Western Co Leonardo Off-Grid 4kW/3000/48 GE Py Скачать руководство пользователя страница 26

 

Leonardo Off-Grid 4kW/3000/48 GE 

User Manual

 

 

EN

 

 
 

EXTERNAL PROTECTION 

Protections for Alternating Current side 

Leonardo  Off-Grid  4kW/3000/48  GE

  is  equipped  with  an  AC-OUT  alternating  current  output  line  and  an  AC-IN 

alternating current input line. 
Since the device has a conductor connected to the NEUTRAL - TT system, the AC output line AC-OUT can be protected 
with a thermal-magnetic circuit breaker AC type, with nominal current In = 16A and differential current Id = 0.03 (usually 
this switch is already in the house switchboard as protection against indirect contact, with 30mA of differential current). 
The  input  line  into  alternating  current  AC-IN  can  be  protected  with  a  thermal-magnetic  circuit  breaker  AC  type,  with 
nominal current In = 16A and differential current Id = 0.3A, this switch can be put in an additional general switchboard 
or, if possible, in the existing switchboard of the house. 

Protections Direct Current side 

The battery bank is connected through a protective fuse to the positive pole, and the positive pole disconnection switch 
ensures that the inverter is activated in complete safety. 

 

ATTENTION: the battery fuse mounting accessories are designed for batteries that have fixing clamps with M8 bolts, 
in the case of different diameter of the fixing bolt it will not be possible to use the accessories supplied. If a different 
type of fuse is used, it must be sized correctly, otherwise the system may be impaired. 

 

Pic.5 Protection Fuse 

 

INVERTER CIRCUIT BREAKER 

The activation of the positive pole of the cutting switch provides the power of the inverter in complete safety. 

 

ATTENTION:  in  the  device  ON  sequence  the  circuit  breaker 
must  be  activated  ON  for  FIRST,  with  respect  to  the  PV 
connections and AC-IN and AC-OUT alternating current. 

In  the  device  OFF  sequence  of  the  device,  the  circuit  breaker 
must  be  deactivated  on  OFF  for  LAST,  compared  to  the  PV 
connections and AC-IN and AC-OUT alternating current.  

    

   

 

 

                Pic.6 Inverter circuit breaker 

Plastic nut 

Eyelet d.10mm 

300A fuse 

M8 round nut 

Eyelet d. 8mm 

Grain M8 x 60mm 

INVERTER cable 

PARALLEL 

BATTERY cable 

Содержание Leonardo Off-Grid 4kW/3000/48 GE Py

Страница 1: ...Leonardo Off Grid 4kW 3000 48 GE Manuale utente User manual IT EN...

Страница 2: ......

Страница 3: ...empre l energia erogata Collegando un gruppo elettrogeno all ingresso AC input il sistema garantisce la continuit di esercizio delle utenze senza percettibili discontinuit in caso di batteria scarica...

Страница 4: ...e contattare personale di manutenzione qualificato Assicurarsi che i cavi di collegamento siano dotati di fusibili e interruttori automatici Non sostituire mai un dispositivo di protezione con un comp...

Страница 5: ...sia insufficiente garantisce una continuit di servizio grazie al gruppo elettrogeno collegato all ingresso AC IN 5 un contatto pulito per l attivazione automatica permette l accensione del gruppo ele...

Страница 6: ...rno al Leonardo Off Grid provvede al controllo ed alla gestione del sistema inoltre fornisce una visualizzazione rapida dello stato di funzionamento del sistema Il Leonardo Data Logger esterno all app...

Страница 7: ...ontinua 3000 VA Potenza di sovraccarico 2500W Ingresso AC Batteria 48Vdc DATA LOGGER OPZIONALE Energia prodotta Energia prelevata Indice di indipendenza energetica BANCO BATTERIE Tensione di sistema 4...

Страница 8: ...di protezione sul polo positivo inoltre l interruttore di sezionamento del polo positivo provvede all attivazione dell inverter in completa sicurezza ATTENZIONE gli accessori di montaggio del fusibile...

Страница 9: ...ingressi indipendenti garantendo cos lo sfruttamento ottimale di tutta la potenza Tensione nominale batteria Caratteristiche moduli PV Batteria a 48V di tipo ermetico tensione di carica in fase di ten...

Страница 10: ...funzionamento Bypass Mode Fig 9 Segnalazione Bypass Mode Nel caso in Fig 9 infatti possibile notare lo stato di funzionamento dell inverter in modalit Bypass Mode il carico viene alimentato dal gruppo...

Страница 11: ...48V Potenza di uscita LOAD livello 3 la potenza elettrica delle utenze in uscita compresa in un intervallo di 2200W 4000W Stato di carica SOC livello 2 l energia effettivamente stoccata in batteria s...

Страница 12: ...erficie non infiammabile e posizionato in modo da lasciare uno spazio privo di ostacoli di almeno 10cm nell intorno del dispositivo che ne permette il raffreddamento per convezione forzata dell aria b...

Страница 13: ...tensione sul cavo in fase di funzionamento quindi una errata lettura della tensione di batteria La sezione dei cavi batteria di 25 mm2 Utilizzare il cavo in dotazione per effettuare il collegamento a...

Страница 14: ...4kW 5000 48 GE 4kW e corrente massima 80A 48V per il modello 8kW 8000 48 GE 3 il dispositivo Leonardo Off Grid contemporaneamente carica la batteria ed alimenta le utenze al fine di ridurre al minimo...

Страница 15: ...ER spenti Entrambi i Led Bypass e Inverter spenti Provvedere a resettare l inverter eseguendo la procedura come da manuale Ad inverter spento girare solo il sezionatore DC delle batterie e verificare...

Страница 16: ...Leonardo Off Grid 4kW 3000 48 SL Manuale utente IT 14 Schema Unifilare dell impianto trifase 9kW Fig 14 Schema Unifilare dell impianto trifase 9Kw...

Страница 17: ...NVERTER SLAVE L2 A Plug Sincronismo B Plug Sincronismo INVERTER SLAVE L3 A Plug Sincronismo B Plug Sincronismo INVERTER SLAVE L1 A Plug Sincronismo B Plug Sincronismo INVERTER SLAVE L2 A Plug Sincroni...

Страница 18: ...Leonardo Off Grid 4kW 3000 48 Manuale utente IT 16 CARATTERISTICHE MECCANICHE E PESO Leonardo Off Grid 4kW 3000 48 GE 25 kg Fig 17 Caratteristiche meccaniche...

Страница 19: ...eratura di esercizio Tamb 10 C 25 C 60 C 10 C 40 C 60 C 10 C 25 C 60 C 10 C 25 C 60 C PV CHARGER Min Tip Max Min Tip Max Min Tip Max Min Tip Max Tensione di batteria Vbatt 24 0V 48 0V 48 0V 48 0V Ingr...

Страница 20: ...in caso di danni derivanti da trasporto e o cattiva conservazione del prodotto causa di forza maggiore o eventi catastrofici gelo per temperature inferiori a 20 C incendio inondazioni fulmini atti van...

Страница 21: ...t of the PV module always maximizing the energy delivered By connecting a genset to the input AC input the system ensures continuity of operation of the users without perceptible discontinuity in case...

Страница 22: ...vented from accidentally being put into operation again contact qualified maintenance personnel Ensure that the connection cables are provided with fuses and circuit breakers Never replace a protectiv...

Страница 23: ...is insufficient it guarantees a continuity of service thanks to the genset connected to the AC IN input 5 a clean contact for automatic activation allows the switching on of the genset that manages t...

Страница 24: ...gy Manager inside the Leonardo Off Grid provides for the control and management of the system and also provides a quick view of the operating status of the system Leonardo Data Logger optional from th...

Страница 25: ...ERTER Continuous Power 3000 VA 2500W overload power AC input 48Vdc Battery OPTIONAL DATA LOGGER Produced energy Drawn energy Index of Energy independence BATTERY BENCH 48Vdc system voltage Recommended...

Страница 26: ...bank is connected through a protective fuse to the positive pole and the positive pole disconnection switch ensures that the inverter is activated in complete safety ATTENTION the battery fuse mounti...

Страница 27: ...d on four independent inputs in order to ensure the best use of the whole power Nominal battery voltage Features of PV modules 48V hermetic battery charging voltage in constant voltage phase ABSORPTIO...

Страница 28: ...evel of 40 then it switches to the operating mode Bypass Mode Pic 9 Bypass Mode signaling In the case in Pic 9 in fact it is possible to note the operating status of the inverter in mode Bypass Mode t...

Страница 29: ...ge higher than 48V Output Power LOAD level 3 the output electric power of the consumptions is in a range of 2200W 4000W SOC charge status level 2 the actually stored energy in the battery is in an int...

Страница 30: ...GE in a dry and adequately ventilated place fixed on a non combustible surface and positioned in order to have a space free of obstacles of at least 10 cm around the device so to have the cooling by f...

Страница 31: ...ease in the voltage drop on the cable during operation and therefore an incorrect reading of the battery voltage The battery cable section is 25 mm Use the supplied cable to make the connection to the...

Страница 32: ...0 48 GE 4kW and maximum current 80A 48V for model 8kW 8000 48 GE 3 the Leonardo Off Grid device simultaneously charges the battery and supplies the consumptions in order to reduce the genset set up ti...

Страница 33: ...ed are off Provide to reset the inverter performing the procedure in the manual When the inverter is turned off turn the DC switch of the batteries and check the starting of the BATTERY and INVERTER L...

Страница 34: ...Leonardo Off Grid 4kW 3000 48 SL User manual EN 14 Single phase diagram of the 9kW three phase system Pic 14 Single line diagram of the 9Kw three phase system...

Страница 35: ...L2 A Synchronous Plug B Synchronous Plug INVERTER SLAVE L3 A Synchronous Plug B Synchronous Plug INVERTER SLAVE L1 A Synchronous Plug B Synchronous Plug INVERTER SLAVE L2 A Synchronous Plug B Synchron...

Страница 36: ...Leonardo Off Grid 4kW 3000 48 GE User Manual EN 16 MECHANICAL FEATURES AND WEIGHT Leonardo Off Grid 4kW 3000 48 GE 25 kg Pic 17 Mechanical features...

Страница 37: ...5 C 65 C Operating temperature Tamb 10 C 25 C 60 C 10 C 40 C 60 C 10 C 25 C 60 C 10 C 25 C 60 C PV CHARGER Min Typ Max Min Typ Max Min Typ Max Min Typ Max Battery Voltage Vbatt 24 0V 48 0V 48 0V 48 0V...

Страница 38: ...also lapses in the case of damages deriving from transport and or bad preservation of the product cause of force majeure or catastrophic events freezing for temperatures below 20 C fire floods lightn...

Страница 39: ...i contenute nel presente documento sono vietati senza il consenso scritto di WESTERN CO Srl This document is the property of WESTERN CO Srl All rights are reserved Reproduction and use of information...

Страница 40: ......

Отзывы: