Wheelock’s Series ET70/90 Low Profile Speakers and Speaker Strobes are UL Listed under Standard 1971 for Signaling Devices for the 
Hearing Impaired and UL Standard 1480 for Speaker Appliances.  They are designed for multiple power requirements with high dBA output 
at each power tap.  All models offer a choice of field selectable taps, 1/8W to 8W for either 25.0VRMS or 70.0VRMS audio systems.  The 
Low Profile design incorporates a high efficiency speaker for maximum output at minimum power across a frequency range of 400Hz to 
4000Hz, and features a sealed back construction for extra protection and improved audibility.  The Series ET appliances also incorporate a 
Speaker Mounting Plate attached to the speaker for ease of installation. The Low Profile Speaker Strobes can provide a non-synchronized 
strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in 
conjunction with a Sync Module (SM), Dual Sync Module (DSM), or Power Booster (PS-12/24-8).  The Strobes use a Xenon flashtube with 
solid state circuitry enclosed in a rugged Lexan

 lens to provide maximum visibility and reliability for effective visible signaling.  The 

241575W candela wall mounted strobes are listed at 15 candela under UL Standard 1971 and meet 75 candela intensity on axis with low 
current draw.  The ET70 Speaker Strobes for wall mounting 

only

 are available with a choice of five UL Listed strobe options:  2415W, 

241575W, 2430W, 2475W and 24110W.  The ET90 Speaker Strobes for ceiling mounting 

only

 are available with a choice of four UL Listed 

strobe options:  2415C, 2430C, 2475C, and 24100C.  All models are Listed for 

indoor use only

 with the backboxes specified in these 

instructions (see Mounting Options). 

NOTE:

  All 

CAUTIONS

 and 

WARNINGS

 are identified by the symbol 

.  All warnings are printed in bold capital letters. 

WARNING:  READ THESE INSTRUCTIONS CAREFULLY.  FAILURE TO COMPLY WITH ANY OF THE FOLLOWING 

INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

 

SPECIFICATIONS: 

Table 1:  UL Listed Models and Ratings 

 Speaker 

Strobe 

 

 

 

dBA at 10 Feet 

Voltage 

 

Mounting 

Models Voltage 

(Rated 

Watts) 

(VDC/VRMS) 

Candela 

Options 

 

(VRMS) 

1/8 1/4 1/2  1  2  4  8  Min Nom Max 

 

 

ET70 

25/70 

75 78 81 84 87 90 93 ---- ---- ---- 

---- 

A,C 

ET70-2415W 

25/70 

75 78 81 84 87 90 93  16  24  33 

15 

B,D 

ET70-241575W 

25/70 

75 78 81 84 87 90 93  16  24  33

 

 15* 

B,D 

ET70-2430W 

25/70 

75 78 81 84 87 90 93  16  24  33

 

30 B,D 

ET70-2475W 

25/70 

75 78 81 84 87 90 93  16  24  33

 

75 B,D 

ET70-24110W 

25/70 

75 78 81 84 87 90 93  16  24  33

 

110 B,D 

ET90 

25/70 

75 78 81 84 87 90 93 ---- ---- ---- 

---- 

ET90-2415C 

25/70 

75 78 81 84 87 90 93  16  24  33

 

15 B 

ET90-2430C 

25/70 

75 78 81 84 87 90 93  16  24  33

 

30 B 

ET90-2475C 

25/70 

75 78 81 84 87 90 93  16  24  33

 

75 B 

ET90-24100C 

25/70 

75 78 81 84 87 90 93  16  24  33

 

100 B 

*241575W models are UL Listed at 15cd and meet 75cd on axis. 

NOTES: 

1.  Strobes will produce 1 flash per second over the “regulated voltage” range. 
2.  All models are UL Listed for indoor use with a temperature range of +32oF  to +120oF  (0oC to +49oC) and maximum humidity of 85% RH. 
3.  dBA is rated per UL Standard 1480 for Speaker Appliances. 

WARNING:  THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING 

FILTERED (DC) OR UNFILTERED FULL-WAVE RECTIFIED (FWR).  DO NOT APPLY 80% AND 110% OF THESE VOLTAGE 
VALUES FOR SYSTEM OPERATION. 

WARNING:  CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND 

SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO 
THE STROBES. 
NOTE:  THE MAXIMUM WIRE IMPEDENCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.  THE MAXIMUM NUMBER 
OF STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47.

 

Copyright 2000 Wheelock, Inc.  All rights reserved.

 

Содержание Cooper ET70

Страница 1: ...y with the backboxes specified in these instructions see Mounting Options NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters WARNING READ THES...

Страница 2: ...230 0 230 0 230 0 230 16 0VRMS 0 155 0 155 0 155 0 155 0 155 24 0VRMS 0 235 0 235 0 235 0 235 0 235 33 0VRMS 0 325 0 325 0 325 0 325 0 325 Table 2A Ceiling Mount Strobe Current Ratings AMPS Rated Aver...

Страница 3: ...e power supplies inrush capacity the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in...

Страница 4: ...8 10 4 0 14 10 0 31 14 3 39 80 1 8 8 9 3 6 13 9 0 27 13 2 36 85 1 8 7 9 3 6 13 9 0 27 13 2 37 90 1 8 3 9 3 6 9 9 0 12 13 2 16 1575W models are UL Listed for 15cd and meet 75cd on axis Table 3B Horizo...

Страница 5: ...t by 3 dBA Field selectable input terminals are provided on each unit The following wattage selections are available 1 8W 1 4W 1 2W 1W 2W 4W and 8W Frequency range of speakers is 400 4000Hz 2 A 10 F b...

Страница 6: ...sitive of terminal block and select the power tap terminal for 1 8W 1 4W 1 2W 1W 2W 4W or 8W 25V or 70V as required see Figures 1 2 3 4 and Table 4 Each letter corresponds to a plug position of the he...

Страница 7: ...CREWS NON STROBE ROUND GRILLE SQUARE OR SPEAKER MOUNTING PLATE CONE PROTECTOR MAXIMUM NUMBER OF CONDUCTORS AWG 18 AWG 16 AWG 14 AWG 12 4 4 4 4 4 SQ X 2 1 8 B FLUSH MOUNTING 4 SQ X 1 1 2 BACKBOX 2 8 32...

Страница 8: ...ll models can be flush mounted to a 4 square by 1 1 2 deep backbox with a 4 square 1 1 2 extension ring Figure A or B ET70 models can also be surface mounted to a SBB Figure C or D 9 Use care and prop...

Страница 9: ...restrictions on wiring and or locating Notification Appliance Circuits NAC and notification appliances Some system communication circuits and or audio circuits for example may require special precauti...

Страница 10: ...SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATIO...

Отзывы: