1. GENERAL DESCRIPTION

 

1.1.  The Noran Tel NPGMT1012 Fuse Panel 
provides up to 30 circuits for the distribution of DC 
power to equipment.  Each of the 30 circuits is 
individually protected by a GMT style 
telecommunication fuse (20A max) located on the 
panel's faceplate. Alarm circuits are provided to 
indicate and extend alarm conditions when faults 
occur.  Normal Operation LEDs are provided to 
indicate the status of each bus in the panel. 
 
1.2.  Input wiring is connected to a high current, 2-
hole lug input block located at the rear of the 
panel.  Each group of fuses or bus has its own 
completely isolated inputs, allowing the 
distribution of two battery voltages through the 
same panel.   
 
1.3.  The power is distributed to the load side 
equipment through GMT style fuses. There are 15 
fuses per fuse group and two groups per panel.  
Each fuse position is available for installer 
connection at the rear of the panel.  A designation 
card is provided for keeping records of which 
position is connected to which equipment and 
what amperage is to be used. 
 

1.4.  Alarm circuits are provided to alert service 
personnel of fault conditions. A fuse alarm is a 
blown fuse within a given bus. A red fuse alarm 
LED

!

on the faceplate will illuminate when 

a fuse alarm condition is present. As well, the 
green Normal Operation LED 

9

 will extinguish 

to signal a fuse alarm or input power failure and 
the appropriate relay contacts will change 
states.  These fuse panels have common (C), 
normally open (NO) and normally closed (NC) 
terminals for alarms.  Note, the use of the alarm 
contacts is optional, if you do not wish to extend 
the alarms, you don’t have to do anything with 
the alarm pins. The “Normal” condition of the 
relay exists when the panel is powered up 
without any blown fuses.  

The local alarm LEDs 

are located on the front of the panel as shown in 
Figure 1.4.1 
 

LED SYMBOL 

SIGNIFICANCE 

GREEN

 

9

 

NORMAL OPERATION 

RED

 

!

 

BLOWN FUSE

 

1

2

3

13

14

15

C:\Documents and Settings\sdolinsky\Desktop\Westell_By_Noran_Tel_RED.bmp

20A MAX FUSE

C:\Projects\Other\Logos\westellc_transparent.gif

Noran Tel

By

9

9

!

Ì

!

Ì

10

20

12

 

Figure 1.4.1

 

 

1.5.  These Fuse Panels are made from 0.050" 
steel and painted off-white. Single rack

 

height 

panels are shipped with universal brackets (1” & 
1-3/4” spacing) that will fit both 19" and 23" wide 
racks and use only one 1.75" panel space.  The 
panel has a clear L shaped plastic shield  to 
protect the wiring connections on the back of the 
panel. The panel is shipped with 30 dummy fuses.

 

 

2.  APPLICATION

 

2.1.  The NPGMT1012 Fuse Panels are designed 
to be used in the distribution of DC power.  They 
are rack mount panels that can provide fused DC 
power to up to 30 individual circuits, or 15 pieces 
of equipment, providing redundant battery feeds 
to each.   

 

2.2  The NPGMT family fuse panels are suitable 
for installation as part of a Common Bonding 
Network (CBN). As well, this family of fuse panels 
is suitable for restricted access locations in 
Network Telecommunications Facilities and OSP. 

 

3.  CIRCUIT DESCRIPTION

 

3.1.  Power is connected to the fuse panel via ¼” 
studs on 5/8” centers located at the rear of the 
panel (torque 5.5 ft-lbs).  These inputs are high 
current stud blocks that supply current to the fuse 
panel. Connect the battery return cable to the stud 
input that is labeled “RTN” and the Battery supply 
cable to the terminals labeled “BAT”.  
 
3.2. Distribution of current from each bus is 
provided by GMT style fuses.  Each bus has 15 
fuse holders for distribution, the fuses are labeled 
1 to 15 on each bus.  Each fuse position is made 
available at the rear of the fuse panel.  Maximum 
fuse size allowed in each position is 20 Amps, 
provided the maximum bus current or BDFB fuse 

Содержание NPGMT1012

Страница 1: ...e at 200 Amps of output current per panel 100 Amps per Bus Barrier terminal strips for fused outputs and isolated returns grounds Two sets of Form C relay contacts are provided to extend alarms One se...

Страница 2: ...of the relay exists when the panel is powered up without any blown fuses The local alarm LEDs are located on the front of the panel as shown in Figure 1 4 1 LED SYMBOL SIGNIFICANCE GREEN 9 NORMAL OPE...

Страница 3: ...can be mounted so the panel can be installed for a flush mounting or 5 offset Adjust the position and orientation of the correct mounting brackets on the fuse panel such that it will fit the rack you...

Страница 4: ...d be electrically connected to the rack ground From step 4 3 the panel should already be ground to the rack via the 12 24 thread forming rack screws and outside tooth lock washers In addition to groun...

Страница 5: ...00 Amps Max 5 5 Output Fuse GMT Style Fuse Holders 5 6 Output Bus 15 Fuses 30 per panel 5 7 Output Panel 2 Busses per Panel 5 8 Input Block Two Studs on 5 8 centers Max std lug is 1 AWG Max lug width...

Страница 6: ...Be sure to have the model number and serial number available when making inquiries about the equipment 7 WARRANTY REPAIRS 7 1 Westell warrants this product to be free of defects at the time of shipme...

Страница 7: ...___________________________________________________________________________________ 7 Noran Tel Mounting Options 5 OFFSET MOUNTING FLUSH MOUNTING...

Страница 8: ...12 13 14 15 1 2 3 4 6 5 7 8 11 9 10 12 13 14 15 BAT RTN BAT RTN A B 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 POS 48 VDC NEG 24 VDC POS 48 VDC NEG 24 VDC 13 14 15 C Documents and...

Страница 9: ...___________________________________________________________________________________ 9...

Отзывы: