12
■
Compressor runs—goes off on
overload.
■
Loose connection. Inspect connection. Tighten if needed.
■
Shorted or broken wires. Test circuits with ohmmeter. Replace if needed.
■
Shorted or open capacitor. Test capacitor.
■
Shorted or grounded compressor. Test motor windings.
■
Compressor stuck. Use test cord.
■
Faulty compressor contactor. Test continuity of coil and contacts. Replace, if needed.
■
Low voltage. Test voltage.
■
Overcharge of refrigerant. Recover part of charge.
■
Dirty outdoor coil. Inspect coil and clean, if needed.
■
Improperly located thermostat. Relocate thermostat.
■
Wrong type of expansion valve. Replace valve.
■
Expansion valve restricted. Remove restriction or replace valve.
■
Undersized expansion valve. Replace valve.
■
Inoperative expansion valve. Check valve operation. Replace if needed.
■
Faulty reversing valve. Replace valve or solenoid.
■
Compressor cycles on overload.
■
Shorted or open capacitor. Test capacitor.
■
Compressor stuck. Use test cord.
■
Low voltage. Test voltage.
■
Improper cooling anticipator. Check resistance of anticipator.
■
Shortage of refrigerant. Test for leaks. Add refrigerant.
■
Restricted liquid line. Replace restricted part.
■
Overcharge of refrigerant. Recover part of charge.
■
Dirty outdoor coil. Inspect coil and clean, if needed.
■
Noncondensibles. Recover charge. Evacuate and recharge.
■
Recirculation of condensing air. Remove obstruction to airflow.
■
Wrong type of expansion valve. Replace valve.
■
Expansion valve restricted. Remove restriction or replace valve.
■
Undersized expansion valve. Replace valve.
Unsatisfactory Cooling/Heating
■
System runs continuously—little
cooling/heating.
■
Shortage of refrigerant. Test for leaks. Add refrigerant.
■
Restricted liquid line. Replace restricted part.
■
Open element or limit on electric heater (heating only). Test heater element and
controls.
■
Dirty air filter. Inspect filter; clean or replace as needed.
■
Dirty indoor coil. Inspect coil and clean, if needed.
■
Not enough air across indoor coil. Check blower speed. Check duct static pressure and
filter.
■
Infiltration of outdoor air. Check windows, doors, vent fans, etc.
■
System undersized. Refigure cooling load.
■
Broken valves. Test compressor efficiency.
■
Inefficient compressor. Test compressor efficiency.
■
Wrong type of expansion valve. Replace valve.
■
Expansion valve restricted. Remove restriction or replace valve.
■
Oversized expansion valve. Replace valve.
■
Undersized expansion valve. Replace valve.
■
Inoperative expansion valve. Check valve operation. Replace if needed.
■
Flowrator not seating properly. Check flowrator and seat, or replace flowrator.
Problem
No Cooling/Heating
Cause/Test Method and/or Solution