TYPE  048  FLEXITEST  SWITCHBOARD  METERS 

I.  L.  42-227 

Balance  Adjuster 

Light  Load  Adjuster 

FT-21 Case 

WARNING 

To  avoid  bodily  injury  and/or  propert y  damage,  it  is  recommended 
that  installation,  testing,  and  servicing  be  done  only  by  authorized 

personnel using appropriate installation procedures. 

GENE RAL 

The  meter  elements  are  mounted  on  a  removable  chassis, 

which  is  held  in  the  case  by  two  latches.  All  connections 

between  the  case  and  the  chassis  are  made  through  the 

test switches. 

CAUTION 

Automatic  shorting  switches are  provided  on all current  cir· 

cuits  to  prevent  opening  current  transformers  when  testing 
or  removing  the  chassis  to  avoid  electrical  shock  or  bodily· 
injury. 

For  testing,  leads  can  be  clipped  to  the  test  lugs  above  the 

chassis jaws  and on the switch  blades. 

All  rotors  are  supported  by  a  maintenance-free  Magne­
thrust  bearing  system  and  include  a  pinion  for  operating 
gear-driven  pulse initiators. 

Two  test  plugs  are  available to facilitate calibration of these 

meters.  A  10-circuit  plug  is  inserted  into  the  chassis  jaws 

and  is  provided  with binding  post  terminals  for  connections 
to  the  test  circuit.  Current  measurements  are  made  by 

connecting  ammeters  to  a  current circuit test plug, which  is 

then  inserted  into  the  current switcn  assembly, between  the 
chassis  and  the case. 

D4B-7F Chassis 

The  hardware  supplied  with  the  meter  permits  semi-flush 
mounting  on  panels  up  to  3/16  inch  thick.  For  projection 
mounting  on  panels  thicker  than  3/16  inch,  special  hard· 
ware  is  furnished  upon  request  (specify  panel  thickness). 

Provisions  have  been  made  on  all  FT-21  cases  for  con­

venient  field  installation  of  either  2- or  3-wire  pulse 

m1t1ators. 

Removal  of  three  knockouts  (located  in  the 

back  of  the  case  near  the  top)  will  permit  installation  of 

an  output  terminal  block  and  pin  assembly. 

A  mating 

bracket 

dnd 

socket 

assembly  is  then  attached  to  the 

meter  frame  and  latch  assembly. 

The  output  circuits 

will  be  closed  by  inserting  the  meter  frame  and  latch 

assembly  into  the  case.  All  necessary  parts  are  available  in 
kit  form  for  each  type  of pulse initiator. 

CA LIB RATION 

All  meters  have  been  factory  tested  before  shipment.  For 

single  stator  meters,  the  full  load  test  speed  is  16-2/3 rpm, 

and  the  watthour  constant  is  0.6  per  nominal  600-watt 
rating  (constant  of  7.2  for  30  amp,  240  volt  meter).  For 
two-stator  meters,  the  full  load  test  speed  is  8-1/3  rpm, 
and  the  watthour  constant  is  1.2  per  nominal  300-watt 
rating.  For  three-stator  meters,  the  full  load  test  speed  is 

8-1/3  rpm,  and  the  watthour  constant  is  1.8  per  nominal 
300-watt rating. 

Full  Load 

Single  stator  sensitivity  is  approximately  1.3  percent  per 
turn. 

Two- and  three-stator  sensitivity  is  approximately 

1.2  percent per turn. 

www 

. ElectricalPartManuals 

. com 

Содержание D48-F, D4B-2F, D4B-3F, D4B-7F, D48-SF

Страница 1: ...elta D4B 8F 2 Split Coil 3 Phase 4 Wire Wye All possible contingencies which may arise during installation operation or maintenance and all details and variations of this equipment do not purport to be covered by these instructions If further information is desired by purchaser regarding his particular installation operation or maintenance of his equipment the local Westinghouse Electric Corporati...

