Operator’s Manual

Distributed in the U.S.A. and Canada by

ARTERRA DISTRIBUTION

(877) 294-8997

Warranty: [email protected]

Fax (574) 294-8698

www.wfcoelectronics.com

Power PROs Technical Support 

(877) 294-8997

WF-8930/50 Series Distribution Centers

WF-8930/50NP  |  WF-8930/50NP-30  |  

(The Distribution Center model number is located on the front panel label near the AC 
breakers)

Содержание WF-8930/50 Series

Страница 1: ...8997 Warranty warranty wfcoelectronics com Fax 574 294 8698 www wfcoelectronics com Power PROs Technical Support 877 294 8997 WF 8930 50 Series Distribution Centers WF 8930 50NP WF 8930 50NP 30 The Distribution Center model number is located on the front panel label near the AC breakers ...

Страница 2: ...in Circuit Breaker List 4 UL Listed Branch Circuit Breaker List 5 TROUBLESHOOTING INSTRUCTIONS Check Converter or Battery Input Voltage 6 Blown Fuse Indicators 6 GENERAL COMPLIANCE INFORMATION Agency Listings 7 INSTALLATION INSTRUCTIONS Mounting the Enclosure 7 Wiring the AC Breakers 8 Wiring the DC Fuse Board 9 WARRANTY INFORMATION 10 TABLE OF C ONTENTS 2 ...

Страница 3: ...cation and replacement instructions Blown Fuse Indicators on DC Fuse Board The DC Fuse Board has individual blown fuse indicators as standard equipment The WF 8930 50 Series Distribution Centers have 15 DC circuits Each of the circuits contain a Red LED to indicate a blown fuse If one of the circuits draws more current than the rating of the fuse the fuse will blow When this occurs the Red LED for...

Страница 4: ...eries Distribution Center accepts standard residential breakers The WF 8930 50NP has spaces for two 50 Amp or one 30 Amp Main breakers and up to 12 Branch breakers when using duplex breakers The WF 8930 50NP 30 has spaces for a 30 Amp Main and up to 6 Branch breakers when using duplex breakers A list of factory tested and approved breakers follows The breakers may be purchased at most big box depa...

Страница 5: ... C Type BRD BD and A Thomas Betts Type TB or TBBD ITE Siemens Type QP or QT Square D Type HOM or HOMT Murray Type MP T or MH T General Electric Type THQL When replacing any of the installed circuit breakers the replacement should be of the same manufacturer type designation and equal interrupting rating not to exceed 30 A The Short Circuit Current rating for the breaker should be 10 000 Amps Break...

Страница 6: ... lug and place the Negative black meter probe on the NEG lug If the voltage from the converter charger reads approximately 13 6 VDC 0 2 at the lugs the fuse board is getting DC power If no converter charger battery input voltage is read at these lugs check for an open inline fuse or disconnect switch in circuit coming to the fuse board One may have been installed by the RV manufacturer Also check ...

Страница 7: ...d for return label and disconnect each wire as it is removed from the fuse board lug Follow the packaging instructions in your warranty claim packet GENERAL COMPLIANCE INFORMATION Agency Listings UL The WF 8930 50 Series Distribution Centers are UL Listed and cUL Listed Canadian TROUBLESHOOTING INSTRUCTIONS 7 INSTALLATION INSTRUCTIONS Installing the WF 8930 50 Series Distribution Center Mounting t...

Страница 8: ... when using duplex breakers Refer to the tables on pages 4 and 5 for a selection of approved breakers The Main breakers should be installed in the center position See the wiring diagrams below A hold down clip is provided to keep the breaker securely in place The Shore cord should be routed through one of the large knockouts in the back of the wiring compartment as indicated above and secured with...

Страница 9: ...r current loads and can have a maximum 30 Amp ATO or ATC fuse installed The remaining 13 circuits are general purpose and can have up to a 20 Amp ATO or ATC fuse installed Make sure the fuses are seated properly All models have lug screw connections Strip approximately 1 4 of insulation from the DC load wires and insert the wire into the appropriate lug Tighten the lug screw to the torque spec fou...

Страница 10: ...ted to Recreational Vehicle application and is only valid within the continental United States Alaska Hawaii and the Provinces of Canada WFCO warrants to the owner that its products are free from defects in material and workmanship under normal use and service based on its intended use and function This warranty is limited to the repair or replacement at WFCO s discretion of any defective parts or...

Страница 11: ...y Department at 574 294 8698 After receipt of the forms an RGA number will be issued This number shall appear on all correspondence with warranty service Upon validation of the warranty WFCO shall replace the product with a like product The RGA number shall be placed on the outside of the carton used to return the product for ease of identification Do not mark directly on the product The product m...