P83984 E 

Sheet 4 of 9

 

 

WARNING:  THE NS4-MCW APPLIANCE MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL 

BEFORE THEY ARE INSTALLED.  THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE 
INSTRUCTIONS.  INCORRECT SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN 
PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

 

 

WARNING: THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE 

INSTALLATION.  WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT 
“CLICKS” IN PLACE.  AFTER CHANGING THE CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY 
PROPER OPERATION (FLASH RATE MUST BE BETWEEN 60-64 FLASHES PER MINUTE).  IMPROPER SETTING OF THE 
CANDELA SELECT SWITCH, WHETHER IT IS ON AN INCORRECT SETTING OR IN BETWEEN TWO CANDELA POSITIONS, 
MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THE PRODUCT, WHICH COULD RESULT IN PROPERTY 
DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

SETTINGS: 

 

NOTE

:

  The Code 3 Horn incorporates the temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second 

on, 1-1/2 off and repeat) specified by ANSI/NFPA for standard emergency evacuation signaling.  

The Code 3 Horn should be used 

only for fire evacuation signaling and not for any other purpose. 

 

Figure 1:  Showing Location of Jumper Plug and Candela Selector.

 

JUMPER 

PLUGS

    CANDELA 

    SELECTOR

TOP

PLUG

NO PLUG

HI

LOW

CODE 3

HORN

STB

AUD

WARNING:

TO PREVENT ELECTRIC SHOCK, DO NOT REMOVE

THIS COVER.  NO USER SERVICEABLE PARTS INSIDE.

   

15

75

1

30

1 0

 CANDELA

 POINTER

BOTTOM VIEW

 

 

NOTE

:  Factory setting is on High dB, Code 3 and 15cd. 

 
 

Figure 2:  Jumper plug settings for High dB and Code 3. 

 

Figure 3:  Jumper plug settings for Low dB and Continuous Horn. 

 

SHOWN 

SET ON 

HI dB 

 CENTER PIN 

 IS NOT USED

 SHOWN

 SET ON 

 CODE 3

 

 

 

 CENTER PIN 

 IS NOT USED

 SHOWN

 SET ON

 CONT' HORN *

SHOWN 

SET ON 

LOW dB

 

 

Figure 4:  Jumper plug settings for Low dB and Code 3.

 

 

Figure 5:  Jumper plug settings for High dB and Continuous Horn.

 

 

 CENTER PIN 

 IS NOT USED

SHOWN 

SET ON 

LOW dB

 SHOWN 

 SET ON 

 CODE 3

 

(Use needle nose pliers to pull and properly set the jumper 
plugs.)

 

 

 

 CENTER PIN 

 IS NOT USED

 SHOWN

 SET ON

 CONT' HORN *

SHOWN 

SET ON 

HI dB 

 

No jumper plugs are needed for Continuous Horn and low dB settings.  
However, it is recommended that the jumper plug be retained in the unit 
for future use (if needed) as shown in Figure 3, 4 and 5.

 

 

NOTE

:  

The NS4-MCW must be set for Code 3 horn when used with the sync module. 

 

*  Continuous horn operation without sync module. 

 

Содержание NS4-24MCW

Страница 1: ...on of circuit wiring by a FACP NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters WARNING THE NS HORN STROBE IS A FIRE ALARM DEVICE DO NOT PAINT NOTE All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems CAN ULC S524 01 and Canadian Electrical Code Part 1 Final acceptance is...

Страница 2: ...30 1 210 The time duration for the peak current is 1 millisecond NOTE Inrush current is less than rated peak current Table 3A UL ULC Horn Current Ratings AMPS UL Voltage ULC Voltage High dBA Low dBA 16 0VDC 20 0VDC 0 019 0 012 24 0VDC 24 0VDC 0 028 0 015 33 0VDC 31 0VDC 0 039 0 018 16 0VRMS 20 0VRMS 0 029 0 016 24 0VRMS 24 0VRMS 0 044 0 019 33 0VRMS 31 0VRMS 0 061 0 022 WARNING MAKE SURE THAT THE ...

Страница 3: ... 8 4 7 5 9 18 8 22 27 5 31 90 3 8 8 7 5 15 18 8 38 27 5 48 Table 4A Vertical Plane UL 1971 Vertical 15cd 30cd 75cd 110cd Angle in deg UL Min Typ 15cd UL Min Typ 30cd UL Min Typ 75cd UL Min Typ 110cd 0 15 0 23 30 0 49 75 0 116 110 0 155 5 13 5 26 27 0 51 67 5 123 99 0 166 10 13 5 21 27 0 42 67 5 105 99 0 139 15 13 5 19 27 0 39 67 5 95 99 0 134 20 13 5 19 27 0 36 67 5 82 99 0 116 25 13 5 17 27 0 34 ...

Страница 4: ...t specified by ANSI NFPA for standard emergency evacuation signaling The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose Figure 1 Showing Location of Jumper Plug and Candela Selector JUMPER PLUGS CANDELA SELECTOR TOP PLUG NO PLUG HI LOW CODE 3 HORN STB AUD WARNING TO PREVENT ELECTRIC SHOCK DO NOT REMOVE THIS COVER NO USER SERVICEABLE PARTS INSIDE 15 75 1...

Страница 5: ...DULE When the sync module is used the audible tone will be Code 3 sound only Refer to Sync Module Installation Instruction sheets SM P83123 DSM P83177 or PS 12 24 8 P83862 for additional information Audible will operate only with power applied to both strobe and audible Figure 8 1 The NS4 MCW Appliance has in out wiring terminals that accepts two 12 to 18 American Wire Gauge AWG wires at each scre...

Страница 6: ...tress on the product from wiring C A B D FLUSH MOUNTING STD SINGLE GANG BACKBOX 6 32 X 7 8 SCREWS NS MOUNTING PLATE NSMP NS BEAUTY PLATE SUPPLIED MAXIMUM NUMBER OF CONDUCTORS BACKBOX DEPTH AWG 18 AWG 16 AWG 14 AWG 12 2 1 2 8 4 4 4 3 1 8 8 8 8 8 MAXIMUM NUMBER OF CONDUCTORS AWG 18 AWG 16 AWG 14 AWG 12 8 8 8 8 NS MOUNTING PLATE NSMP NS MOUNTING PLATE NSMP NS MOUNTING PLATE NSMP NS BEAUTY PLATE SUPPL...

Страница 7: ... for each mounting option is supplied 7 Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product 8 When terminating field wires do not use more lead length than required Excess lead length could result in insufficient wiring space for the signaling appliance 9 Use care and proper techniques to position the field wires in the backbox so th...

Страница 8: ...idelines or restrictions on wiring and or locating Notification Appliance Circuits NAC and notification appliances Some system communication circuits and or audio circuits for example may require special precautions to assure electrical noise immunity e g audio crosstalk NOTE This equipment has been tested and found to comply with the limits for a Class B digital appliance pursuant to Part 15 of t...

Страница 9: ... SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIR...

Отзывы: