background image

14

SEQUENCE OF OPERATION

Cooling (cooling only or heat pump)

When the thermostat calls for cooling, the circuit between R and 
G is completed, and the blower relay is energized. The Normally 
Open contacts close, causing the indoor blower motor to 
operate. The circuit between R and Y is also completed; this 
circuit closes the contactor in the outdoor unit starting the 
compressor and outdoor fan motor. Circuit R and O energizes the 
reversing valve, switching it to the cooling position. (The 
reversing valve remains energized as long as selector switch is in 
the COOL position.)

Heating (electric heat only)

When the thermostat calls for heat, the circuit between R and W 
is completed, and the heater sequencer is energized. A time 
delay follows before the heating elements and the indoor blower 
motor come on. Units with a second heat sequencer can be 
connected with the first sequencer to W on the thermostat 
subbase or connected to a second stage on the subbase.

Heating (heat pump)

When the thermostat calls for heat, the circuits between R and Y 
and R and G are completed. Circuit R-Y energizes the contactor 
starting the outdoor fan motor and the compressor. Circuit R and 
G energizes the blower relay starting the indoor blower motor.

If the room temperature should continue to fall, the circuit 
between R and W 1 is completed by the second stage heat room 
thermostat. Circuit R-W 1 energizes a heat sequencer. The 
completed circuit will energize supplemental electric heat (if 
applicable). Units with a second heater sequencer can be 
connected with the first sequencer to W 1 on the thermostat or 
connected to a second heating stage W 2 on the thermostat 
subbase.

Emergency Heat (heating heat pump)

If selector switch on thermostat is set to the emergency heat 
position, the heat pump will be locked out of the heating circuit, 
and all heating will be electric heat (if applicable). A jumper 
should be placed between W 2 and E on the thermostat subbase 
so that the electric heat control will transfer to the first stage heat 
on the thermostat. This will allow the indoor blower to cycle on 
and off with the electric heat when the fan switch is in the AUTO 
position.

AIR HANDLER MAINTENANCE

IMPORTANT: Do not operate system without a filter. A filter is 
required to protect the coil, blower, and internal parts from 
excessive dirt and dust. See “Installation Configurations” for the 
location of the filter in the unit cabinet and the service panel 
giving access to unit filter. The filter is placed in the supply air 
return duct by the installer.

Inspect air filters at least once a month and replace or clean 
as required. Dirty filters are the most common cause of 
inadequate heating or cooling performance.

Replace disposable filters. Cleanable filters can be cleaned 
by soaking in mild detergent and rinsing with cold water.

Install new/clean filters with the arrows on the side pointing in 
the direction of airflow.

Do not replace a cleanable (high velocity) filter with a 
disposable (low velocity) filter unless return air system is 
properly sized for it.

If water should start coming from the secondary drain line, a 
problem exists which should be investigated and corrected. 
Contact a qualified person.

ASSISTANCE OR SERVICE

If you need further assistance, you can write to the below 
address with any questions or concerns: 

Whirlpool

®

 Home Cooling and Heating

317 S. North Lake Blvd.
Altomonte Springs, FL 32701

Please include a daytime phone number in your correspondence.

Accessories

Electric Heat Kits 

Refer to the accessory kit label on the front panel of the air 
handler for electric heat kit accessory options and applications.

Horizontal Drain Pan Kit

Consult with your distributor to obtain the part number for this kit.

Содержание WAHM

Страница 1: ...mplete Installation 12 SEQUENCE OF OPERATION 14 AIR HANDLER MAINTENANCE 14 ASSISTANCE OR SERVICE 14 Accessories 14 WARRANTY 15 Whirlpool Models WAHU WAHM 065937400 You can be killed or seriously injured if you don t immediately You can be killed or seriously injured if you don t follow All safety messages will tell you what the potential hazard is tell you how to reduce the chance of injury and te...

Страница 2: ...nd follow the instructions provided with any tools listed here Tools Needed Parts Needed Check local codes check existing electrical supply and read Ductwork Requirements and Electrical Requirements before purchasing parts OutdoorSystemRequirements The air handler is designed to match and must be used with outdoor units as rated The indoor sections are manufactured with an interchangeable refriger...

Страница 3: ...pply Adequate support must be provided to ensure cabinet integrity Ensure that there is adequate room to remove service and access panels if installing in the horizontal position For correct horizontal coil installation see Installation Configuration Options later in this section IMPORTANT This coil is provided with a secondary drain that should be trapped and piped to a location that will give th...

Страница 4: ... drain pan and the side drain pan 5 Remove the side drain pan from the coil drain pan assembly and install on the opposite side 6 Reinstall the coil drain pan assembly in the same orientation as before by lifting and sliding into the air handler 7 Install the coil support bracket on the opposite side of the air handler A Drain connections B Coil access cover C Blower access cover A Drain connectio...

Страница 5: ...E Use copper conductors only All field wiring must be done in accordance with National Electrical Code applicable requirements of UL and local codes where applicable Electrical wiring disconnect means and over current protection are to be supplied by the installer Refer to the air handler rating plate for maximum over current protection minimum circuit ampacity as well as operating voltage The pow...

Страница 6: ...ension of the blower housing and minimizes air expansion losses from the blower INSTALLATION INSTRUCTIONS InspectShipment These air handlers are completely factory assembled and all components are performance tested Each unit consists of a blower assembly refrigerant coil and controls in an insulated galvanized steel factory finished enclosure Knockouts are provided for electrical wiring entrance ...

Страница 7: ...ow complete drainage of the pan NOTE Horizontal runs must also have an anti siphon air vent standpipe installed ahead of the horizontal run See Typical Condensate Drain Connection in this section An extremely long horizontal run may require an oversized drain line to eliminate air trapping Typical Condensate Drain Connection secondary drain not shown NOTE Do not operate air handler without a drain...

Страница 8: ...ions are ready to be completed 1 Route the suction and liquid lines from the fittings on the indoor coil to the fittings on the outdoor unit Run the lines in as direct a path as possible avoiding unnecessary turns and bends 2 Make sure that the suction line is insulated over the entire exposed length and that both suction and liquid lines are not in direct contact with floors walls ductwork floor ...

Страница 9: ... with electrical power 1 2 or 3 circuits See the air handler Accessory Kit label for number of circuits and ratings 2 Disconnect all power supplies 3 Knock out the correct number of knockouts 1 2 or 3 and install UL listed wires and fittings A Connect yellow to yellow B Connect black to black C Connect ground wire to ground terminal marked GND WARNING Electrical Shock Hazard Electrically ground ai...

Страница 10: ...nnects are used the front panel knockouts will need to be removed 8 Reinstall the air handler blower access panel 9 Reconnect power 10 Dispose of recycle all remaining parts WARNING Electrical Shock Hazard Electrically ground electric heater Connect ground wire to ground terminal marked GND Use copper wire rated for supply connection Correct wire gauge is shown in the chart below Failure to follow...

Страница 11: ...Only Application Thermostat Air Handler Air Handler Air Handler Thermostat Thermostat R R R G G G BU BU W W W Heat Pump Unit BK BK Cooling Application with Electric Heat Heat Pump Application with Electric Heat Condensing Unit Connect common wire only if required See thermostat installation instructions ...

Страница 12: ...ng Diagram Electric Heat Control Circuit Wiring To Be 24 Volt N E C Class 2 Power Factory Wired Power Field Wired Control Factory Wired Control Field Wired Plug Pin Location Opt Amp 350781 1 6 Pin Cap 4 1 5 6 2 3 TB Terminal Block Opt Heaters Used 5 KW HE1 7 5 10 KW HE1 HE2 15 KW HE1 HE2 HE3 20 KW HE1 HE2 HE3 HE4 24 C 3 2 6 5 1 4 W IF 120V GND BR BR W 3 4 R BK MTR Cap 1 Y 14 BK HI 14 Y COM 2 14 R ...

Страница 13: ... matches the maximum cooling capacity rating of the air handler If the outdoor unit is smaller than the maximum cooling capacity rating for the air handler the cooling blower speed may need to be changed Refer to Blower Performance Chart IMPORTANT The cooling blower speed must be set to provide a minimum of 350 CFM airflow per ton 12 000 Btu h of outdoor cooling capacity To change blower speed Ref...

Страница 14: ...position the heat pump will be locked out of the heating circuit and all heating will be electric heat if applicable A jumper should be placed between W 2 and E on the thermostat subbase so that the electric heat control will transfer to the first stage heat on the thermostat This will allow the indoor blower to cycle on and off with the electric heat when the fan switch is in the AUTO position AI...

Страница 15: ...15 ...

Страница 16: ...late Dealer name____________________________________________________ Address ________________________________________________________ Phone number__________________________________________________ Model number __________________________________________________ Serial number __________________________________________________ Installation date ________________________________________________ 0659374...

Отзывы: