 

 

1.

 

After 8 hours (+/-10 minutes) of compressor running, calculated considering just the thermostat function. 

2.

 

When the product goes into defrost (in thermostatic mode) a time period of 20 min (+/-1 minute) is allowed 
to complete the time to defrost. 

3.

 

If the door open time  > 10  min, within first 5 hrs of cumulative compressor run time, defrost is initiated at 
5hrs. 

4.

 

If the door open time < 10 min or If there is at least one door opening up to 8 hrs of compressor running then 
defrost time is as per point 1. 

5.

 

If there is no door opening up to 8 hrs of compressor running than defrost time will be 18hrs 

6.

 

If  there is no door opening  for 8  hrs, & there  is door opening between  8  to 18 hrs of  compressor running, 
defrost will take place immediately. 

 

Содержание WIN852 GS

Страница 1: ...1 WHIRLPOOL OF INDIA LTD Service Manual Top Mount No Frost Refrigerator ...

Страница 2: ...X Sno Detail Page No 1 MODEL RANGE 3 2 SAFETY PRECAUTIONS 4 3 FEATURE TECHNICAL SPECIFICATION 6 4 GENX CONTROL CONFIGURATION 7 5 COOLING CONTROL 8 6 WIRING DIAGRAM 9 7 EXPLODED VIEWS 10 8 SERVICE PART LIST 14 ...

Страница 3: ...3 NO FROST REFRIGERATOR MODEL RANGE 220L GRAPHITE WIN852 GS ...

Страница 4: ...4 ...

Страница 5: ...5 ...

Страница 6: ...Run Capacitor PTC Relay QP2 15G Motor Protector BT60 120Y Fan motor 5 8W MI FAN MOTOR ASSY GENX Split Diffuser NO Deodorizer CHARCOAL Number of Shelves 2 Type of Shelves WIRE Humidity Control YES RC Illumination BULB FC Illumination Bottle Retainer Egg tray 8 EGGS Freezer Door Bins 1 Refrigerator Door Bins 3 Door lock YES Handle M0 Electromechanical Control in RC YES Fast Forward Cool Operation Do...

Страница 7: ...ntrols Configuration Product Configuration 220L DLX Product Control RC Controlled RC Illumination Yes Lamp Control Board No Defrost heater Yes Radiant Heater 180 W Fan motor FAN MOTOR MI Compressor ASD65 Run Capacitor Door Reversibility No ...

Страница 8: ...static mode a time period of 20 min 1 minute is allowed to complete the time to defrost 3 If the door open time 10 min within first 5 hrs of cumulative compressor run time defrost is initiated at 5hrs 4 If the door open time 10 min or If there is at least one door opening up to 8 hrs of compressor running then defrost time is as per point 1 5 If there is no door opening up to 8 hrs of compressor r...

Страница 9: ...9 WIRING DIAGRAM ...

Страница 10: ...10 EXPLODED VIEWS ...

Страница 11: ...11 ...

Страница 12: ...12 ...

Страница 13: ...13 ...

Страница 14: ...REW ONYX 2 EA 9 A2245930000 Rubber Cap For Suction Tube 6 35 1 EA 10 A226158000B PLUNGER SWITCH NC ESBEE 1 EA 11 W10422954 RIVET AL POP 4 MM 1 EA 12 W10478024 SCREW TRILOBULAR M6X1 0 HEX HEAD 6 EA 13 A201037000A LIGHT LENS 1 EA 14 A201135000E KNOB THERMOSTAT modified 1 EA 15 W10597271 CHILLER 55CM PWS MINI 1 EA 16 A201354000D PHILIPS HEAD SCREW M5 5X1 8 2 EA 17 A2013550000 SCREW HEX HEAD HI LO SEM...

Страница 15: ...TER 1 EA 35 A211939000C RIGHT ATTACHMENT RADIANT HEATER 1 EA 36 A211940000A COVER RADIANT HEATER 1 EA 37 A211983000A Control box 220 250L Dom New Graphics 1 EA 38 A2221470000 BULB APPLIANCE E14 1 EA 39 A229048000E HINGE BOTTOM SUB ASSY OPAL 1 EA 40 A229064000C PLATE LEVELLER SUB ASSY OPAL 1 EA 41 W10467948 SLEEVE TOP HINGE ONYX 1 EA 42 A2291860000 FLIP UP SHELF FREEZER OPAL 1 EA 43 A2293320000 Cov...

Страница 16: ...W10529669 Top Hinge Assy Genx Ph1 DLX 1 EA 65 A2252540000 Grommet Compressor THK 4 EA 66 W10464278 Screw Cap for Lock Bracket 3D 1 EA 67 W10579573 EARTHING WIRE WITH RING TERMINAL 1 EA 68 A2295680000 COSMETIC HOLDER GENX 1 EA 69 D111308000K S T SCREW 6X13 2 EA 70 A234099B500 CAP COVER HINGE TOP GRAPHITE TRINIT 1 EA 71 W10589230 FC M0 HANDLE BASE CHARCOAL GREY 1 EA 72 W10589251 FC M0 HANDLE FRONT C...

Отзывы: