Piping work and refrigerant charge
Completion
of Ref.
Piping
Repairing
of Leakage
Part
Check of
Pressure
Decrease
Applying
Nitrogen
Gas
Pass
Procedure
Air tight procedure
Although refrigerant has been charged into this unit, additional refrigerant charge is
required according to the piping length.
•
The additional refrigerant precharge quantity should be determined and charged into the system
according to the following procedure.
•
Record the additional refrigerant quantity in order to facilitate maintenance and servicing activities.
Refrigerant charge before shipment (W0 (kg))
W0 is the outdoor unit refrigerant charge before shipment
;
Xg is additional refrigerant outdoor unit needed to charge according to piping length during
installation.
Model
Refrigerant
precharged before
shipment
(W0(
oz/
g))
Total refrigerant pipe length
0
~
2
4.6
ft
(0
~
7.5 m)
Long
er
than
2
4.6
ft (7.
5
m
)
9K
33.5/0.95
0g
Additional refrigerant charge=
(L-24.6)×0.161 oz/ft
18K
56.44/1.6
0g
36K
111.2/3.15
0g
12K
45.9/1.3
0g
24K
91.7/2.6
0g
Additional refrigerant charge=
(L-24.6)×0.376 oz/ft
Air tight test
Additional refrigerant charge
Do use nitrogen when performing air-tight test.
Connect the gauge manifold using charging hoses with a nitrogen cylinder to the check joints of
the liquid line and the gas line stop valves. Perform the air-tight test. Don't open the gas line stop
valves. Apply nitrogen gas pressure of 4.3MPa. Check for any gas leakage at the flare nut
connections, or brazed parts by gas leak detector or foaming agent. It is OK if gas pressure does
not decrease. After the air tight test, release nitrogen gas.
- 21 -
Содержание WHU09DHA21S
Страница 57: ...2 3 4 5 6 7 8 9 10 11 1 Indoor unit WHU09DHA21S 56 Parts list ...
Страница 58: ...12 13 14 15 16 17 18 19 14 15 57 Fan ...
Страница 59: ...20 21 22 58 Electrical parts ...
Страница 61: ...2 3 4 5 6 7 8 9 10 11 1 60 Indoor unit WHU12DHA21S ...
Страница 62: ...12 13 15 16 17 18 19 14 14 15 61 Fan ...
Страница 63: ...20 21 22 62 Electrical parts ...
Страница 65: ... 64 Indoor unit WHU18DHA21S 2 3 4 5 6 7 8 9 10 11 1 ...
Страница 66: ... 65 Fan 12 13 16 17 18 19 20 21 22 14 14 14 15 15 15 ...
Страница 67: ... 66 Electrical parts 23 24 25 ...
Страница 69: ...Indoor unit WHU24DHA21S 68 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 ...
Страница 70: ... 69 Fan 16 17 18 19 20 21 22 23 18 23 ...
Страница 71: ... 70 Electrical parts 24 25 26 27 25 ...
Страница 73: ...Indoor unit WHU36DHA21S 72 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 1 ...
Страница 74: ... 73 Fan 20 21 22 23 24 25 26 27 22 24 25 27 ...
Страница 75: ... 74 Electrical parts 28 29 30 29 31 ...
Страница 77: ...Outdoor unit WHU09SZA21S 76 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 ...
Страница 78: ... Refrigerant cycle 77 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 ...
Страница 79: ... Electrical parts 78 32 33 34 35 36 37 38 39 40 31 41 ...
Страница 81: ...Outdoor unit WHU12SZA21S 80 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1 ...
Страница 82: ... Refrigerant cycle 81 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 ...
Страница 83: ... Electrical parts 82 32 33 34 35 36 37 38 39 40 31 41 ...
Страница 85: ...Outdoor unit WHU18SZA21S 84 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 ...
Страница 86: ... Refrigerant cycle 85 17 18 19 20 21 22 23 24 25 26 27 28 29 30 35 31 34 48 32 33 ...
Страница 87: ... Electrical parts 86 36 37 38 39 40 41 42 43 45 46 47 44 ...
Страница 89: ...Outdoor unit WHU24SZA21S 88 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 1 ...
Страница 90: ... Refrigerant cycle 22 23 24 25 26 27 28 29 30 32 33 34 35 36 31 89 37 ...
Страница 91: ... Electrical parts 90 38 39 40 42 43 44 45 46 47 48 49 41 ...
Страница 93: ...Outdoor unit WHU36SZA21S 92 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 ...
Страница 94: ... Refrigerant cycle 93 17 18 19 20 21 22 23 24 25 26 27 28 29 30 32 33 31 ...
Страница 95: ... Electrical parts 94 34 35 36 37 38 39 40 42 43 44 45 46 47 48 49 41 ...