2. Venting Through an Existing System

This heater may be vented through an existing unused vent system. 

The inner diameter of the existing vent system is utilized for the 

combustion air source. Two methods have been approved for 

such venting: Concentric Venting Through an Existing System and 

Venting as a Chase.

Vent / Air Inlet Size

Minimum Existing Vent / Chase Size

2”

4”

3”

5”

4”

7”

Table 10 - Minimum Existing Vent / Chase Sizing

Do not install the heater into a common existing vent with 

any other appliance. This will cause flue gas spillage or heater 

malfunction, resulting in substantial property damage, serious 

personal injury, or death.

Contractors must check state and local codes before installing 

through an existing vent opening. State and local codes always 

take precedence over manufacturer’s instructions. Failure to 

check state and local codes before installing through an existing 

opening could result in property damage and add significantly to 

installation costs.
If an existing venting system is converted for use with this heater, 

the installer must ensure that the existing venting system is clean 

and free from particulate contamination that could damage the 

heater. Failure to do so could result in  property damage and 

heater failure. Such failure IS NOT covered under warranty.

Concentric Venting Through an Existing System

NOTE: The following instructions refer only to venting through 

an existing vent system, and not to venting with Westinghouse’s 

optional concentric vent kits. Refer to Concentric Vent Kit installation 

manual (LP-166) for further information on venting with the optional 

concentric vent kits.

Concentric venting through an existing system must run vertically 

through the roof. See Table 10 for proper minimum vent sizing. Use 

only the approved venting materials specified in Table 5 for piping the 

system. All instructions listed in this Venting section apply. See Figures 

12-1 and 12-2 for venting demonstrations.

SEAL

SEALED

EXISTING

EXHAUST

CAP

(w/SCREEN)

SEAL

AIR INTAKE

SEAL

LP-325-LL

03/15/12

Exhaust

In

take

Concentric Venting through an Existing System

1

12" MIN.

LP-325-MM

03/15/12

EXHAUST

SEAL

w/SCREEN

EXISTING

AIR INTAKE

SEALED CAP

COMBUSTION AIR

COMBUSTION 

AIR

SEAL

Concentric Venting through an Existing System

2

In

take

Exhaust

Exhaust

In

take

07/22/13

LP-325-NN

INTAKE

EXHAUST

24"

SEAL

EXISTING

VENT

CAP

SEAL

Exhaust

In

take

Chase Venting through an Existing System

3

Figure 12 -  1, 2 - Concentric Venting Through an Existing System, 3, Chase Venting Through an Existing System

NOTE: 

These drawings are meant to demonstrate system venting only. The installer is responsible for all equipment and detailing required 

by local codes.

The upper and lower vent terminations as well as all joints in 

the venting system must be properly sealed to ensure that all 

combustion air is drawn properly and exhaust does not leak from 

the system. Failure to properly seal the venting system will result in 

property damage, serious personal injury, or death.

Chase Venting Through an Existing System

When venting as a chase, follow all instructions included in this 

Venting section, including those in the previous Concentric Venting 

Through an Existing System section. See Figure 12-3 for chase venting 

demonstration.

Содержание WGR050NG076

Страница 1: ...ce and will not be held liable for typographical errors in literature NOTE TO CONSUMER PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE www westinghousewaterheating com WHL 001 Rev 001 Rel 008 Date 8...

Страница 2: ...e Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your ga...

Страница 3: ...stalledbyqualifiedandlicensedpersonnel The installer should be guided by the instructions furnished with the water heater and by local codes and utility company requirements In the absence of local co...

Страница 4: ...repare the Water Heater 6 A Locating the Water Heater 7 B Leveling 7 C Clearances for Service Access 8 D Residential Garage and Closet Installations 8 E Exhaust Vent and Intake Pipe 8 1 Direct Vent of...

Страница 5: ...to heat potable water ONLY Using this water heater to heat non potable fluid WILL VOID product warranty and could result in property damage personal injury or death Do not use this water heater for an...

Страница 6: ...ature and adjusts fan speed to regulate the heater s energy output This allows the unit to deliver the required amount of heated energy and nothing more Burner Constructed of high grade stainless stee...

Страница 7: ...m air for combustion Indoor air will have a much lower relative humidity and hence potential corrosion will be minimized High heat sources generating heat 100o F 37o C or greater such as boiler flue p...

Страница 8: ...ould result in severe personal injury or death Do not attempt to vent this water heater by any means other than those described in this manual Doing so will void the warranty and may result in severe...

Страница 9: ...inch per 1 000 BTU hr 22cm2 kW of the total input of all appliances in the space but not less than 100 square inches 645cm2 If the confined space is within a building of tight construction air for co...

Страница 10: ...ith EPA secondary maximum contaminant levels 40 CFR Part 143 3 If the water contains contaminants higher than outlined by the EPA water treatment is recommended and additional more frequent maintenanc...

Страница 11: ...se as required by ANSI Part 4 Piping Failure to follow the instructions in this section WILL VOID the warranty and may result in property damage severe personal injury or death DO NOT pipe this water...

Страница 12: ...The expansion tank must be located as shown in Applications this manual or following recognized design methods See expansion tank manufacturer s instructions for details Use a backflow preventer spec...

Страница 13: ...nt temperature as low as possible Feel water before bathing or showering If thermostatic valves are required use devices specifically designed for such purpose Install these devices in accordancewithi...

Страница 14: ...r all equipment and detailing required by local codes In Massachusetts you must install a vacuum relief valve per 248 CMR 6 Mixing valve application is optional but recommended to help prevent scaldin...

Страница 15: ...ithout water will result in dry firing NOTES FOR AIR HANDLER APPLICATION 1 MASSACHUSETTS STATE PLUMBING CODE REQUIRES A DISTANCE NO GREATER THAN 50 FEET FROM THE WATER HEATER TO THE FAN COIL IN THE AI...

Страница 16: ...state provincial and national codes for best practices to prevent condensate freezing in the exhaust vent pipe system Improper seating of vent pipe gaskets can cause eventual gasket failure and exhau...

Страница 17: ...p terminations clear could result in property damage severe personal injury or death The exhaust and intake components installed with this water heater must be used for near water heater piping BEFORE...

Страница 18: ...t may be opened Direct Vent 1 foot 3 feet 91 cm Power Vent 4 ft below or to side of opening 1 ft above opening C Clearance to permanently closed window D Vertical clearance to ventilated soffit locate...

Страница 19: ...piping may be used on air inlet piping only 2 Remove all burrs and debris from joints and fittings 3 When using PVC or CPVC pipe all joints must be properly cleaned primed and cemented Use only cemen...

Страница 20: ...ree feet for concealed piping b At all changes of direction c On each side of a penetration through a partition wall or ceiling and d The labels shall be black lettering that i Indicates that the pipi...

Страница 21: ...ing support brackets on vent piping the first bracket must be within 1 foot of the water heater and the balance of 4 foot intervals on the vent pipe Venting must be readily accessible for visual inspe...

Страница 22: ...IDE VIEW LP 325 PP EXHAUST AIR INTAKE F E D C EXHAUST AIR INTAKE B Figure 10 Horizontal Snorkel Venting UNBALANCED VENTING WITH TEE INTAKE AND COUPLING EXHAUST All vent pipes must be glued properly su...

Страница 23: ...er to Concentric Vent Kit installation manual LP 166 for further information on venting with the optional concentric vent kits Concentric venting through an existing system must run vertically through...

Страница 24: ...sidered part of the space Confined space is space with volume less than 50 cubic feet per 1 000 Btu hour 4 8 cubic meters per kW of the total input rating of all fuel burning appliances installed in t...

Страница 25: ...cidic pH from 3 2 to 4 5 Install a neutralizing filter if required by local codes Power to the optional condensate pump is continuous When the water heater is powered off the condensate pump will rema...

Страница 26: ...WHL 001 Rev 001 Rel 008 Date 8 23 18 26 1 2 3 4 Figure 16 Removing and Installing the Condensate Neutralizer Water Heaters Manufactured Prior to 9 27 17 ONLY...

Страница 27: ...uctions are included with the outdoor sensor to correctly mount the sensor on the exterior surface of the building It is preferable to mount the sensor on the north side in an area that will not be af...

Страница 28: ...ing plate LP for liquefied petroleum propane gas or Nat for natural or city gas All gas connections must be approved by the local gas supplier or utility in addition to the governing authority prior t...

Страница 29: ...being installed If there are additional gas appliances on the main supply line size the supply line for the maximum total COMBINED BTU Hr draw of the appliances This will ensure the supply line is siz...

Страница 30: ...ts individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of the system at pressures greater than psi 3 5 kPa 2 The water heater must be isolated f...

Страница 31: ...t in increments of two degrees After choosing the setpoint wait five seconds The screen will return to normal operation and the setpoint will be stored 70 160 120 Outdoor Reset Curve Enabling Outdoor...

Страница 32: ...sume water heater operation 3 Putting the Water Heater in ECO Mode Press to put the water heater in ECO Mode Press to resume normal operation 4 Changing User Setpoint Press either or once to change th...

Страница 33: ...imum tank temperature for reset curve 70 160 140 P10 Warm Weather Shutdown Temperature o C o F Outdoor temperatures greater than this value return the tank target temperature to the User Setpoint 50 1...

Страница 34: ...een cleared Press at any History Mode screens to return to the upper level menu Part 10 Start Up Procedure FOR YOUR OWN SAFETY READ BEFORE OPERATING 1 This water heater does not have a pilot It is equ...

Страница 35: ...a maximum of 15 minutes 8 Test Mode can be disabled by pressing Combustion Settings on All Models Fan Speed Natural Gas NG Propane LP Low Ignition High Low Ignition High Carbon Monoxide CO PPM 1 10 2...

Страница 36: ...result in property damage serious personal injury or death Such damages ARE NOT covered by water heater warranty Part 12 Troubleshooting A Error Code An error code may occur during installation of th...

Страница 37: ...the sensor is 40o F 122o F 2 Check the Outdoor Temperature Sensor Ensure it is properly wired and connected and that there are no breaks cuts or other visible issues with the sensor wire 3 Use an ohm...

Страница 38: ...ault code occurs again reset the water heater and 3 When water heater attempts to fire check voltage at the gas valve connector If there is voltage but no gas pressure on the outlet side of the valve...

Страница 39: ...serve water heater operation If fault code occurs again 3 Check the Dual Temperature Sensor Ensure it is properly wired to the control and that there are no breaks cuts or other visible issues with th...

Страница 40: ...ons been installed at least one foot above exterior grade and one foot above normal snow accumulation level Is vent piping properly supported Has vent piping been checked for leaks Has the exhaust ven...

Страница 41: ...ter that has not been used for a long period of time generally two weeks or more When opening a hot water faucet in a system that has been out of use for a time keep all ignition sources electrical ap...

Страница 42: ...ctrode Clean Set gap at 1 4 Clean probe with plumbers cloth to remove oxides Combination Ignitor and Flame Probe Check ionization in uA i04 in the Inquiry Mode menu Record high fire and low fire Clean...

Страница 43: ...T P A D A 4 8 6 0 P 0 0 7 7 S P M A L C w E S O H E T A S N E D N O C 5 4 4 0 P 0 0 1 7 B R A B X E L A M T P N 2 1 G N I T T I F 6 2 0 0 P 0 0 7 7 2 1 T U N K C O L 7 7 7 0 P 0 0 7 7 2 1 X 2 1 R E T...

Страница 44: ...00P 004 27 CONDENSATE HOSE w CLAMPS 7700P 068 28 FITTING 1 2 NPT MALE X BARB 7100P 044 29 LOCKNUT 1 2 7700P 002 30 ADAPTER 1 2 X 1 2 7700P 077 31 FLUE TEMPERATURE SENSOR 7450P 026 32 PRESSURE SWITCH 7...

Страница 45: ...t s E If at the time of a request for service the Owner cannot provide a copy of the original sales receipt or the warranty registration the warranty period for the water heater shall then be deemed t...

Страница 46: ...warranty registration for a warranty service request If the water heater is in warranty contact the retailer from whom the water heater was purchased or the installer for assistance Be prepared to pro...

Страница 47: ...WHL 001 Rev 001 Rel 008 Date 8 23 18 47 Maintenance Notes...

Страница 48: ...allation Installation Address Product Name Serial Number s Comments Installer s Code Name Installers Phone Number Signed by Installer Signed by Customer Installation Notes IMPORTANT Customer Please on...

Отзывы: