Westinghouse Portable Power | 17

ADDING GASOLINE TO THE FUEL TANK

WARNING

Never refuel the generator while the 

engine is running.

Always turn the engine off and allow

the generator to cool before refueling.

Required Gasoline

 – Only use gasoline that meets the 

following requirements:

• 

Unleaded gasoline only

• 

Gasoline with maximum 10% ethanol added

•  Gasoline with an 87 octane rating or higher

Filling the Fuel Tank

 – Follow the steps below to fill the 

fuel tank:

1. 

Shut off the generator.

2.  Allow the generator to cool down so all surface areas 

of the muffler and engine are cool to the touch.

3. 

Move the generator to a flat surface.

4. 

Clean area around the fuel cap.

5. 

Remove the fuel cap by rotating counterclockwise.

6. 

Slowly add gasoline into the fuel tank. Be very careful 

not to overfill the tank. The gasoline level should NOT 

be higher than the filler neck (see Figure 7).

7. 

Install the fuel cap by rotating clockwise until 

you hear a click, indicating the cap is completely 

installed.

Figure 7 - Maximum Gasoline Fill Level

CAUTION

Avoid prolonged skin contact with 

gasoline. Avoid prolonged breathing of 

gasoline vapors.

BEFORE STARTING THE GENERATOR

BEFORE STARTING THE GENERATOR, 

REVIEW SAFETY SECTION STARTING ON 

PAGE 5.

Before attempting to start the generator,

 

verify the following:

• 

The engine is filled with engine oil. See 

Checking Engine 

Oil

 on page 22.

• 

The generator is situated in a proper location (

Location 

Selection

 on page 14).

• 

The generator is on a dry surface (

Weather and Dry 

Surface

 on page 14).

• 

All loads are disconnected from the generator (

No 

Connected Loads

 on page 14).

• 

The generator is properly grounded the Generator 

(page 14).

DANGER

Never use the generator in a location 

that is wet or damp. Never expose the 

generator to rain, snow, water spray or  

standing water while in use. Protect the 

generator from all hazardous weather 

conditions. Moisture or ice  can cause a 

short circuit or other malfunction in the 

electrical circuit.

Never operate the generator in an 

enclosed area. Engine exhaust contains 

carbon monoxide. Only operate the 

generator outside and away from 

windows, doors and vents.

NOTICE

The engine is equipped with a low oil shutdown switch. If the 

oil level becomes low, the engine may shut down and not start 

until the oil is filled to the proper level. Poor oil quality may 

interfere with the operation of the low oil shutdown switch.

The owner of the generator is responsible to ensure the proper 

oil level is maintained during the operation of the generator. 

Failure to maintain the proper oil level can result in engine 

damage.

NOTICE

DO NOT connect 240V loads to a 120V receptacles. DO NOT 

connect 3-phase loads to the generator. DO NOT connect 50Hz 

loads to the generator. Let engine stabilize and warm up for a 

few minutes before adding load.

OPERATION 

Содержание WGen5500

Страница 1: ...USER MANUAL WGen5500 Portable Generator 5500 Running Watts 6850 Peak Watts...

Страница 2: ...to be seriously hurt or killed Model Number Running Watts Peak Watts Fuel Tank Size L G Rated Speed RPM Ignition Type Spark plug Engine Disp cc Stroke X Bore Oil Capacity L Oil Type THD WGen5500 5500...

Страница 3: ..._ Model Number ______________________________________ Last Name ________________________________________ Serial Number _______________________________________ Street Address __________________________...

Страница 4: ...ns 16 How to Float the Neutral Ground 16 Engine Fluids and Fuel 16 Adding Gasoline to the Fuel Tank 17 Power Output and Demand 18 Starting the Generator 18 Manual Start 18 Stopping the Generator 19 No...

Страница 5: ...ot avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE Indicates a situation which can cause da...

Страница 6: ...Never remove the fuel cap with the engine running Never refuel the generator while the engine is running Always turn engine off and allow the generator to cool before refueling Only fill fuel tank wit...

Страница 7: ...Chine CSA Master Contract Number Num ro de contrat principa l de CSA MWE Investments LLC Columbus Ohio 43228 USA Con u columbus Ohio tats Unis MWE Investments LLC Columbus Ohio 43228 Etats Unis Part N...

Страница 8: ...8 Westinghouse Portable Power SAFETY SAFETY LABELS AND DECALS 8 9 7 10 8 9 6 6 7 5 10...

Страница 9: ...ld back top flaps to reveal the manual 3 Remove the Wheel Kit Accessories cardboard box 4 Carefully cut two sides of the carton to remove the generator WHAT COMES IN THE BOX Manual Quick Start Guide M...

Страница 10: ...wheel kit is not intended for on road use The wheel kit is designed for use on this generator only INSTALLING FEET TO FRAME 1 Place generator on a flat surface 2 Place a piece of cardboard or other s...

Страница 11: ...nd outlets Oil Fill Plug Dipstick Must be removed to add and check oil Oil Drain Plug Must be removed to drain engine oil Never Flat Wheels For easy portability Fuel Shut off Valve Controls the flow o...

Страница 12: ...the spark plug CARB Canister Required for models sold into and used in California Muffler and Spark Arrester Avoid contact until engine is cooled down Spark arrestor prevents sparks from exiting the m...

Страница 13: ...Control Switch Allows fuel to flow to engine and energizes the ignition system Data Center The VFT Meter is an LED display that will rotate through volts frequency and lifetime run hours You can press...

Страница 14: ...utput will be reduced approximately 3 5 for every 1000ft of increased altitude from sea level This is a natural occurrence and cannot be adjusted by engine Increased exhaust emissions can also result...

Страница 15: ...n the top line of the chart Then select the rated amperage of the generator on the left side of the chart Where the two meet is the size of the conductor required for the application When using the WC...

Страница 16: ...intained during the operation of the generator Failure to maintain the proper oil level can result in engine damage OPERATION CONNECTING THE GENERATOR TO A BUILDING ELECTRICAL SYSTEM It is recommended...

Страница 17: ...ne is filled with engine oil See Checking Engine Oil on page 22 The generator is situated in a proper location Location Selection on page 14 The generator is on a dry surface Weather and Dry Surface o...

Страница 18: ...eld or portable devices and a value of 3 5 for larger stationary devices For example a 900 W angle grinder can be assumed to have a starting power demand of at least 1 2 900 W which equals 1 080 W Sim...

Страница 19: ...Normal Operation During normal operation use the following steps to stop your generator 1 Remove any connected loads from the control panel receptacles 2 Allow the generator to run at no load to redu...

Страница 20: ...tor to malfunction and could result in death or serious injury NOTICE Periodic maintenance intervals vary depending on generator operating conditions Operating the generator under severe conditions su...

Страница 21: ...muffler cover 4 Once the cover is removed locate the screw on the tip of the muffler and remove Pull the spark arrestor out of the muffler see Figure 15 Figure 15 Remove spark arrestor 5 If the spark...

Страница 22: ...Figure 18 below Figure 18 Oil Fill Plug Dipstick 6 Check oil level When checking the engine oil remove the oil fill plug dipstick and wipe it clean Thread the oil fill plug dipstick all the way back i...

Страница 23: ...apply slow but firm squeezing action 6 Rinse in clean water by submerging the air filter elements in fresh water and applying a slow squeezing action CHANGING ENGINE OIL 1 Always operate or maintain t...

Страница 24: ...ug boot by firmly pulling the plastic spark plug boot handle directly away from the engine see Figure 23 NOTICE Never apply any side load or move the spark plug laterally when removing the spark plug...

Страница 25: ...o loosen and remove all dirt on or around the engine s cooling fins Clean All Alternator Cooling Air Inlets and Exhaust Ports Make sure the cooling air inlets and exhaust ports of the alternator are f...

Страница 26: ...an come in contact with an ignition source such as a 1 pilot light of a stove water heater clothes dryer or any other gas appliance or 2 spark from an electric appliance NOTICE Gasoline stored for as...

Страница 27: ...ugged spark arrestor 9 Check and clean the spark arrestor 10 Stale fuel 10 Drain fuel and replace with fresh fuel 11 If trying 1 11 above does not solve the problem the cause might be the generator ha...

Страница 28: ...enerator Accessories call to order 210004 GENERATOR COVER 210003 WGC25 25 POWER CORD 210052 30A 6 BREAKER TRANSFER SWITCH KIT MODEL WHMTS30 210075 25 Cord 30AMP Transfer Switch 210076 50A 6 BREAKER TR...

Страница 29: ...IRE WGen5500 EXPLODED VIEW PART NO No Part Description 1 100533 FRAME 2 100552 ISOLATOR B 3 100553 ISOLATOR A 4 100551 NUT M10 5 180524 NUT M8 6 150507 CONNECTING PIPE 7 180563 BRACKET AIR CLEANER 8 1...

Страница 30: ...190418 CRANKCASE 2 180536 BALL BEARING 3 180504 OIL SEAL 4 190225 GOVERNOR ASSEMBLY 5 190410 SHAFT GOVERNOR ARM 6 190409 WASHER GOVERNOR ARM SHAFT 7 190408 PIN LOCK 8 180507 BOLT DRAIN PLUG 9 180508 W...

Страница 31: ...EL PIN CASE COVER 13 190407 PISTON 14 190406 PISTON RING SET 15 190405 ROD ASSEMBLY CONNECTING 16 190404 PIN PISTON 17 180791 CLIP PISTON 18 180534 COVER ASSEMBLY CRANKCASE 19 170502 CLIP 20 190417 CY...

Страница 32: ...32 Westinghouse Portable Power WGen5500 SCHEMATIC...

Страница 33: ...6 gal 25 L Run Time at 25 Load hrs 20 hrs Run Time at 50 Load hrs 15 hrs Gasoline Fuel Gauge Yes Choke type Manual Choke Location Above Air Filter AC Outlets 1 120 240V 30A L14 30R 2 Duplex 120V 20A G...

Страница 34: ...34 Westinghouse Portable Power Version 07 23 18KD...

Отзывы: