Westpow L1600 Скачать руководство пользователя страница 16

User  Manual

User  Manual

User  Manual

User  Manual

displays on the keyboard. Press        or         key to modify this parameter. 

When the modification is finish, keep press          key 5 seconds, the sys-

tem return  ready state           , and the modified parameter value is saved 

automaticly. The rate current of the soft starter is the modified value.

(Note: this parameter is only admitted to change smaller than the default.

displays on the keyboard. Press        or         key to modify this parameter. 

When the modification is finish, keep press          key 5 seconds, the sys-

tem return  ready state           , and the modified parameter value is saved 

automaticly. The rate current of the soft starter is the modified value.

(Note: this parameter is only admitted to change smaller than the default.

 For Example: modify the rate current from 60A to30A

 For Example: modify the rate current from 60A to30A

Figure8-8

Press

Press

Press

Press

Press

Press

8.3.7 

Displayed Current calibration

8.3.7 Displayed Current calibration

The displayed current of each Soft starter is calibrated before leave 

factory. If user finds the current value showing on the keyboard is not 

equal to the actual current value, this parameter must be calibrated. The 

way of calibration is that: the parameter of  Starting mode is set Jogging     

           , the motor must be connected to its load, the parameter of Jogging 

Voltage  is set below 40%, keep press        key (enter the Jogging state), 

press         and         or        key at the same time to modify this value until it 

is equal to the actual current. Then release the        key and        key, the 

modified parameter is saved automatic.

The displayed current of each Soft starter is calibrated before leave 

factory. If user finds the current value showing on the keyboard is not 

equal to the actual current value, this parameter must be calibrated. The 

way of calibration is that: the parameter of  Starting mode is set Jogging     

           , the motor must be connected to its load, the parameter of Jogging 

Voltage  is set below 40%, keep press        key (enter the Jogging state), 

press         and         or        key at the same time to modify this value until it 

is equal to the actual current. Then release the        key and        key, the 

modified parameter is saved automatic.

  Explain:

  Explain:

When any of one parameter is selected, press whether        key 

m(change page) or        key( return             state), the modified 

parameters will be saved automatic.

When modify any of the parameter, press         key to return the        

state.

When any of one parameter is selected, press whether        key 

m(change page) or        key( return             state), the modified 

parameters will be saved automatic.

When modify any of the parameter, press         key to return the        

state.

9.   

Fault explanation and solution

9.   Fault explanation and solution

User parameter is not right. When power is on, the self-test is carried 

out. It is shows on the keyboard if the parameter is not right. In such 

circumstances, the factory default value will restore automatically 

Solution: Because the factory default value is restored, so user 

should set the parameter again.

User parameter is not right. When power is on, the self-test is carried 

out. It is shows on the keyboard if the parameter is not right. In such 

circumstances, the factory default value will restore automatically 

Solution: Because the factory default value is restored, so user 

should set the parameter again.

 Fault

 Fault

Explanation and Solutions

Explanation and Solutions

Phase lack. The system detects this fault on any time. If this fault is 

detected, the protection will act within 120 ms, and the fault code 

display on the keyboard. 

Solution: Check the power supply.

Phase lack. The system detects this fault on any time. If this fault is 

detected, the protection will act within 120 ms, and the fault code 

display on the keyboard. 

Solution: Check the power supply.

otor current is higher than the current limit. In start sequence, if the 

high current which is six times as the rate current is detected( such as 

stall), the trigger sign of the thyristors is locked within several

s. 

The fault code display on the keyboard and system enter fault protect 

state.

Solution: Check load or mechanical drive part.

otor current is higher than the current limit. In start sequence, if the 

high current which is six times as the rate current is detected( such as 

stall), the trigger sign of the thyristors is locked within several

s. 

The fault code display on the keyboard and system enter fault protect 

state.

Solution: Check load or mechanical drive part.

Over Temperature. The sink temperature of the thyristor is detected 

consequently on any time. If the temperature is over what is set, 

protect will act within 3 S. The fault code displays on the keyboard.

Solution: Check whether the load is too heavy or the frequent of 

starting is too much.

Over Temperature. The sink temperature of the thyristor is detected 

consequently on any time. If the temperature is over what is set, 

protect will act within 3 S. The fault code displays on the keyboard.

Solution: Check whether the load is too heavy or the frequent of 

starting is too much.

