                                                               PA7300 Inverter Pump Quick Start Manual 
__________________________________________________________________ 

_______________________________________________________________ 

                                                                                           TECO – Westinghouse Motor Company 

3

 
 

Step 4

 - Check Pump Motor Operation 

 

Enter 

10.00Hz

 for the frequency reference and set parameter 

Sn-05 = 0010 

 to disable Reverse

 

Direction operation. 

Note

The output from the inverter is displayed in

 Hz

 as factory default. If 

desired, the output may be displayed in per cent 

(%)

 of full speed. 

(see appendix)

 

 

 

 

 

Press the 

RUN

 key, and check the pump direction of rotation. If the direction is not correct, press 

the 

STOP 

key and wait until the pump has come to a complete 

STOP.

 Next, 

Power Down the 

inverter.

 

    

 

   

Danger 

After the power has been turned OFF, wait at least 5 minutes until the charge 
indicator extinguishes completely before touching any wiring, circuit boards or 
components.  

 

Reverse any 

two

 of the pump motor connections at the inverter ( U(T1),V(T2), or W(T3) ). Next, 

following 

STEP 2, 

Power-up the inverter; the motor direction should now be correct. 

 

Step 5

 – Select Method of Control  

 

Before selecting the method of control, ensure the inverter is in the 

STOP

 mode. 

 

There are two methods of control or combinations thereof that may be selected; 

Keypad 

and 

Analog Signal.

  

 

        RUN / STOP Command - 

Can be provided from the keypad or from an external contact 

        

 (see Fig. 2a). 

           Speed Reference – 

Can be from the keypad or from an external analog signal (0 – 10 VDC or 

            4 – 20 mA).  see Fig’s 3a,3b, and 3c. 

 

 

The method of control is set by parameter 

Sn – 04.

 The table on the next page shows the value 

that 

Sn – 04

 needs to be set  for the various combinations of control.  

 
 

Содержание TECO PA7300 Series

Страница 1: ...PA7300 INVERTER SERIES Pump Quick Start Manual Rev 1 0 Nov 27th 2007...

Страница 2: ...rter Referring to the PA7300 Instruction Manual please review and verify that the correct inverter size for the motor was received free of damage To ensure personnel safety and to avoid equipment dama...

Страница 3: ...the power has been turned OFF wait at least 5 minutes until the charge indicator extinguishes completely before touching any wiring circuit boards or components Reverse any two of the pump motor conne...

Страница 4: ...elect the desired combination in Key to scroll to the digit position and the Press the to return to the output frequency display as in Fig 1 accordance with the table value press the Key to select the...

Страница 5: ...TOP START STOP SWITCH Connect shield to terminal E E Fig 2a Start Stop switch connection EXTERNAL FAULT CONTACT 24VG 1 2 3 3 E Connect shield to terminal E N O Fig 2b External Fault contact connection...

Страница 6: ...eed of the pump motor when External Analog is selected by Sn 04 in STEP 5 Only one method may be used as the input source with Fig 3a Potentiometer Input being most common Fig 3a Speed Control Potenti...

Страница 7: ...tinghouse Motor Company 7 PA7300 BLOCK DIAGRAM Fig 4 is an overall basic electrical connection diagram for the PA7300 It is used in conjunction with the other sections of this guide to give the user t...

Страница 8: ...ncy in Hz If desired the display can be changed to show the output frequency as a percentage of full speed To do this parameter Cn 20 must be changed from 00000 to 00001 as follows press the Key and t...

Страница 9: ......

Отзывы: