Страница 3: ...onsible for any loss of data or income or any special incidental and consequential or indirect damages howsoever caused More information about Westermo can be found at www westermo com License and copyright for included Free Libre Open Source Software This product includes software developed by third parties including Free Libre Open Source Software FLOSS The specific license terms and copyright a...

Страница 4: ...a potentially hazardous situation Possible death or major injury Major damage to the product CAUTION Indicates a potentially hazardous situation Minor or moderate injury Moderate damage to the product NOTICE Provides information in order to avoid misuse of the product confusion or misunderstanding No personal injury Minor damage to the product NOTE Used for highlighting general but important infor...

Страница 5: ...ousings Westermo recommends a cross sectional area of at least 4 mm2 Upon removal of the product ensure that the protective earthing conductor is disconnected last WARNING HAZARDOUS VOLTAGE Do not open an energized product Hazardous voltage may occur when connected to a power supply WARNING PROTECTIVE FUSE The power supply wiring must be sufficiently fused It must be possible to disconnect manuall...

Страница 6: ...t high temperatures the external surface may exceed Touch Temperature Limit according to the product s relevant electrical safety standard CAUTION ELECTROSTATIC DISCHARGE ESD Prevent electrostatic discharge damages to internal electronic parts by discharging your body to a grounding point e g use a wrist strap ...

Страница 7: ...rking properly contact the place of purchase nearest Westermo distributor office or Westermo technical support Product disposal This symbol means that the product shall not be treated as unsorted municipal waste when disposing of it It needs to be handed over to an applicable collection point for recycling electrical and electronic equipment By ensuring this product is disposed of correctly you wi...

Страница 8: ... FCC Part 15 105 Notice This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the ins...

Страница 9: ...ps and interruption EN 50155 DC power ports 10 ms interruption 100 ms 40 voltage variation Radiated emission CISPR 16 2 3 ANSI C63 4 FCC part 15 Enclosure Class B 30 6000 MHz Conducted emission CISPR 16 2 1 DC power port Ethernet ports Class B Dielectric strength EN 50155 Ethernet ports to other isolated ports 500 VAC 1 min Power Fault port to other isolated ports 1500 VAC 1 min Temperature EN 600...

Страница 10: ... 6 shocks Shock sawtooth IEC 60068 2 27 Cat 1 class B IEEE1478 2001 Operating Vertical 100 m s2 Transverse 100 m s2 Longitudinal 100 m s2 11 ms 3 x 6 shocks Enclosure UL 94 Nickel coated zinc Flammability class V 1 Dimension W x H x D 175 x 100 x 50 mm Weight 0 9 kg Degree of protection IEC 529 Enclosure IP 65 when all ports are protected connected Cooling Convection Mounting Wall mounted ...

Страница 11: ...when all ports are protected connected Our unique FRNT Fast Recovery of Network Topology technology is the fastest protocol on the market to reconfigure a network in the event of any failure of a link or hardware Real time properties are implemented in order to achieve determinism for real time critical applications Viper 408 supports QoS Quality of Service with four priority queues and strict pri...

Страница 12: ... supply lines fault relay signals are also contained within PWR Connection 4 pin male M12 connector with A code Connector size M12 recommended cable area 0 5 mm2 recommended minimum 0 25 mm2 cable dimensions depend on choice of M12 connector Shielded cable Not required twisted pair is recommended Fault relay resistance 10 Ω Operating voltage Up to 110 VDC Max continuous current 250 mA If external ...

Страница 13: ...that has link alarm enabled Redundancy Mode activated i e one or more FRNT link is down Description of how connection to the fault contact could be done is shown below The relay is closed when the unit is OK and open at failure The relay is of semiconductor type no moving parts It is specified for max current 250 mA continuous 500 mA peak 10 ms operational voltage up to 110 V protected by a 150 VD...

Страница 14: ...00 VAC PWR 1500 VAC Galvanic connection to None except for shielded contact to housing Connection 4 pole M12 female with D code Shielded cable Not required twisted pair is recommended Conductive housing Nickel plated zinc metal housings of X1 X8 also connected to the housing Number of ports 8 Ethernet X1 X8 Position Direction Description 1 Out Transmit Data 2 In Receive Data 3 Out Transmit Data 4 ...

Страница 15: ... not supported GREEN FRNT is running and the switch is configured as member switch in the ring GREEN FLASH FRNT is running and the switch is configured as Focal Point RED FRNT Error ST1 GREEN Indicates STP root ST2 NC X1 to X8 OFF No Link GREEN Link is up GREEN FLASH Data is transmitted YELLOW ON Port larm and no link If RSTP FRNT mode are activated port is blocked X1 X2 X6 X3 X7 PWR SERVICE X4 X8...

Страница 16: ... address of the unit is valid in the connected network it is possible to access the unit directly from a web browser Change local IP address The local address of Viper can be configured using the IP Configuration tool then it is possible to browse into the unit for further configuration The IP Configuration program is available on the CD or for download from the Westermo web page http www westermo...

Страница 17: ... you would like to quit Click the OK button figure 4 and you will be back to the main view of the IP Configuration program see figure 1 Click the Scan for switches button again and the settings you configured will appear in the list Now you can access the Viper via the browser for further configuration by clicking the unit with an IP address that fits your subnet Figure 2 will appear and when you ...

Страница 18: ... can be used in the login The following characters are not valid ASCII 34 ASCII 35 ASCII 39 ASCII 40 ASCII 92 Figure 5 Log in via Web You will be prompted with a Login screen where the default settings for Username and Password are Username admin Password westermo Westermo location Provided by Westermo http 192 168 2 220 conf p cgi Google File Edit View Favorites Tools Help Home Print Page Tools W...

Страница 19: ...obstructing the airflow around the unit Spacing is recommended for the use of unit in full operating temperature range and service life Mounting There are four 6 mm bore holes intended for mounting the unit The unit can be mounted vertical or horizontal The unit is wall mounted X1 X2 X6 X3 X7 PWR SERVICE X4 X8 X5 FRNT ST1 ST2 ...

Страница 20: ...you have any doubts whether the reset is performed or not do NOT unplug the power supply wait for confirmation according to step 5 1 Disconnect the power 2 Connect cables between port x1 x6 and port x2 x5 3 Apply power 4 Wait for approx imately 90 seconds Some LED will flash during start up 5 When the Green LED s on all Ethernet ports are constantly on then remove the cables connected to port x1 x...