Table 24:
Status and Substatus for BKCAL_OUT parameter in AO blocks
Parameter
Status: Quality-Substatus-Limit
Possible causes and fixes
BKCAL_OUT
Good-FaultStateActive-NotLimited
•
Device is in Fault State and STATUS_OPTS = Propagate Fail Bkwd.
See Resource block.
•
Block mode goes to LO (Local Override)
Bad-OutOfService-NotLimited
•
Block mode is in OOS, check MODE_BLK parameter.
•
Check Resource block mode in OOS.
Good-NotInvited-NotLimited
•
Block mode is CAS or AUTO but no CHANNEL has been assigned.
•
Check associated Transducer block mode in OOS or MAN.
Good-NonSpecific-SensorFail
•
check the positioner’s calibration
Good-NonSpecific-LowLimited
•
Position reading is below -2%, check calibration, mechanical
assembly
Good-NonSpecific -HighLimited
•
Position reading is above +102%, check calibration, mechanical
assembly.
Good-NonSpecific-NotLimited
•
Normal condition with block in AUTO or CAS.