MOUNTING NOTES: 
 

CAUTION:  

Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and 

conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used. 
 

1.  Multitone Strobe models can be flush mounted to a standard 4 inch square by 2-1/8 inch deep electrical box (Figure A) or a 

standard 2-gang by 3-1/2" inch minimum deep electrical box (Figure B).   

 

2.  All models can also be surface mounted to Wheelock's model IOB backbox (Figure C or D) or to a 4" square backbox (model 

DBB or BB) with Wheelock's model ISP extender (Figure F and G). 

 

3.  Multitone Strobe models can also be retrofitted to an existing FSB backbox to replace Wheelock's model 7001 Strobe Horn 

when used with Wheelock adapter plate model RP (Figure E). 

 

4.  All models are supplied with four snap-in covers to hide the mounting holes and provide an attractive installation.  The snap-in 

covers are interchangeable and have slots on each end so they can be removed if necessary (by prying them up with a thin blade 
screwdriver).  To insert snap-in cover, slide the outside edge of the cover (furthest edge from the strobe lens) partially into the 
mounting hole recess; then align the cover so it is parallel to the grille (not tilted) and snap cover into place. 

 

5.  The IOB surface backbox has 1/2-inch conduit knockouts on two sides.  It has a variety of knockouts on the back for mounting 

it to recessed electrical boxes and for wire entrances (Figure D).  It can also be mounted to a surface with the two mounting ears 
that are supplied.  The ears slide into slots on the back of the box (Figure C).  Use appropriate anchors for the wood screws that 
are supplied with the box (if necessary). 

 

6.  The IOB includes a prefastened gasket and four hole plugs.  Make sure the condensation drain holes on the box face down and 

that the box is vertical to permit drainage of any moisture.  Use the mounting ears to secure the box (do not use the back 
knockouts).  Use the hole plugs to seal the unused mounting holes on the Multitone grille (press them in securely from the 
backside of the grille).  Mount the unit to the IOB with the four #8-18 screws supplied with the box. 

 

7.  Mounting hardware for each mounting option is supplied. 

 

8.  Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.  When 

extension rings are required, conduit should enter through the backbox, not the extension ring.  Use Steel City #53151 (1-1/2" 
deep) or #53171 (2-1/8" deep) extension rings (as noted in the mounting options) or equal with the same cutout area. 

 

9.  When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring 

space for the signaling device. 

 

10.  Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum 

stress on the product.  This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 

 

11.  Do not pass additional wires (used for other than the signaling device) through the backbox.  Such additional wires could result 

in insufficient wiring space for the signaling device. 

 
 
 
 
 
 
 
 
 
 

Содержание MT-12-LS

Страница 1: ...f circuit wiring by a Fire Alarm Control Panel FACP NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters WARNING PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION INSTALLATION AND OR OPERATION OF THESE PRODUCTS ...

Страница 2: ... 88 79 75 82 75 Anechoic dBA is measured on axis in a non reflective free field test room using fast meter response For peak dBA measured with peak meter response add 5 dBA to anechoic values shown in Table 3 Reverberant dBA is a minimum UL rating based on sound power measurements in a reverberant test room WARNING MULTITONE STROBE MODELS SET ON CODE 3 TONE WITH STANDARD dBA DO NOT MEET THE 75 dBA...

Страница 3: ...plies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies For example an auxiliary power supply that lacks filtering at its output stage either via lack of capacitance and or lack of battery backup across the output may exhibit this characteristic CAUTION Strobes are not designed to be used on coded syste...

Страница 4: ...odels Volts 20 0 22 0 24 0 26 0 28 0 31 0 10 5 12 0 15 6 LS DC 1 0 1 1 1 3 1 4 1 5 1 7 0 9 1 0 1 5 FWR 1 0 1 1 1 3 1 4 1 6 1 8 0 9 1 0 1 5 LSM DC 1 0 1 2 1 3 1 4 1 5 1 6 0 9 1 0 1 6 FWR 1 0 1 2 1 3 1 4 1 5 1 7 0 9 1 0 1 5 MS DC 1 0 1 1 1 2 1 4 1 5 1 6 0 9 1 0 1 6 FWR 1 0 1 1 1 2 1 4 1 4 1 6 0 9 1 0 1 4 IS DC 1 1 1 2 1 3 1 3 1 4 1 5 FWR 1 0 1 1 1 2 1 3 1 3 1 4 NOTE ADA guidelines presently specify ...

Страница 5: ...T IS BELOW THE 75 dBA MINIMUM CODE REQUIREMENT FOR PUBLIC MODE FIRE PROTECTION STEP 2 Set desired alarm tone as follows refer to Figure 3 and Table 8 Multitone Strobe Appliances are field set for any one of eight alarm tones by setting a four position switch SW1 as shown in Figure 3 and Table 8 Use SW1 POS 2 3 4 to select the desired alarm tone Table 8 Switch Settings Tone POS POS POS 2 3 4 Horn 1...

Страница 6: ...m wiring MAXIMUM NUMBER OF CONDUCTORS Figure A FLUSH 4 BOX 2 8 32x1 SCREWS 4 SQ X 2 1 8 DEEP BACKBOX 4 SCREW COVERS 8 4 8 8 AWG 18 AWG 16 AWG 14 AWG 12 Figure B 8 8 8 8 AWG 18 AWG 16 AWG 14 AWG 12 MAXIMUM NUMBER OF CONDUCTORS 4 6 32x1 4 SCREW COVERS SCREWS FLUSH 2 GANG BOX 2 GANG x 3 1 2 DEEP BACKBOX Figure C 8 8 8 8 AWG 18 AWG 16 AWG 14 AWG 12 MAXIMUM NUMBER OF CONDUCTORS 2 WOOD 4 8 18x1 4 SCREW ...

Страница 7: ...lso be mounted to a surface with the two mounting ears that are supplied The ears slide into slots on the back of the box Figure C Use appropriate anchors for the wood screws that are supplied with the box if necessary 6 The IOB includes a prefastened gasket and four hole plugs Make sure the condensation drain holes on the box face down and that the box is vertical to permit drainage of any moistu...

Страница 8: ...d or audio circuits for example may require special precautions to assure electrical noise immunity e g audio crosstalk The Multitone Strobe products and these instructions are copyrighted by Wheelock and Multitone Strobe products contain proprietary confidential and trade secrets of Wheelock No part of the Multitone Strobe products and these instructions may be photocopied printed or reproduced i...

Страница 9: ...ONDITIONS BEYOND MANUFACTURER S CONTROL SOME OF THE MANUFACTURER S PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS THE MANUFACTURER DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIREMENTS THE MANUFACTURER S...

Отзывы: