GENERAL INFORMATION
R600A Sealed System 2017
n
1-7
Tools & Supplies
Tools & Supplies
•
Vacuum Pump; Preferred to have a rating 6 CFM capacity
•
Gram measuring Scale
•
¼” High Pressure Hose
•
¼” Low Pressure Hose
•
Exclusive manifold gages and hoses should be
used for servicing R600a Appliances. (High, Low, and
Vacuum) Hose requirements for R600a are still being
defined.
•
Rubber Charging Hose with “T” Adapter & Shutoff Valve
•
20’ PVC Recovery Hose
•
R600a Refrigerant Maximum 420 Gram Cylinder
•
Piercing Pliers
•
Pinch Off Pliers
•
Tubing Cutters
•
Rubber Mallet
•
Certified and calibrated combustible gas leak detector to
test for leaks if the system is charged with an A2L or A3
refrigerant.
•
Liquid Charging Fitting
•
Quick Disconnect Fittings
•
Shutoff Valves
•
Fire Extinguisher dry-powder fire extinguisher
rated for Class B fires
•
Ventilation Fan
•
Note: All tools are sug
g
ested to be Spark
less tools.
Whirlpool requires and AHAM recommends using a leak
detector during the entire process. If gas or a leak is
detected, stop work and do not use tools that could cause
a spark during operation.
Figure 1
Figure 1: This is an example of a manifold gauge,
vacuum pump combination. Figure 2: Typical 6 cfm
vacuum pump without gauges. Figure 3: Vulkan R600a
Cylinder
Figure 2
Figure 3: Vulkan
R600a Cylinder