background image

11

VENTING DESIGN SPECIFICATIONS

This section is intended for architectural designer and builder/
contractor reference only.
NOTES:

Vent materials needed for installation are not provided with 
microwave hood.

We do not recommend using a flexible metal vent.

To avoid possible product damage, be sure to vent air outside, 
unless using recirculation installation. Do not vent exhaust air 
into concealed spaces, such as spaces within walls or 
ceilings, attics, crawl spaces or garages.

For optimal venting installation, we recommend:

using roof or wall caps that have back draft dampers

using a rigid metal vent

using the most direct route by minimizing the length of the 
vent and number of elbows to provide efficient performance

using uniformly sized vents

using duct tape to seal all joints in the vent system

using caulking compound to seal exterior wall or roof opening 
around cap

not installing 2 elbows together, for optimal hood performance

If venting through the wall, be sure that there is proper clearance 
within the wall for the damper to open fully.
If venting through the roof, and rectangular to round transition is 
used, be sure there is at least 3" (7.6 cm) of clearance between 
the top of the microwave oven and the transition piece. See 
“Rectangular to Round Transition” illustration.

Rectangular to Round Transition

NOTE: The minimum 3" (7.6 cm) clearance must exist between 
the top of the microwave oven and the rectangular to round 
transition piece so that the damper can open freely and fully.

Recommended Standard Fittings

The following length equivalents are for use when figuring vent 
length. See the examples in “Recommended Vent Length.”

Roof venting

Roof cap

Wall venting

Wall cap

A. Roof cap
B. 6" (15.2 cm) min. diameter round vent

C. Elbow (for wall venting only)
D. Wall cap

E. 3

¹⁄₄

" x 10" to 6" (8.3 x 25.4 cm to 15.2 cm) 

rectangular to round transition piece

F. Vent extension piece, at least 3" (7.6 cm) high

A. Rectangular to round transition piece: 3

¹⁄₄

" x 10" to 6" = 5 ft

(8.3 x 25.4 cm to 15.2 cm = 1.5 m)

B. Roof cap: 3

¹⁄₄

" x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m)

C. 90° elbow: 3

¹₄

" x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m)

D. 90° elbow: 6" = 10 ft (15.2 cm = 3 m)

E. Wall cap: 3

¹⁄₄

" x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m)

F. 45° elbow: 6" = 5 ft (15.2 cm = 1.5 m)

G. 90° flat elbow: 3

¹⁄₄

" x 10" = 10 ft (8.3 x 25.4 cm = 3 m)

A

B

C

E

F

D

3" (7.6 cm)

A                           B                            C

D                  E                    F               G

Содержание 8206327

Страница 1: ...Install Damper Assembly 9 Install the Microwave Oven 9 Complete Installation 10 VENTING DESIGN SPECIFICATIONS 11 ASSISTANCE 12 Replacement Parts 12 Accessories 12 IMPORTANT Read Installation Instructions thoroughly before beginning installation Save Installation Instructions for local house inspector s use 8206327 You can be killed or seriously injured if you don t immediately You can be killed or...

Страница 2: ...nd building materials are not designed to withstand the heat produced by the microwave oven for cooking Check with your builder or cabinet supplier to make sure that the materials used will not discolor delaminate or sustain other damages Special Requirements For Wall Venting Installation Only Cutout must be free of any obstructions so that the vent tube fits properly and the damper blade opens fr...

Страница 3: ...ground prong Do not use an adapter Do not use an extension cord Failure to follow these instructions can result in death fire or electrical shock WARNING GROUNDING INSTRUCTIONS SAVE THESE INSTRUCTIONS For all cord connected appliances The microwave oven must be grounded In the event of an electrical short circuit grounding reduces the risk of electric shock by providing an escape wire for the elec...

Страница 4: ...e oven is set for ventless recirculating installation For wall or roof venting changes must be made to the venting system NOTE Skip this section if you are using ventless recirculating installation Keep the damper assembly in case the venting method is changed or the microwave oven is reinstalled in another location where wall or roof venting may be used Wall Venting Installation Only 1 Remove scr...

Страница 5: ...e back of microwave oven Lower blower motor back into microwave oven A Exhaust port IMPORTANT If blower motor is not positioned with flat sides facing the back of the microwave oven as shown performance will be poor 6 Reattach blower motor to back of microwave oven with 2 screws removed in Step 3 of Wall Venting Installation Only Securely tighten screws NOTE If blower motor is not correctly orient...

Страница 6: ... Wall Studs at Corner Holes Figure 1 No Wall Studs at Corner Holes Figure 2 NOTE If wall stud is within 6 15 2 cm of the vertical centerline see Mark Rear Wall section only recirculation or roof venting installation can be done One Wall Stud at Two Corner Holes Figure 3 Wall Studs at All Four Corner Holes Figure 4 A Corner holes on mounting plate B Cabinet opening vertical centerline C Wall stud c...

Страница 7: ...omplete the 12 x 4 30 5 x 10 2 cm rectangle This is the venting cutout area 11 Cut a 3 4 19 mm hole in one corner of the cutout area 12 Using a keyhole saw cut out the venting cutout area Drill Holes in Rear Wall In addition to being installed on at least 1 wall stud the mounting plate must attach to the wall at all 4 corner holes If the holes are not over wall studs use four 1 4 20 x 3 round head...

Страница 8: ... through the wall and to open 3 Position mounting plate on the wall making sure that the top of the mounting plate is aligned with the front edge of the upper cabinet 4 Push the 2 bolts with toggle nuts through the drywall and finger tighten the bolts to make sure toggle nuts have opened against drywall 5 Insert 2 lag screws into the remaining 2 corner holes 6 If installing on a second wall stud i...

Страница 9: ...s Install the Microwave Oven IMPORTANT The control side of the unit is the heavy side Handle the microwave oven gently 1 Place a washer on each 1 4 20 x 3 bolt and place inside upper cabinet near the 3 8 10 mm holes 2 Make sure the microwave oven door is closed and taped shut 3 Using 2 or more people lift microwave oven and hang it on support tabs at the bottom of mounting plate NOTE Do not grip o...

Страница 10: ...te Then secure with sheet metal screw NOTE The screw cannot be installed if the damper assembly is not positioned as shown 2 Connect vent to damper assembly Complete Installation 1 Refer to the Use and Care Guide for instructions on how to install filters into your model 2 Plug microwave oven into grounded 3 prong outlet 3 Reconnect power 4 Check the operation of microwave oven by placing 1 cup 25...

Страница 11: ...amper to open fully If venting through the roof and rectangular to round transition is used be sure there is at least 3 7 6 cm of clearance between the top of the microwave oven and the transition piece See Rectangular to Round Transition illustration Rectangular to Round Transition NOTE The minimum 3 7 6 cm clearance must exist between the top of the microwave oven and the rectangular to round tr...

Страница 12: ...front frame of the microwave oven If you need additional assistance call us at our toll free number listed in the Use and Care Guide or visit us on the Web Replacement Parts If any of the installation hardware needs to be replaced call us at our toll free number listed in the Use and Care Guide and reference the appropriate part number listed here Accessories Filler Panel Kits are available from y...

Отзывы: