5-7
OVERLOAD PROTECTOR
Refer to page 4-14 for the procedure for servic-
ing the overload protector.
1.
Unplug air conditioner or disconnect power.
2.
Disconnect the overload protector wires.
3.
Set the ohmmeter to the R x 1 scale.
4.
Touch the ohmmeter test leads to the
overload protector terminal and connec-
tor.
5.
The meter should indicate continuity (0
Ω
).
COMPRESSOR
Refer to page 4-14 for the procedure for servic-
ing the compressor.
1.
Unplug air conditioner or disconnect power.
2.
Disconnect the three wires from the com-
pressor terminals.
3.
Set the ohmmeter to the R x 1 scale.
4.
Clip an ohmmeter test lead to the overload
protector terminal
C (W)
.
5.
Touch the free test lead to the following
compressor terminals. The meter should
indicate as shown:
Terminal
R (U)
= 0.5
Ω
Terminal
S (V)
= 3.16
Ω
Terminal
S (V)
to
R (U)
= 3.65
Ω
R
(U)
S
(V)
C
(W)
Red
Black
Blue
Compressor
Terminals
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.