Страница 2: ...chassis and the case 1 D4B 7F Chassis The hardware supplied with the meter permits semi flush mounting on panels up to 3 16 inch thick For projection mounting on panels thicker than 3 16 inch special hard ware is furnished upon request specify panel thickness Provisions have been made on all FT 21 cases for con venient field installation of either 2 or 3 wire pulse m1t1ators Removal of three knock...

Страница 3: ...ate full load unity power factor to 100 percent registration by turning I L 42 227 the Full Load adjuster screw at the front of the meter Calibrate full load 50 percent lagging power factor to 1CO percent registration by turning the Power Factor adjuster screw on the rear stato1 adjuster bracket from the right side Energize the remaining two stators one at a time Calibrate full load unity power fa...

Страница 4: ...1 20 1 20 3 Wire Coil Each Half Watts Loss Volt Amps Mounting of FT 21 Case case dirnenslc PS p J nel cutout d1rncn Jons D4B 3F 2 5 Amps 120Volt 4 50 8 1 3 1 80 6 40 0 95 0 14 0 30 1 20 front view siJe VlCW sern1 flush prOJCCtton FT 21 I 4 5141 r lt 2B 2B r J 10 Circuit plug for test See Page I Order from Newark Relay as Style 1164046 Current circuit test plug See Page I Order from Newark Relay as...

Страница 5: ...N IIKNAL CHASStS iClltRt HT TOT I L J _ 10 4 9 l VOLTAGE TRANSFORMER CONNECTION BELOW Fig 3 Type 048 2 F 3 Phase 3 Wire I L 42 227 CIRCUIT CLOSifiiiG OEviCE cuRNENT TE T loi CIC OhtAHO IIIQTOf 8 lllt ACTOR WI H USE O 0A INTERNAL POW 111 SUPP _Y NOTE CIRQJIT CLOSING SWITCHES OPERAT O IY t ST WITCI1 HAND 8 ALSO 8T R MOIAlL 01 CHAS S EliTERNAL JI MPERS _ POTENTIAL TRANSFORMER CONNECTION BELOW L JI F ...

Страница 6: ...7 F 3 Phase 4 Wire Delta 0 Meter i L I I I I I I JtC T V P iOSING I I I L 42 227 T CIRCUIT CLOSING SWITCHES OPERATED BY TEST SWITCH HANDLE a _SO 8T R IIOVAL C7 CHASSIS 1fT RNAL JUMPERS 9 7 5 NEuTRAl VOLTAGE TRANSFORMER CONNECTION BELOW k t J_J 3 r REAR VIEW Fig 6 Type D48 7 F 3 Phase 4 Wire Delta CIIICllT Q OSIIIG Q yiC VOLTAGE TRANSFOAMER id COIIHECTION BELOW f r VIEW Fig 8 Type D48 2F 3 Phase 4 ...

Страница 7: ...E CIM I MT Cl OIM SWITCHE I OP 1U Tf D IT T H SWITCH HANOI a AlSO IY REMOVAL Of CHaa Fig 11 Type D4B 3F 3 Phase 4 WireWye 0 Meter Dt o J 4 WIM WY OM ftl fO IUT oo ll OIIr I Z J u Ulh c u 4 1 l Jio90 6 J 2 J A OuTICII 0 we 01 1 r a I i L x o o I r _ __ AC _ __ r rt I I I lO I I I i1 I i j H Cru r OI ooc I I i I hiO ___ JI I 7 I J j f I 4 i i 4 1 lo I o _ _j t f t e 0 I 0 0 IKMWIOf Fig 10 Type D4B 3...

Страница 8: ...lJI T CLOSINI S ITCHfl O f ATIO IY T IT IWtTCH HANOL e _SO IY llt WOYAL OFCHAit Fig 1 4 Type D4B 8F 3 Phase 4 WireWye withPhase Shifting Transformer I O t IAND WOTOR WH H USED 0R IIHERNAL POW R SUPPLY IO T CIRCUtr CLOSINOI SWITCtt S OPfRATEO BY TtST WITCH HANOL a ALSO eY REMOVAL Of CHASSIS Fig 15 Type D4B 8F 3 Phase 4 WireWye 0 Meter Westinghouse Electric Corporation Meter And Low Voltage Instrume...

Отзывы: