12
Plan Vent System
Choose your exhaust installation type
Recommended exhaust installations
Typical installations vent the dryer from the rear of the dryer.
Alternate installations for close clearances
Venting systems come in many varieties. Select the type best for
your installation. Two close-clearance installations are shown.
Refer to the manufacturer’s instructions.
NOTE: The following kits for close clearance alternate
installations are available for purchase. For information on
ordering, see “Assistance or Service.”
■
Over-the-Top Installation:
Part Number 4396028
■
Periscope Installation (for use with dryer vent to wall vent
mismatch):
Part Number 4396037 - for mismatch of 0" (0 cm) to
18" (45.72 cm)
Part Number 4396011 - for mismatch of 18" (45.72 cm) to
29" (73.66 cm)
Part Number 4396014 - for mismatch of 29" (73.66 cm) to
50" (127 cm)
Special provisions for mobile home installations
The exhaust vent must be securely fastened to a noncombustible
portion of the mobile home structure and must not terminate
beneath the mobile home. Terminate the exhaust vent outside.
Determine vent path
■
Select the route that will provide the straightest and most
direct path outdoors.
■
Plan the installation to use the fewest number of elbows and
turns.
■
When using elbows or making turns, allow as much room as
possible.
■
Bend vent gradually to avoid kinking.
■
Use the fewest 90° turns possible.
Determine vent length and elbows needed for best
drying performance
■
Use the Vent system chart below to determine type of vent
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specified in
the Vent system chart. Exhaust systems longer than those
specified will:
■
Shorten the life of the dryer.
■
Reduce performance, resulting in longer drying times and
increased energy usage.
The Vent system chart provides venting requirements that will
help to achieve the best drying performance.
Vent system chart
Install Vent System
1. Install exhaust hood. Use caulking compound to seal exterior
wall opening around exhaust hood.
2. Connect vent to exhaust hood. Vent must fit inside exhaust
hood. Secure vent to exhaust hood with 4" (10.2 cm) clamp.
3. Run vent to dryer location. Use the straightest path possible.
See “Determine vent path” in “Plan Vent System.” Avoid 90º
turns. Use clamps to seal all joints. Do not use duct tape,
screws or other fastening devices that extend into the interior
of the vent to secure vent.
A. Exhaust hood
B. Flexible metal vent or rigid metal vent
C. Elbow
A. Over-the-top installation (also available with
one offset elbow)
B. Periscope installation
A
B
C
A
B
Number of
90º turns
or elbows
Type of
vent
Box or
louvered
hoods
Angled
hoods
0
Rigid metal
Flexible metal
36 ft (11 m)
28 ft (8.5 m)
26 ft (7.9 m)
22 ft (6.7 m)
1
Rigid metal
Flexible metal
26 ft (7.9 m)
18 ft (5.5 m)
16 ft (4.9 m)
12 ft (3.7 m)
2
Rigid metal
Flexible metal
16 ft (4.9 m)
8 ft (2.8 m)
6 ft (1.8 m)
2 ft (0.6 m)