background image

P84022 F 

Sheet 3 of 6 

When calculating the total average, peak or inrush currents:  Use Table 2A and 2B to determine the highest value of “Rated Average 
Current”  for an individual strobe (across the expected operating voltage range of the strobe) to determine the highest value of “Rated 
Inrush Current” or “Rated Peak Current” (whichever is higher) of an individual strobe (across the expected voltage range of the 
strobe) then multiply the value by the total number of strobes; be sure to add the currents for any other appliances, including audible 
signaling appliances, powered by the same source and include any required safety factors. 

 

If the inrush current or peak current exceeds the power supplies’ inrush capacity, the output voltage provided by the power supplies 
may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of 
power supplies.  For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or 
lack of battery backup across the output) may exhibit this characteristic. 

 

CAUTION:  

Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.

 

 
 

LIGHT DISTRIBUTION: 

 

Table 3:  Horizontal Plane 

Horizontal 15W 

30W 

75W 

110W 

Angle 

(in deg.) 

UL  

Min. 

Typ. 

15W 

UL  

Min. 

Typ.  

30W 

UL  

Min. 

Typ.  

75W 

UL  

Min. 

Typ.  

110W 

  0 

15.0 

24 

30.0 

46 

75.0 

103 

110.0 

149 

  5 

13.5 

24 

27.0 

46 

67.5 

103 

  99.0 

152 

10  13.5 24 27.0 45 67.5 104  

 

99.0 151 

15  13.5 24 27.0 46 67.5 100  

 

99.0 151 

20  13.5 23 27.0 43 67.5 101  

 

99.0 148 

25 

13.5 

23 

27.0 

43 

67.5 

  98 

  99.0 

140 

30 

11.3 

21 

22.5 

41 

56.3 

  94 

  82.5 

135 

35 

11.3 

20 

22.5 

40 

56.3 

  89 

  82.5 

129 

40 

11.3 

19 

22.5 

39 

56.3 

  83 

  82.5 

124 

45 

11.3 

18 

22.5 

41 

56.3 

  81 

  82.5 

133 

50 

  8.3 

18 

16.5 

36 

41.3 

  77 

  60.5 

121 

55 

  6.8 

12 

13.5 

27 

33.8 

  60 

  49.5 

  85 

60 

  6.0 

11 

12.0 

30 

30.0 

  59 

  44.0 

  95 

65 

  5.3 

13 

10.5 

35 

26.3 

  71 

  38.5 

113 

70 

  5.3 

17 

10.5 

29 

26.3 

  73 

  38.5 

  81 

75 

  4.5 

13 

  9.0 

22 

22.5 

  53 

  33.0 

  72 

80 

  4.5 

  8 

  9.0 

17 

22.5 

  35 

  33.0 

  50 

85 

  3.8 

  7 

  7.5 

15 

18.8 

  30 

  27.5 

  38 

90 

  3.8 

  6 

  7.5 

15 

18.8 

  30 

  27.5 

  43 

Table 3A:  Vertical Plane 

Vertical 15W 

30W 

75W 

110W 

Angle 

(in deg.) 

UL 

Min. 

Typ.  

15W 

UL  

Min. 

Typ.  

30W 

UL  

Min. 

Typ.  

75W 

UL  

Min. 

Typ.  

110W 

  0 

15.0 

24 

30.0 

46 

75.0 

103 

110.0 

149 

  5 

13.5 

24 

27.0 

46 

67.5 

103 

  99.0 

149 

10  13.5 24 27.0 46 67.5 103  

 

99.0 137 

15  13.5 24 27.0 45 67.5 102  

 

99.0 120 

20  13.5 24 27.0 41 67.5 104  

 

99.0 110 

25 

13.5 

21 

27.0 

48 

67.5 

  89 

  99.0 

129 

30 

13.5 

23 

27.0 

40 

67.5 

  96 

  99.0 

114 

35 

  9.8 

22 

19.5 

45 

48.8 

  91 

  71.5 

119 

40 

  6.9 

13 

13.8 

39 

34.3 

  57 

  50.6 

109 

45 

  5.1 

  9 

10.2 

24 

25.5 

  36 

  37.4 

  66 

50 

  4.0 

  9 

  8.1 

16 

20.0 

  33 

  29.7 

  45 

55 

  3.3 

  8 

  6.6 

15 

16.3 

  31 

  24.2 

  43 

60 

  2.7 

  8 

  5.4 

15 

13.5 

  31 

  19.8 

  40 

65 

  2.4 

  8 

  4.8 

14 

12.0 

  31 

  17.6 

  40 

70 

  2.3 

  8 

  4.5 

15 

11.3 

  31 

  16.5 

  39 

75 

  2.0 

 8 

  4.0 

14 

10.0 

  31 

  14.3 

  39 

80 

  1.8 

  8 

  3.6 

13 

  9.0 

  27 

  13.2 

  36 

85 

  1.8 

  7 

  3.6 

13 

  9.0 

  27 

  13.2 

  37 

90 

  1.8 

  3 

  3.6 

  9 

  9.0 

  12 

  13.2 

  16 

 

Содержание RSS-1215W

Страница 1: ...H ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION INSTALLATION AND OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS SPECIFICATIONS Table 1 Ratings Per UL 1971 Model Regulated Voltage VDC VRMS Voltage Range Limit VDC VRMS Strobe Candela CD Mounting Options RSS ...

Страница 2: ...odels Rated Average Current Voltage 1215W MEAN RMS 8 0VDC 0 220 0 246 12 0VDC 0 129 0 187 17 5VDC 0 099 0 163 8 0VRMS 0 246 12 0VRMS 0 198 17 5VRMS 0 170 Rated Peak Current Voltage 1215W 8 0VDC 0 410 12 0VDC 0 426 17 5VDC 0 438 8 0VRMS 0 414 12 0VRMS 0 426 17 5VRMS 0 444 Rated Inrush Current Voltage 1215W 8 0VDC 0 081 12 0VDC 0 100 17 5VDC 0 145 8 0VRMS 0 098 12 0VRMS 0 140 17 5VRMS 0 190 Rated av...

Страница 3: ... Min Typ 15W UL Min Typ 30W UL Min Typ 75W UL Min Typ 110W 0 15 0 24 30 0 46 75 0 103 110 0 149 5 13 5 24 27 0 46 67 5 103 99 0 152 10 13 5 24 27 0 45 67 5 104 99 0 151 15 13 5 24 27 0 46 67 5 100 99 0 151 20 13 5 23 27 0 43 67 5 101 99 0 148 25 13 5 23 27 0 43 67 5 98 99 0 140 30 11 3 21 22 5 41 56 3 94 82 5 135 35 11 3 20 22 5 40 56 3 89 82 5 129 40 11 3 19 22 5 39 56 3 83 82 5 124 45 11 3 18 22...

Страница 4: ...he backbox used with each mounting option If these limits are exceeded there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product Although the limits shown for each mounting option comply with the National Electrical Code NEC Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wir...

Страница 5: ...OBES BEING SUFFICIENT TO MAKE SURE THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION REGARDLESS OF THE VIEWER S ORIENTATION FAILURE TO DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS RSS RSSP 24110 strobe models are Listed for use in sleeping or non sleeping areas when installed in accordance with appropriate NFPA Standards and the Authority Having J...

Страница 6: ...ATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT WHEELOCK MAKES NO REPRESENTATION OR WARRANTY OF ANY OTHER KIND EXPRESS IMPLIED OR STATUTORY WHETHER AS TO MERCHANTABILITY FITNESS FOR A PARTICULAR PURPOSE OR ANY OTHER MATTER USERS ARE SO...

Отзывы: