Installation Guide
5. Installation
5.2 Ultrastar Data60 Installation Procedure
Figure 16:
Front Rail Release Clip Operation
g.
Use a level to make sure that the rails are aligned properly.
h.
Follow these steps for the other outer rail.
Step 6 :
Install the rail mounting hardware, starting with the uppermost rack mounting hole of the 4U
space on the front of the rack.
a.
Install one cagenut at the uppermost mounting hole of the 4U space that the enclosure
will occupy.
b.
If the Ultrastar Data60 will be installed in a rack for shipping purposes, install four more
M5 cage nuts in the holes 3-6 of the 4U space. These will receive the M5 x 12mm T15 Flat
Head Torx screws that secure the enclosure to the rack with the shipping bracket.
43