background image

Table 1:  UL Max Current*

E70/E90 

Speaker 

Strobes

E70 Strobe Current - Wall Mount

E90 Strobe Current - Ceiling Mount

241575W

24MCW

24MCWH

24MCC

24MCCH

1575cd

15cd

30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd

16-33 VDC

0.090

0.060 0.092 0.165 0.220 0.300 .0420 0.065 0.105 0.189 0.249 0.300 0.420

Table 2:  E70/E90 UL Reverberant dBA @ 10 Feet**

watts

1/8

1/4

1/2

1

2

E Speaker

77

81

83

86

89

E Speaker Strobe

76

80

82

85

88

**dBA ratings are based on testing under UL Standard 1480.

* UL max current rating is the maximum RMS current 
within  the  listed  voltage  range  (16-33v  for  24v 
units).  For strobes the UL max current is usually at 
the minimum listed voltage (16v for 24v units).  For 
audibles the max current is usually at the maximum 
listed voltage (33v  for 24v units).  For unfiltered FWR 
ratings, see installation instructions.

NOTE: All CAUTIONS and WARNINGS are identified by the symbol 

. All warnings are printed in bold capital letters.

 

  WARNING:  PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR 

APPLYING THIS PRODUCT.  VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS.  
FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR 
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU 
AND/OR OTHERS. 

General Notes:

 

Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”.  Note that NFPA-72 specifies a flash rate of 1 
to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.

• 

All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971.

• 

Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and 
maximum humidity of 93% (± 2%).   

• 

Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). 

• 

“Regulated Voltage Range” is the newest terminology used by UL to identify the voltage range.  Prior to this change UL used the 
terminology “Listed Voltage Range”.