Replacing Parts

The Robonic Automatic Transfer Switch has been designed to have all
components accessible and readily removable from the front of the
panels. The Robonic Transfer Switch is divided into two basic sections.
The upper section consists of the main contacts and transfer mechanism,
the lower section consisting of all the automatic control devices.

Caution

When replacing any parts of the mechanism, control transformers or
breakers, isolate the Robonic Transfer Switch from any possible source
of power.

To remove the transfer mechanism of the LRO transfer switch, first
open the cover and remove the slide pin from the operating cam, then
remove the centre bolt, the mechanism will lift straight off. The breakers
and  transfer motor bracket are held by four screws for ease of removal
and replacement. When replacing the mechanism, first set it on the
Robonic with the breaker handles in the holes provided and then fasten
the centre bolt reasonably tight with the mechanism fully movable with
an equivalent swing distance up and down.

To remove the transfer mechanism of the RO transfer switch, remove
the four bolts holding it, taking note of which holes the bolts were in,
then lift the mechanism straight off. The breakers are held by two bolts
at one end and the bus connectors on the other end. The transfer motor
is mounted to the transfer mechanism cover and centre drive gear.
When replacing any part of the transfer mechanism, be sure that the
scribe lines of the gears are in a straight row (example shown on page 6).

To prevent operation of the transfer switch while replacing mechanism
or components, disconnect all sources of power.

When replacing the mechanism move it about until the breaker toggles
fit between the mechanism fingers and then fasten the bolts tightly. To
test for proper operation first operate manually and then connect 120
volt, 60 Hertz supply to motor leads and observe operation for free
movement and proper breaker operation.

The PRO transfer switch mechanism is similar to the RO with the
exception that the PRO mechanism has five gears and is mounted
horizontally. The breakers are fastened to the panel by six bolts.

All Robonic transfer switch breakers and mechanisms have allowed
some adjustments for mounting to assure proper operation without
slipping or binding. Be sure all hardware is tightened sufficiently before
re-energizing any transfer switch.

To replace any of the octal plug-ins relays, pull old units straight out
and insert the replacement unit. Due to the tight fit of the receptacle
and pins, you may have to move the relay about a little to pull it out.

DO NOT INTERCHANGE ANY RELAY WITH ANY OTHERS.

To replace any solid state logic modules, pull straight out and insert the
replacement unit.

Parts List

Part Name

Style No.

Parts Common to Robonic II

Plug-in Modules

Timer,1-60 sec. adjustable, for TDEN,TDEC,TDNE

1275C74G01

Timer,0.1-10 min. adjustable, for TDEN,TDEC,TDNE 1275C74G01
Timer,0.2-30 min. adjustable, for TDEN,TDEC,TDNE 1275C74G03
Timer, 5 min. adjustable, for TDEN,TDEC,TDNE

1275C74G08

Relay driver — used in place of timers, for
instantaneous operation

1266C77G02

Instantaneous relay, used for NR,ER and EC 1Ø
under frequency module, for “normal” or “emergency 1275C74G04
1Ø over frequency module, for “normal” or “ermergency” 1275C74G06
3Ø over voltage module, for “normal” or “emergency” 1266C79G01
1Ø over voltage module, for “normal” or “emergency” 1266C79G02
3Ø under voltage module, for “normal” or “emergency” 1266C79G03
1Ø under voltage module, for “normal” or “emergency” 1266C79G04
Blank cover, for unused module space

1266C77G01

Time delay relay for engine starting, 2.5s fixed

3152A51H01

Time delay relay for engine starting, adjustable 1-300s

688A886H11

Options

Plant Exerciser

688A888G01

Battery Charger 12V

1259C26G01

Battery Charger 24V

1259C26G03

4 Position s/s fixed

7070A56H01

4 Position s/s keyed

7070A56H02

Transformer Modules

Standard

Optional

600V, for LRO, RO

160D997G05

160D997G15

480V, for LRO, RO

160D997G04

160D997G14

416V, for LRO, RO

160D997G03

160D997G13

240V, for LRO, RO

160D997G02

160D997G12

208V, for LRO, RO

160D997G01

160D997G11

600V, for PRO

160D997G10

160D997G20

480V, for PRO

160D997G09

160D997G19

416V, for PRO

160D997G08

160D997G18

240V, for PRO

160D997G07

160D997G17

208V, for PRO

160D997G06

160D997G16

For Type LRO Robonic II

Mechanism

833C222G02

Motor Assembly

833C223G01

Motor

688A732H02

Operating Cam

688A458G01

Slide Pin

688A731H01

Limit Switch

688A747H01

For Type RO Robonic II

Mechanism 150 to 400A

833C226G01

Mechanism 600 to 1000A

833C226G01

Motor

688A749H01

Solenoid

688A740H01

Brake Shoe Assembly

688A738G01

Operating Cam

572B774H01

Auxiliary & Limit Switch

688A747H01

For Type PRO Robonic II

Mechanism

688A109G01

Motor

688A749H02

Solenoid

688A740H01

Auxiliary & Limit Switch

688A747H01

Содержание 30-471 (E)

Страница 1: ...ic II Automatic Transfer Switches Operation and Maintenance Manual Index Warranty 2 Westinghouse Offices 3 General Description 4 Component Identification 7 LRO Description 5 RO Description 6 PRO Description 6 Application Information 7 Logic Control 7 Replacing Parts 13 Trouble Shooting Guide 14 Recommended Maintenance 14 AUTOMATIC TRANSFER SWITCH ...

Страница 2: ...ted to the negligence of the Company it s employees or agents shall the Company be liable for special or consequential damages or damages for loss of use and on expiration of the Warranty period any liability of the Company shall terminate This constitutes the only warranty of the Company and no other warranty or condition statutory or otherwise shall be implied IMPORTANT Check equipment for shipp...

Страница 3: ...t you Utility Sales Offices Fredericton 454 6952 460 440King St Winnipeg 772 9906 1460 Ellice Acve Halifax 422 4441 720 Barrington St Tower Calgary 265 1204 707 324 8th Ave SW Montreal 842 2566 2723 1 Complexe Desjardins Edmonton 428 7540 516 10303 Jasper Ave Toronto 595 9551 1012 790 Bay St Burnaby 299 5566 6000 Lougheed Hwy Westinghouse Service Centres provide after sales service installation an...

Страница 4: ...1 2 3 on page 7 The information given in these tables is necessary for proper application Type B Robonics are equipped with standard thermal magnetic breakers which will provide the required overload and short circuit protection Type B Robonics can also be built using Seltronic or SCB breakers which could include ground fault tripping as well as overload and short circuit protection For applicatio...

Страница 5: ...operate The type LRO has three operating positions They are the normal breaker closed and the emergency breaker open the emergency breaker closed and the normal breaker open or both the normal and emergency breakers open but never both normal and emergency breakers closed The type LRO can also be easily manually operated Open the lever cover remove the slide pin and place it in the hole supplied i...

Страница 6: ...switch will seek the power available The various control components are described under the section titled Logic Control Type PRO Robonic II Automatic Transfer Switch Rated 1200 amperes through 3000 amperes at 600 volts Ac or 250 volts Dc The transfer mechanism consists of a transfer motor a gear train and two breaker operating cams Spur Gear Meshing Relationship bottom view of top cover The trans...

Страница 7: ...J or L K5 or R amps LRO 30 EB EHB FB HFB FB P 100 100 LRO 70 EB EHB FB HFB FB P 100 100 LRO 100 FB HFB 100 100 RO 150 CA CAH JA KA HKA LC HLC LA P 225 225 RO 200 DA LBB LB HLB LC HLC LA P 225 225 RO 225 DA LBB LB HLB LC HLC LA P 225 225 RO 300 DA LBB LB HLB LC HLC LA P 400 400 RO 400 LA HLA LC HLC NB P 400 400 RO 600 MA HMA MC HMC NB P 600 600 RO 800 NB HNB NC HMC PB PC PB P 800 RO 1000 PB PC PB P...

Страница 8: ...0 2 30 min timer S 1275C74G03 Option 1C 3C 4C 5 min fixed S 1275C74G08 Option 4D All can be used to accomplish TDEC and TDNE functions Relay Driver S 1266C77G02 Option 1A 1B 1C 3A 3B 3C 4A 4B 4C 4D This card is used in place of any of the timing modules when instantaneous operation is required Blank S 1266C77G01 Used to cover any unused card slots All Cards Mechanically Interlocked All cards are i...

Страница 9: ...Rotate Dropout Counterclockwise until LED is OFF 8 Drop line voltage to pull in desired value LED should come ON 9 Increase line voltage to desired Dropout value LED should go OFF DT and DTM Time Delay Relays Option 32A 32B Ratings 6 Watts Power Consumption Input coil Voltage 120 volts Contact Rating 3 amperes at 220 volts Ac 50 60 Hertz Operating Temperature Rating 10o C to 50o C Time Ratings Var...

Страница 10: ...day and night scale and has tabs around the periphery which may be adjusted to operate the micro switch within intervals each 24 hours Each tab represents a 15 minute interval Dial B has 7 spokes and advances one position for each revolution of Dial A Each spoke has provision to add a pin to operate the micro switch These pins represent days of the week and their function is to prevent operation o...

Страница 11: ...he interval it will cause the engine generator to shutdown INSTRUCTIONS TO OPERATE THE ENGINE FOR AN INTERVAL ONCE EACH WEEK WITH OR WITHOUT OPERATION OF THE TRANSFER SWITCH 1 Extend the tabs of Dial A outwards except those representing the time of day for the running of the engine or operation of the transfer switch 2 Determine the day of the week for this testing Install the six brass pins calle...

Страница 12: ...tor begins to operate First the normal interrupter is opened and then the emergency interrupter is closed At this point the ELS emergency limit switch contacts change state and the BS motor brake closes preventing TM over travel The NLS normal limit switch contacts change state in preparation for re transfer to the normal power source Upon return of stabilized normal power NR is re energized disab...

Страница 13: ...re proper operation without slipping or binding Be sure all hardware is tightened sufficiently before re energizing any transfer switch To replace any of the octal plug ins relays pull old units straight out and insert the replacement unit Due to the tight fit of the receptacle and pins you may have to move the relay about a little to pull it out DO NOT INTERCHANGE ANY RELAY WITH ANY OTHERS To rep...

Страница 14: ...e loctite 3 Check lubricant in high speed bearings of the motor and the low speed bearings of the gear box For lubrication use Dow Corning Silicon DC44 or equivalent on the high speed bearings and Aero Shell No 6 grease or equivalent in gear box after 5000 operations 4 Check if control components are tight in sockets 5 Periodically inspect all terminals load line and control for tightness Retighte...

Отзывы: