background image

Section DTW‐A52‐802‐202

030‐101665 Rev. C

R

3

1205I2RC

Wall-Mount Keyhole

Customer Side

Figure 3.   Top View of 528‐02I2 Interior (Cover Open for Visual Clarity), Typical Wall‐Mounted Position

Terminal Block*

Network Side

Terminal Block*

(Total of 4)

* List option 4-9 contains

wirewrap pin headers

instead of screw

terminals.

Shorting Bar/

Ground Jumper

RJ48C/S Switch

Power/Ground

Terminal Block

RJ48C/S Switch

Ckt 1

Ckt 2

Figure 4.   528‐02I2 Interior, Cover Open, Typical Table­

top Mount Position

Hinged Cover, 

Access

Card Guides

2 56‐pin Card

See‐through

Switch, CKT2

For Modules

RJ Jack,

Accessible

Rear‐

Customer

Network 

Power/Ground
Terminal Strip

S2, JR48C/S

Terminal Block*

Edge Connectors

J2,

Ribbon Cable

RJ48S

RJ48C

CKT

 2

Customer
Terminal Block*

Switch, CKT1

S1, RJ48C/S

RJ48S

RJ48C

CKT

 1

Module

Opens For

To Wiring

Wiring Label

Window

* The List 4‐9 option contains wirewrap pins instead of screw terminals.

Earth ground as stated in Paragraph 2.5. CIRCUIT GND must
be connected to an earth ground regardless of the power
source. Use 24 AWG or greater  insulated wire  (see Figure 7).

The ‐PWR position is used to connect the negative terminal
from the power supply.

2.5

Frame Ground Connections

The metal housing can be connected to earth ground by using
one of the methods below. On some units, this optional strap is
provided in the parts bag, and on the DTMA528‐02I2L4 it is
factory installed.

S

Exterior Frame Ground Lug on Rear of Assembly
(Preferred Method).

 A frame ground lug, labeled FRAME

GND, is provided on the rear of the metal housing. This
lug should be used to connect the metal housing to earth
ground.

S

Interior TB5 Frame Ground Screw Terminal (Inside
Assembly).

 A frame ground screw terminal, labeled TB5,

located inside the assembly can be used as an optional
method for earth grounding the metal housing (Figure 3
and Figure 8) when local power is supplied.

S

Optional Interior TB5 Removable Ground Strap. 

The

528‐02I2 features a factory‐assembled, pre‐installed,
ground strap for applications requiring frame ground to
be connected to circuit ground. The strap is connected
across TB5's FRAME GND and CIRCUIT GND termi­
nals. On some units, this optional strap is provided, but
not factory‐installed.

3.

INSTALLATION

The assembly should be installed by authorized, trained person­
nel only. This assembly is for use with NEBS‐certified 200
MECHANICS

r

 or 400‐type cards. Installation consists of in­

specting the assembly for damage, selecting the mounting site or
location, gathering all necessary tools and hardware, mounting