Fault Contact

The Viper switch is equipped with a potential free normally closed fault contact. 
The fault contact is a solid state component (relay) that requires power to work and it 
is transient protected. Additionally, the fault contact is opened when any of the following 
conditions is met:

No voltage on the power supply pin, a voltage level outside the legal voltage range 

• 

or current limitation on the voltage source is applied on the power input.
Link alarm i.e. missing link on any Ethernet port that has link alarm enabled. 

• 

Redundancy Mode activated i.e. one or more FRNT link is down.

• 
Description of how connection to the fault contact could be done is shown below.  
The relay is closed when the unit is OK and open at failure. The relay is of semiconduc-
tor type (no moving parts). It is specified for max current 250 mA continuous,  
500 mA peak (10 ms), operational voltage up to 110 V, protected by a 150 VDC-varistor, 
ON-resistance less than 10 Ohm, and leakage current max 1 µA.

External relay

+24/48 VDC

+

1 k

0V

Viper

2

2

4

4

Viper

To logic input

Input on PLC

Service port

The Service Port should not be used by non other than the Westermo Technical Support 
team. Do not connect any device or cable to the Service Port.

Содержание Viper 108

Страница 1: ...Managed 8 port Ethernet Switch www westermo com Westermo Teleindustri AB User Guide 6641 2201 Viper 1 0 8 a n d 4 0 8 ...

Страница 2: ...icular purpose are made in relation to the accuracy and reliability or contents of this document Westermo reserves the right to revise this document or withdraw it at any time without prior notice Under no circumstances shall Westermo be responsible for any loss of data or income or any special incidental and consequential or indirect damages howsoever caused More information about Westermo can be...

Страница 3: ...ithin this unit when connected to power supply Care recommendations Follow the care recommendations below to maintain full operation of unit and to fulfil the warranty obligations This unit must not be operating with removed covers or lids Do not attempt to disassemble the unit There are no user serviceable parts inside Do not drop knock or shake the unit rough handling above the specification may...

Страница 4: ...nt to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occu...

Страница 5: ...EN 55022 Information technology equipment Radio disturbance characteristics Limits and methods of measurement 2006 A1 2007 EN 55024 Information technology equipment Immunity characteristics Limits and methods of measurement 1998 A1 2001 A2 2003 EN 61000 6 1 Electromagnetic compatibility Generic standards Immunity for residential commercial and light industrial environments 2007 EN 61000 6 2 Electr...

Страница 6: ... 10 ms interruption 100 ms 40 voltage variation Radiated emission EN 55022 Enclosure Class B FCC part 15 Class B Conducted emission EN 55022 DC power port Ethernet ports Class B FCC part 15 DC power port Class B Dielectric strength EN 50155 Ethernet ports to other isolated ports 707 VDC 1 min Power Fault port to other isolated ports 2121 VDC 1 min Temperature Operating 40 to 70ºC Storage Transport...

Страница 7: ...cks Shock sawtooth IEC 60068 2 27 Cat 1 class B IEEE1478 2001 Operating Vertical 100 m s2 Transverse 100 m s2 Longitudinal 100 m s2 11 ms 3 x 6 shocks Enclosure UL 94 Nickel coated zinc Flammability class V 1 Dimension W x H x D 175 x 100 x 50 mm Weight 0 8 kg Degree of protection IEC 529 Enclosure IP 65 when all ports are protected connected else IP 40 Cooling Convection Mounting Wall mounted ...

Страница 8: ...n when all ports are protected connected else IP 40 Our unique FRNT Fast Recovery of Network Topology technol ogy is the fastest protocol on the market to re configure a network in the event of any failure of a link or hardware Real time properties are implemented in the Viper108 and 408 in order to achieve determinism for real time critical applications The Viper switches supports QoS Quality of ...

Страница 9: ...nes fault relay signals are also contained within PWR Connection 4 pin male M12 connector with A code Connector size M12 recommended cable area 0 5 mm2 recommended minimum 0 25 mm2 cable dimensions depend on choice of M12 connector Shielded cable Not required twisted pair is recommended Fault relay resistance 10 Ω Operating voltage Up to 110 VDC Max continuous current 250 mA If external power supp...

Страница 10: ...that has link alarm enabled Redundancy Mode activated i e one or more FRNT link is down Description of how connection to the fault contact could be done is shown below The relay is closed when the unit is OK and open at failure The relay is of semiconduc tor type no moving parts It is specified for max current 250 mA continuous 500 mA peak 10 ms operational voltage up to 110 V protected by a 150 V...

Страница 11: ...00 VAC PWR 1500 VAC Galvanic connection to None except for shielded contact to housing Connection 4 pole M12 female with D code Shielded cable Not required twisted pair is recommended Conductive housing Nickel plated zinc metal housings of X1 X8 also connected to the housing Number of ports 8 Ethernet X1 X8 Position Direction Description 1 Out Transmit Data 2 In Receive Data 3 Out Transmit Data 4 ...

Страница 12: ...r not supported GREEN FRNT is running and the switch is configured as member switch in the ring GREEN FLASH FRNT is running and the switch is configured as Focal Point RED FRNT Error ST1 GREEN Indicates STP root ST2 NC X1 to X8 OFF No Link GREEN Link is up GREEN FLASH Data is transmitted YELLOW ON Port larm and no link If RSTP FRNT mode are activated port is blocked X1 X2 X6 X3 X7 PWR SERVICE X4 X...

Страница 13: ...it is possible to browse into the unit for further configuration The IP Configuration program is available on the CD or for download from the WESTERMO web page http www westermo com choose Downloads Software Ethernet Ethernet switches Name IP config Westermo zip Install the software and start the application from a PC on the network connected to the same network as the Viper Make sure that the Def...

Страница 14: ...ick the Close button to get back to main view You will then be asked if you would like to quit Click the OK button figure 4 and you will be back to the main view of the IP Configuration program see figure 1 Click the Scan for switches button again and the settings you configured will appear in the list Now you can access the Viper via the browser for further configuration by clicking the unit with...

Страница 15: ...e used in the login Note For login the following characters are not valid ASCII 34 ASCII 35 ASCII 39 ASCII 40 ASCII 92 Figure 5 Log in via Web You will be prompted with a Login screen where the default settings for Username and Password are Username admin Password westermo Westermo location Provided by Westermo UK http 192 168 2 200 conf p cgi Google File Edit View Favorites Tools Help Home Print ...

Страница 16: ...obstructing the airflow around the unit Spacing is recommended for the use of unit in full operating temperature range and service life Mounting There are four 6 mm bore holes intended for mounting the unit The unit can be mount ed vertical or horizontal The unit is wall mounted X1 X2 X6 X3 X7 PWR SERVICE X4 X8 X5 FRNT ST1 ST2 ...

Страница 17: ...you have any doubts whether the reset is performed or not do NOT unplug the power supply wait for confirmation according to step 5 1 Disconnect the power 2 Connect cables between port x1 x6 and port x2 x5 3 Apply power 4 Wait for approx imately 90 seconds Some LED will flash during start up 5 When the Green LED s on all Ethernet ports are constantly on then remove the cables connected to port x1 x...

Страница 18: ...8 6641 2201 175 1 164 1 142 1 56 1 22 1 100 1 6 5 0 2 4x M5 3 9 0 3 41 5 1 53 4 1 22 7 1 Min 4 0 Max 7 5 0 4 35 5 51 66 5 82 97 5 0 0 4 18 8 37 2 28 55 6 Dimensions Measurements are stated in millimeters ...

Страница 19: ......

Страница 20: ...rmo de www westermo de Austria Westermo Data Communications Tel 43 0 72030 3920 Fax 43 0 2235 86131 info westermo at www westermo at France Westermo Data Communications Bat A 9 Chemin de Chilly FR 91160 Champlan Tel 33 1 69 10 21 00 Fax 33 1 69 10 21 01 infos westermo fr www westermo fr North America Westermo Data Communications 939 N Plum Grove Road Suite F IL 60173 Schaumburg USA Tel 1 847 619 6...

Отзывы: