Figure 3: Temporal (Code 3) / Non-Temporal(Continuous) Select
PINS
LABEL
TERMINALS
NON-TEMPORAL
TEMPORAL
BEAUTY
PLUGS
NOTE
: Temporal (shorted) Non-Temporal (open)
Unit is shipped from factory with Temporal (Code 3) selected (jumper to right). Installer can select Non-Temporal (Continuous)
audible signal by moving the factory installed jumper to the left one position. The jumper will be placed only on the left pin, leaving
the circuit open to select Continuous. Detach ‘Beauty Plugs’ from rear of grille before installing unit.
Figure 4.
Figure 5.
3/8"
ROUTE WIRE
THROUGH
NOTCH AS
SHOWN
MOUNTING PROCEDURES:
Use this mounting procedure to position the field wires in the backbox so that they use minimum space and produce minimum stress
on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing.
1) Bend the 4 field wires 90
°
as shown in Figure 4.
2) Connect the 2 field wires to each screw terminal (in-out wiring) and dress the 2 wires through the slot as shown in Figure 5
(polarity must be observed).
3) Gently push the 4 field wires into the backbox by hand and screw the unit to the backbox.