background image

4

Venting Requirements

Venting systems for Whirlpool dryers must meet the following 
requirements:

The capacity to handle 200 CFM of air for each dryer in the 
system.

A back pressure of 0.0" (0 cm) to 0.6" (1.5 cm) of water 
column when measured at the connection to the dryer. 

Back pressure should be measured with an empty dryer, a clean 
lint screen and with the dryer operating in the Air Only cycle (no 
heat). Use an inclined manometer, such as Dwyer model 102 (0"-
2" [0 cm - 5.1 cm] range) or Dwyer model 172 (0"-1" [0 cm - 
2.5 cm] range) to measure the back pressure. See the following 
illustration.

Single Dryer Venting Systems

Single dryer venting systems are defined as systems that have 
only one dryer unit attached to a residential-type 4" (10.2 cm) 
diameter rigid metal vent system. For single dryer venting 
systems, see the Installation Instructions that came with your 
dryer to determine the allowable length and number of elbows for 
the venting system. In cases in which the Installation Instructions 
do not address the vent length for the specific number of elbows 
required for a particular application, the following calculations 
may be used. (The total vent system length includes all straight 
and curved portions of the vent system.):

For 90° elbows, reduce the allowable vent system length by 
10 ft (3.05 m). 

For 45° elbows, reduce the allowable vent system length by 
6 ft (1.83 m).

For example, if the Installation Instructions state that a dryer is 
allowed 40 ft (12.2 m) of total vent length with two 90° bends, 
and the installation requires three 90° bends, the total allowable 
vent length would be reduced by 10 ft (3.0 m) (from 40 ft [12.2 m] 
to 30 ft [9.1 m]).

All Whirlpool electric dryer models, including “long vent dryers,” 
that are sold in the United States and Canada are UL listed 
(reference UL2158 standard), and all Whirlpool gas dryer models 
are CSA listed (reference ANSI Z21.5.1 standard). These 
standards require testing at the maximum-rated exhaust vent 
conditions that are published in the product literature for each 
individual model. The designation for the UL or CSA listing can 
be found on or adjacent to the serial label on the product.

“AF” Code

Certain electronic dryer models have airflow detection 
capabilities. (See specific model product literature for details). If 
the airflow in the dryer is extremely low, an “AF” code will be 
displayed on the control panel. For single dryer venting systems, 
this code means that you may have a blocked or partially blocked 
vent or that your overall vent system length is too long. To resolve 
this issue:

Check to see if the vent run from the dryer to the wall is 
crushed. Refer to the “Venting Requirements” section of 
the Use and Care Guide for more information.

Confirm that the vent run from the dryer to the wall is free 
of lint and debris.

Confirm that the exterior vent exhaust hood is free of lint 
and debris.

Confirm that your vent system falls within the 
recommended run length and number of elbows for the 
type of vent you are using. Refer to the “Plan Vent 
System” section of the Use and Care Guide for details.

Select a Timed Dry heated cycle, and restart the dryer.

If the message persists, have your entire home venting 
run cleaned.

For multi-dryer venting systems, the “AF” code means that your 
vent may be blocked or partially blocked or that the venting 
system is creating back pressure in excess of the maximum 
allowable 0.6” (1.5 cm) water column. In this case, the 
engineering firm that designed the system should be consulted.

Multiple Dryer Venting Systems

Multiple dryer venting systems must be designed specifically for 
each application. 

NOTE: It is recommended that an architectural or HVAC 
engineering firm be consulted for designing the dryer venting 
system.

Connecting a number of dryers to a single vent system is 
common in coin-laundry stores and in many apartment buildings. 
Listed here are some requirements for examples of three different 
multiple dryer venting systems. 

Option 1 - Horizontal System

The most common is the horizontal system, in which banks of 
dryers are all located in one room and vented through a common 
duct. See the following illustration for an example of a generic 
horizontal system.

*Minimum spacing required between dryers

A. Dryer - empty and running on Air Only cycle
B. 12" (30.5 cm) min. of straight pipe - measure back 

pressure from the center

C. To vent system
D. 0.6" (1.5 cm) water maximum back pressure

E. Inclined manometer

A

B

C

D

E

A. 4" (10.2 cm) diameter rigid metal back draft damper

A

     1"*
(2.5 cm)

Содержание WED9400SB - 27" Electric Dryer

Страница 1: ...iously injured if you don t follow All safety messages will tell you what the potential hazard is tell you how to reduce the chance of injury and tell you what can happen if the instructions are not followed Your safety and the safety of others are very important We have provided many important safety messages in this manual and on your appliance Always read and obey all safety messages This is th...

Страница 2: ... that have been previously cleaned in washed in soaked in or spotted with gasoline dry cleaning solvents or other flammable or explosive substances as they give off vapors that could ignite or explode Do not allow children to play on or in the dryer Close supervision of children is necessary when the dryer is used near children Before the dryer is removed from service or discarded remove the door ...

Страница 3: ...oisture into the room can also cause damage to walls floors and picture hangers and cause condensation on windows and walls in cold weather Lint Even though the dryer is equipped with a lint screen fine particles of lint can get through the screen and be exhausted out of the dryer Proper venting of the dryer will keep lint from accumulating in the laundry area Heat In order to remove moisture from...

Страница 4: ...Code Certain electronic dryer models have airflow detection capabilities See specific model product literature for details If the airflow in the dryer is extremely low an AF code will be displayed on the control panel For single dryer venting systems this code means that you may have a blocked or partially blocked vent or that your overall vent system length is too long To resolve this issue Check...

Страница 5: ...hese banks then exhausts into a central vertical vent See the following illustration for an example of a combination system A 0 6 1 5 cm water column maximum back pressure B Weighted dampers C Individual dryer exhaust on each floor D 0 1 0 25 cm water column maximum vacuum E Main duct F Barometric damper use depends on exhaust system design G Source of outside air G A B C D F E F F A Central verti...

Страница 6: ...eExhaustSystem 1 Disconnect the exhaust duct from the dryer and from the exhaust hood at the exhaust outlet 2 Inspect the interior of the duct and remove any lint accumulation Be sure that lint is removed from the exhaust hood Lint may collect in the exhaust hood so that the flappers or louvers if installed as part of the exhaust system will not open or close completely After cleaning the exhaust ...

Отзывы: