The visual notification appliances shall be Wheelock Series RSSR Strobe Appliances with Red Lens, or approved
equals. The strobes shall be UL 1638 approved for indoor use only. All strobes shall be certified to meet FCC Part
15 Class B. The strobe appliances shall produce a flash rate of one (1) per second minimum over the Regulated
Voltage range of 16 to 33 VDC for 24-volt models. All inputs shall be polarized for compatibility with standard
reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP).
All visual appliances shall incorporate a Xenon flashtube enclosed in a rugged Lexan® red lens. The Series
RSSR Strobes with Red Lens shall be of a low current design. Series RSSR Strobe Appliances with Red Lens
shall incorporate circuitry for synchronized strobe flash and shall be designed for compatibility with Wheelock’s
Series SM, DSM Sync Module(s) or Wheelock’s PS-12/24-8MP and PS-12/24-8CP Power Supplies with Wheelock’s
Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the
sync module fails to operate (i.e., contacts remain closed), the strobes shall revert to a non-synchronized flash
rate.
The visual appliance shall be designed for indoor surface or flush mounting. Series RSSR with Red Lens models
shall employ a patented Strobe Mounting Plate that shall allow mounting to a single-gang,
double-gang, 4 inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an
NATP (Notification Appliance Trim Plate) shall be provided. An attaching cover plate shall be provided to give the
appliance an attractive appearance. The aesthetic appearance shall not have any mounting holes or screw heads
visible when the installation is completed.