Type
Inverter heat pump
Model name
WHS09SZA21S
WHS12SZA21S
WHS18SZA21S
Power supply
208/230 V ~ 60 Hz
Available voltage range
198—253 V
Fan
Airflow rate
CFM (m
3
/h)
942 (1,600)
942 (1,600)
1,177 (2,000)
Type × Q'ty
Propeller fan × 1
Motor output
W
28
41
Sound pressure level *
1
dB (A)
54
56
Heat exchanger type
Dimensions
(H × W × D)
in (mm)
27-3/8 × 18-3/16 × 11/16
(695 × 462 × 18.2)
27-3/8 × 18-3/16 × 11/16
(695 × 462 × 18.2)
26-15/16 × 18-3/16 × 11/16
(684 × 462 × 18.2)
25-13/16 × 18-3/16 × 11/16
(655 × 462 × 18.2)
33-1/8 × 21-1/2 × 11/16
(842 × 546 × 18.2)
32 × 21-1/2 × 11/16
(813 × 546 × 18.2)
Fin pitch
FPI
18
Rows × Stages
2 × 22
2 × 26
Pipe type
Copper
Fin type
Type (Material)
Aluminum
Surface treatment
Blue fin
Compressor
Type
Rotary
Refrigerant
Type
R410A
Charge
lb oz
1 lb 13 oz
2 lb 3 oz
3 lb 1 oz
g
830
1,000
1,400
Refrigerant oil
Type
VG74 (POE)
Enclosure
Material
Steel sheet
Color
White
Dimensions
(H × W × D)
Net
in (mm)
19 × 28-1/8 × 9-7/16 (482 × 715 × 240)
23-1/16 × 31-7/8 × 11
(585 × 810 × 280)
Gross
20-7/8 × 33-11/16 × 13-3/8 (530 × 830 × 340)
25-3/16 × 37 × 15-3/16
(640 × 940 × 385)
Weight
Net
lb (kg)
55 (25)
60 (27)
86 (39)
Gross
60 (27)
66 (30)
93 (42)
Connection pipe
Size
Liquid
in (mm)
Ø 1/4 (Ø 6.35)
Gas
Ø 3/8 (Ø 9.52)
Ø 1/2 (Ø 12.7)
Method
Flare
Pre-charge length
ft (m)
24 (7.5)
Max. length
65 (20)
Max. height difference
Indoor unit higher than outdoor unit: 32 (10)
Outdoor unit higher than indoor unit: 16 (5)
Operation range
Cooling
°F (°C)
32 to 115 (0 to 46)
Heating
-4 to 75 (-20 to 24)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 80 °FDB (26.67 °CDB) / 67 °FWB (19.44 °CWB), and outdoor temperature of 95 °FDB (35 °CDB) / 75 °FWB (23.9 °CWB).
– Heating: Indoor temperature of 70 °FDB (21.11 °CDB) / 59 °FWB (15 °CWB), and outdoor temperature of 47 °FDB (8.33 °CDB) / 43 °FWB (6.11 °CWB).
– Pipe length: 24 ft 6 in (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 6 -