5. SPECIFICATIONS
5.1 Voltage
+/-24 or +/-48 Vdc
+/-22 to +/- 58Vdc Max.
5.2 Fuse size
125 Amps Max per fuse*
125
Amps
Max
(TLS)*
70
Amps
Max
(TPS)*
5.3. Current/Input
125 Amps Max.**
5.4. Current/Panel
500 Amps Max.**
5.5. Power
13 Watts per position
Dissipation
(at max load)
5.6. Input Blocks
Two ¼” studs on
5/8”
centers
(Torque
3ft-lbs)
5.7. Output Blocks
Two ¼” studs on
5/8”
centers
(Torque
3ft-lbs)
5.8. Alarm Block
0.045” sq wire-wrap pins
5.9. Alarm Fuses
1 Amp Max (GMT)
(GMT18/100A
referred)
5.10. Dimensions
1.75”H, 17”W, 11”D
5.11. Mounting
19” and 23” Racks
1.75”
and
1”
Spacing
5.12. Weight
Approx 11 lbs
5.13. Operating
-40 to +50 C (ambient)
Temperature
(-40 to 131 F)
5.14. Color
Off-White
5.15. Relay current
1Amp/58Vdc max
*We recommend that you size fuses such that they do
not run at more than 70% of their rating. Thus a 70A fuse
should not be run at more than 49 A.
**The sum of the fuse ratings must not exceed the
panels rating.
Compatible lugs for Input and Output Blocks
(2 hole compression lugs for 1/4” studs on 5/8” centers (torque 3ft-lbs)).
Cable Size
T & B
Burndy
Panduit
#8 542040410
YA8CL2TC14
LCD8-14A
#6 54205
YA6CL2TC14
LCD6-14A
#4 54206
YA4CL2TC14
LCD4-14A
#2 54207
YA2CL2TC14
LCD2-14A
We suggest you heat shrink the barrels of the compression lugs for added safety.
NOTE:
If fuse size is not specified in the
equipment manual, fuses should be selected
such that they do not run at more than 70%
of their rating. When installing fuses, the
sum of the fuses installed in the panel should
not exceed the panel’s rating (500 Amps) or
input fuse rating.