background image

9

3.

Attach 

³⁄₄

" PVC pipe to the condensate drain outlet. See 

“Location Requirements.”

4.

Run the PVC pipe to an outdoor drain. Any horizontal run of 
drain pipe must have an anti-siphon vent for it to drain 
properly.

5.

If needed, install a condensate pump kit (optional).

6.

Using a 10" duct, attach the discharge air supply on the 
dehumidifier to the return air supply on the existing furnace or 
air handler. 

NOTE: 

Install ductwork in accordance with NFPA 90B 

Standard for the Installation of Warm Air Heating and Air 
Conditioning Systems (latest edition) and any local codes.

7.

Attach the return air supply on the dehumidifier to the return 
air supply on the existing furnace or air handler near the 
return air grille.

NOTE: 

Do not draw air directly from the kitchen, bathroom, 

laundry room or unconditioned isolated basement.

8.

Attach insulated flexible duct to the discharge air supply on 
the dehumidifier.

9.

Run duct to the basement or crawl space of the building.

Horizontal Installation

Horizontal Installation with Added Return

A. Return air from house
B. Existing return air duct

C. To existing furnace or air handler

D. Backflow damper (required)

E. Dry air to crawl space or unconditioned isolated basement 
F. Manual damper (required)

G. Dehumidifier

H. Power damper (optional)

I. Outside air

J. Screened intake hood

A. Added return
B. Return air from house

C. Existing return air duct
D. To existing furnace or air handler

E. Back flow damper (required) 
F. Dry air to crawl space or unconditioned isolated basement 

G. Manual damper (required) 
H. Dehumidifier 

I. Power damper (optional)

J. Outside air

K. Screened intake hood

B

H

F

G

J

I

A

C

D

E

F

E

F

D

G

G

I

H

J

K

A

B

C

Содержание WGDH160UH

Страница 1: ... filter 14 HEPA or MERV 11 Air Filter 14 Fresh Air Return 15 UVC Germicidal Light 15 ASSISTANCE OR SERVICE 16 Whirlpool Gold Models WGDH160UH and WGDV160UH 400 1014 Whirlpool Models WPDH160XS and WPDV160XS You can be killed or seriously injured if you don t immediately You can be killed or seriously injured if you don t follow All safety messages will tell you what the potential hazard is tell you...

Страница 2: ...ical supply and read Electrical Requirements and Location Requirements before purchasing parts LocationRequirements The dehumidifier may be installed on all new or existing furnaces or air handlers used in residential applications The whole house dehumidifier is designed to be located indoors Locate the whole house dehumidifier as close to the return air duct of an existing furnace or air handler ...

Страница 3: ...n return air inlet A Return air inlet B Filter access panel C Low voltage entry D Line voltage entry E Right side discharge air outlet cover F Electrical access panel G Internal component access panel H PVC condensate drain outlet I 10 round discharge air outlet left side shipped right convertible to left or rear Left Side View Front View Right Side View Top View 22 16 A 32 B 22 C D E 49 H F 20 18...

Страница 4: ...ition See Minimum Clearance Requirements in Location Requirements Installation Configuration Options Suspended Cabinet Installation NOTE Ensure there is adequate room to remove the dehumidifier access panels See Minimum Clearance Requirements chart in Location Requirements The suspending installation uses field fabricated 16 all thread rod passing through the top panel and connected to the dehumid...

Страница 5: ... to each area ElectricalRequirements Recommended Grounding Method A 110 to 120 volt 14 5 FLA amps 60 Hz AC only 20 amp fused grounded electrical supply is required All field wiring must be done in accordance with National Electrical Code requirements applicable requirements of UL or local codes where applicable INSTALLATION INSTRUCTIONS InspectShipment This whole house dehumidifier is shipped in o...

Страница 6: ...e return air supply on the existing furnace or air handler NOTE Install ductwork in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air Conditioning Systems latest edition and any local codes 7 Attach the return air supply on the dehumidifier to the return air supply on the existing furnace or air handler near the return air grille NOTE Do not draw air directly from ...

Страница 7: ... Using a 10 duct attach the discharge air supply on the dehumidifier to the return air supply on the existing furnace or air handler NOTE Install ductwork in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air Conditioning Systems latest edition and any local codes 7 Attach the return air supply on the dehumidifier to the return air supply on the existing furnace or ...

Страница 8: ...humidifier in final location See Location Requirements A Return air from house B Existing return air duct C To existing furnace or air handler D Dehumidifier E Power damper optional F Manual damper required G Outside air H Screened intake hood A Return air from house B Existing return air duct C To existing furnace or air handler D Dehumidifier E Power damper optional F Manual damper required G Ou...

Страница 9: ...raw air directly from the kitchen bathroom laundry room or unconditioned isolated basement 8 Attach insulated flexible duct to the discharge air supply on the dehumidifier 9 Run duct to the basement or crawl space of the building Horizontal Installation Horizontal Installation with Added Return A Return air from house B Existing return air duct C To existing furnace or air handler D Backflow dampe...

Страница 10: ... the return air supply on the existing lower level furnace or air handler NOTE Install ductwork in accordance with NFPA 90B Standard for the Installation of Warm Air Heating and Air Conditioning Systems latest edition and any local codes 8 Attach the return air supply on the dehumidifier to the return air supply on the existing upper level furnace or air handler near the return air grille NOTE Do ...

Страница 11: ...sired MakeElectricalConnections 1 Disconnect all power supplies 2 Remove the electrical access panel 3 Remove the control box cover 4 Route the field supply wires to the dehumidifier s electrical connection box 5 Connect the line voltage wire to the L1 terminal of the contactor 6 Connect the neutral wire to the L2 terminal of the contactor 7 Connect the ground wire to the green ground lug marked G...

Страница 12: ...l on furnace or air handler 15 minute time delay On Make X required on UH models only X X V Remove existing wire between T stat and furnace or air handler C R D H G RF R C H V D G1 R G2 H H G N O Field Supplied 24 Volt Relay Optional 24 Volt Damper S2000 S2020 Humidifier Dehumidistat Fan Control GF GT DVA Low Voltage Terminal Furnace Air Handler Interlock G Terminal on existing thermostat G Termin...

Страница 13: ...p UH UV Models Only BK High Speed For UH C MH H Low Pressure Switch Freeze Stat Blower Motor Compressor Overload C S R Start Assist Optional Component R BK Compressor Run Capacitor 3 2 6 5 4 1 W BK R R BK Contactor 115 Volt 60 Hz 20 Amp 1 Phase Power Supply BK R W BU BR OR BK W BK BU Y G BU Low Voltage Terminal C D G GF X R H GT RF V ...

Страница 14: ...and may cause the compressor to cycle off and on unnecessarily Under normal operating conditions the pre filter should be replaced every 6 months However in high particulate concentrations more frequent replacements may be necessary It is recommended that the pre filter be inspected regularly for the first 3 to 4 months to determine the correct replacement intervals To replace the pre filter 1 Loc...

Страница 15: ...lace the UVC light bulb 1 Disconnect power 2 Remove the filter access panel 3 Remove the electrical access panel 4 Remove the internal component access panel 5 Remove the connector from the UVC light and sleeve 6 Remove the connector sleeve from the UVC bulb 7 Remove the UVC bulb 8 Replace the UVC bulb 9 Replace the connector sleeve 10 Replace the connector 11 Replace the internal component access...

Страница 16: ...ol Home Cooling and Heating 14610 Breakers Drive Jacksonville FL 32258 Please include a daytime phone number in your correspondence 400 1014 2007 All rights reserved Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Coconut Grove Florida 8 07 Printed in U S A ...

Отзывы: