AUDIO PAGE PORT INSTALLATION INSTRUCTIONS:
The ZC-312 can be connected to an audio page port only if the audio page port provides:
(A) A 600 ohm, low power page output, capable of passing DC loop current.
(B) Transmission of DTMF touch tone, or rotary dial pulses.
(C) A dry contact that is normally open, closes when paging and reopens when the page is completed.
If these conditions are met, then connect Tip and Ring as shown in Figure 12.
FIGURE 12
CONNECTING TO A 600 OHM AUDIO PAGE PORT
CO/Centrex and Analog Station Level Paging Installation Instructions:
The ZC-312 can be interfaced to ring start paging applications such as a CO/Centrex line or analog station level line, by using Wheelock's
TPI-100 Telephone Paging Interface. Connect the ZC-312 to the TPI-100 as shown in Figure 13.
FIGURE 13
CONNECTION TO TPI-100 INTERFACE
NOTES
1.
Place talk battery selector switch in the "OFF" position.
2.
Place "TPI Interface" selector jumper in the "LO" position.
3.
If TPI-100 and ZC-312 use separate power supplies, then install wire between GND (TB1, terminal 5) on TPI-100 and GND (TB1, terminal 5) on
ZC-312.
4.
For additional information on TPI-100 refer to its installation instructions.
P81982 K
Sheet 19 of 21
OPERATING INSTRUCTIONS:
NOTE
Check telephone system's manufacturer's installation
instructions for any other audio page port connection
considerations.