Starting time is over limit. In voltage ramp mode , the actual starting 

time is longer 3 seconds  then Starting Time use set , the actual cur-

rent is not lower than the 125%  of the rate current in percent. In Cur-

rent  Limit  mode , the actual starting time is longer  then Starting 

Time use set , the actual current is not lower than the 125%  of the 

rate current in percent.  System enter fault protect state. The fault 

code displays on the keyboard.

Solution: Check whether the load is too heavy or the starting time is 

too short.

Starting time is over limit. In voltage ramp mode , the actual starting 

time is longer 3 seconds  then Starting Time use set , the actual cur-

rent is not lower than the 125%  of the rate current in percent. In Cur-

rent  Limit  mode , the actual starting time is longer  then Starting 

Time use set , the actual current is not lower than the 125%  of the 

rate current in percent.  System enter fault protect state. The fault 

code displays on the keyboard.

Solution: Check whether the load is too heavy or the starting time is 

too short.

1. The inquiry method of last fault code shows at the chapter 

8.2.2 the last 

fault

2. In fault state, user can reset the fault as following:
         Press        key and maintain 3 seconds. 
         Connect controlled terminals RET and COM, and maintain 3 seconds.

Shut down the power and power on again.

Note:

Note:

22

OPERATION

MENU

23

OPERATION

MENU

Содержание L1600

Страница 1: ...ectronics Co Ltd ADD 2 Xibu Road New Industry Park GaoXin Borough Xi an 710119 P R China TEL 86 29 88889286 88889256 88889356 88889257 801 Technique service hot line 86 29 88889352 88889356 FAX 86 29 88889293 Email westpow 163 com http www westpow com or http www westpow cn Xi an Westpow Power Electronics Co Ltd ADD 2 Xibu Road New Industry Park GaoXin Borough Xi an 710119 P R China TEL 86 29 8888...

Страница 2: ...01 Technique service hot line 86 29 88889352 88889356 FAX 86 29 88889293 Email westpow 163 com http www westpow com or http www westpow cn Xi an Westpow Power Electronics Co Ltd ADD 2 Xibu Road New Industry Park GaoXin Borough Xi an 710119 P R China TEL 86 29 88889286 88889256 88889356 88889257 801 Technique service hot line 86 29 88889352 88889356 FAX 86 29 88889293 Email westpow 163 com http www...

Страница 3: ...User Manual User Manual ...

Страница 4: ...s maintained 7 Please do not maintain this product if you are not the professionals Because thereare high voltage 1 Only professional technician can install or guide the installation of thisproduct 2 Ensure the power and specification of the motor matching with this product 3 The capacitor is prohibited strictly to be connected with the output terminal U V W of thisproduct 4 The cables connecting ...

Страница 5: ...ion lifetime of the motor and correspond equipments You can select several sorts of starting mode set the current and voltage in a wide range It can be used in a lot of load conditions so the technic can be improved 1 1 Function 1 OPERATION MENU 1 2 Feature User Manual User Manual User Manual User Manual 17 17 Setting Starting mode Voltage Ramp Mode Current Limitv Jogging Control Mode Setting Rate...

Страница 6: ...vides the protective features such as Overload Line fault Over current Starting Time ultra limit When Soft Starter nominal power is higher than the actual load power user can modify the actual current parameter according to the load current So the power of the soft starter is matched to the power of the actual power of load 2 Type and Inspection 2 Type and Inspection Each STR series soft starter i...

Страница 7: ...tart frequency Start frequency less than 15 per hour according the load less than 15 per hour according the load Cooling Cooling Natural air cooled Natural air cooled Using condition Using condition It is necessarythat bypass contactorand the protect device should be used It is necessarythat bypass contactorand the protect device should be used IP Code IP Code IP20 IP20 EnvironmentIt EnvironmentIt...

Страница 8: ...arter Cabinet installation Cabinet installation User Manual User Manual User Manual User Manual Figure 3 2 Hot Air Out Hot Air Out Hot Air Out Hot Air Out STR STR Figure 3 3 Figure 3 4 Soft starter Ventilation Cool Air in 4 Operating Principle 4 Operating Principle There are three pairs of anti parallel thyristors connected to the stator of motor Using the electric switch feature of the thyristors...

Страница 9: ...ntrol the motor anymore So the bypass contactor must be used See figure 5 2 After the bypass contactor works only the Missing Supply phase fault can be detected So the thermal protection relay or motor protection device must be used See figure 5 2 User Manual User Manual User Manual User Manual 5 Wiring and Terminal 5 Wiring and Terminal RUN JOG STOP COM RET Start Start Jog Jog Free stop Free stop...

Страница 10: ...y of themaccording to theload instance andrequirement 6 1 VoltageRamp 6 1 VoltageRamp The waveform of the voltage shows in Figure 6 1 U0 in figure is initial output voltage When starting the output voltage is up to U0 immediately and then ramps up gradually according to the parameter Start Time t set in advance Then the motor accelerates continuously When the output voltage reaches the rate value ...

Страница 11: ...ht it shows which start mode is Lamp Light it is means the start mode is Current Limit Lamp Light it is means the start mode is Voltage Ramp Ready When the soft Starter is power on self inspection is performed The self inspection includes testthe parameters thatthe user changed fault protection ofparameters setting checkif the phaseof voltage is not right protectionof missing supplyphase and check...

Страница 12: ...ess this key the motor start accordingthe start modeuser set When the system is on Ready state press this key the motor start accordingthe start modeuser set Key Function Key Function There are fivekey on thekeyboard start stop Program Increase Decrease There are fivekey on thekeyboard start stop Program Increase Decrease When the systemis on Startingor Running state press this key the motor stop ...

Страница 13: ...ot release code c and rate current display on thekeyboard the unitis ampere Releasethis key system return to state On state press key and not release code c and rate current display on thekeyboard the unitis ampere Releasethis key system return to state 8 3 Setting 8 3 Setting On Ready state press key and release it5 minutes later orpress and at thesame time systementer Setting state On Ready stat...

Страница 14: ...amp Voltage mode is selected The default value is30 second This parameter isset according tothe load type For the heavy load and big inertia load type this value can be increased For light load type the starting time may be shorter then the time user set It is normal if the starting process is all right Control Mode It is the way user selected to state and stop the motor There are two ways keyboar...

Страница 15: ...arter this fix value is the parameter user set This mode is convenience in trial running and position regulating Control mode It is the way user selected to state and stop the motor There are two ways keyboard control and terminal control The selection of Control Mode describe in chapter 8 3 5 In figure 8 6 In figure 8 6 Quit Press key in any state introduced above system return state Quit Press k...

Страница 16: ...t right In such circumstances the factory default value will restore automatically Solution Because the factory default value is restored so user should set the parameter again Fault Fault Explanation and Solutions Explanation and Solutions Phase lack The system detects this fault on any time If this fault is detected the protection will act within 120 ms and the fault code display on the keyboard...

Страница 17: ...hich power is 7 5kw to 160kw Note This circuit diagram is designed for the motor which power is 7 5kw to 160kw FU2 R KA1 Bypass Bypass K22 K24 K12 K14 K22 K24 STRL AR STRL K12 K14 PA A LH U V W FR FR FR Fault Fault Main circuit Main circuit Figure10 1 24 OPERATION MENU 25 OPERATION MENU STR L STR L L1 L2 L3 N QF1 FU1 R PV V R S T U V W COM M RUN STOP KM FU3 AR AC220V SB1 KA1 SB2 KA1 KM HG HR HY KM...

Страница 18: ...the controlmode to Press key check whether the 3 phase current is balance using current measure meter at this time because the voltage is too low the motor maynot rotate Itis normal If above testresult is normal user can operatethe soft starterto start and stop the motor as normal Press key to start motor after the startsequence complete thebypass contactor cameinto work automatically Shows onthe ...

Страница 19: ...g for ensuring what you ordered is proper Bypass contactor and the electrical protection devices must be equipped when using For the users who have special requirements please say the requirement to the supplier when ordering We will provide perfect service Ordering Ordering 13 Installation and appearance dimension 13 Installation and appearance dimension Table13 1 Table13 1 Type Type STR008 3 STR...

Страница 20: ...ork after starting completed Bypass state Bypass contactor put into work after starting completed Function Function Fault Fault Set starting mode Set starting mode Set initial voltage under voltage ramp mode Set initial voltage under voltage ramp mode Set ramp time under voltage ramp start mode Set ramp time under voltage ramp start mode Set current limit value under current limit mode Set current...

Страница 21: ......

Отзывы: