H. INSTALLER MODE
Installer Mode will activate when button B
is pressed and held for five seconds while the water heater is powered Off.
Figure 48
– Installer Mode Screens
Display
Default
Detail
Description
0: RC
oFF
OFF
Recirculation Pump Operation
oFF: Recirculation Pump is not used. (Recirculation Mode is OFF.)
InRC: Internal Recirculation Mode
– Internal recirculation pump is used.
EtRC: External Recirculation Mode
– External recirculation pump is used.
InRC
EtRC
1: EH
E0:00
Error history up to 10
Check Ten Most Recent Error Codes (E0 - E9)
2: cE
OFF
Clear Error History
Select “ON” to Clear Error History
Range: ON and OFF
3: In
OFF
System Reset
(Factory Setting)
Restores System to Default Factory Settings
(Burner operation time, Ignition cycles, and Supply power time will not be
reset)
Range: ON or OFF
4: FH
00
Maximum Fan speed
Adjusts Maximum Fan Speed. Range: -30 to +30
5: FL
00
Minimum Fan speed
Adjusts Minimum Fan Speed. Range: -30 to +30
6: dr
NO
Reset Burner Operation Time
Select “YES” to Reset Burner Operation Time
Range: YES or NO
7: dI
NO
Reset Ignition Cycle
Select “YES” to Reset Ignition Cycles
Range: YES or NO
8: Cn
0
Cascade Number
N/A
9: CP
1
Cascade Parameter
10: Eh
OFF
Common Vent
11:Cr
Auto
Auto
Automatic rotation
Cr:Ct
48
Cascade Rotation time
12: HA
0-2
High Elevation Mode
This water heater may be installed at elevations up to 10,000 feet and operate
on either Natural or LP. The appliance will de-rate by 4% for each 1000 feet
above sea level. Select the appropriate installation location as described below.
Selects Installation Location for Proper Water Heater Operation at Altitude:
0-2 for installation locations from sea level to 1999 feet
2-5 for locations from 2000 to 4999 feet
5-8 for locations from 5000 to 7999 feet,
8-10 for locations from 8000 to 10000 feet
Default: 0
– 2
NOTE:
Use a combustion analyzer to ensure CO and CO2 are within the
ranges shown in this manual. Adjust the offset screw in the clockwise (positive)
or counterclockwise (negative) directions (approximately 1/8 turn) if the
measured CO2 value on LOW FIRE is out of range.
13:AP
AP:cP
5
Pump Test Mode
This function sets the time to run pumps to purge air from the system. Range: 1
– 30 minutes
Pu:oF
or
Pu:on
OFF
Turn this function on to activate pump testing.
Only works in installation mode. Turns off when in normal mode.